Specifications for Optional Power Supply Products
This section explains the specifications of optional power cords and power related optional products.
For power distribution units, the number of outlets that are required to connect the frontend enclosure, control-
ler enclosures, and drive enclosures should be taken into consideration, and the most appropriate power distri-
bution units should then be selected.
When an existing power socket is used, make sure that the plug type of the power distribution unit fits the exist-
ing power socket and that the power supply facility is able to provide sufficient power to the system. If the plug
type does not fit the power socket, electrical work to change the power socket is required. This electrical work
must be performed in compliance with the electrical codes of the nation, the municipality, or the region.
■
AC200V Power Cords (for the EMEIA, Central American, and Caribbean Regions)
AC200V power cords are used to connect devices to the IEC60320 C13 power socket type. These power cords can
be used if the specifications of the connection device allow AC200V.
Table 11 Specifications for AC200V Power Cords (for the EMEIA, Central American, and Caribbean Regions)
Usage
Plug type
Socket type
(Socket)
Cable length
Voltage rating/current
rating
Used for connection be-
tween the ETERNUS DX
and the socket
(IEC60320 C13
n
IEC60320 C14G)
IEC60320 C14G
IEC60320 C13
1.5m
250V 10A
■
AC200V Power Cords (for Regions other than the EMEIA, Central American, and Caribbean
Regions)
AC200V power cords are used to connect devices to the NEMA L6-15R power socket type. These power cords can
be used if the specifications of the connection device allow AC200V.
Table 12 Specifications for AC200V Power Cords (for Regions other than the EMEIA, Central American, and Carib-
bean Regions)
Usage
Plug type
Socket type
(Socket)
Cable length
Voltage rating/current
rating
Used for connection be-
tween the ETERNUS DX
and the socket
(IEC60320 C13
n
NEMA
L6-15P)
NEMA L6-15P
NEMA L6-15R
4.0m
Rating: 250V 10A
(Normal usage rating:
8A)
1. ETERNUS DX Installation