1. ETERNUS DX Installation
This chapter provides the installation specification of the ETERNUS DX.
Installation Specifications
ETERNUS DX8100 S3
The following table shows the installation specifications of the ETERNUS DX8100 S3.
Table 1 ETERNUS DX8100 S3 Installation Specifications
Item
ETERNUS DX8100 S3
Dimensions
(W
´
D
´
H)
Controller enclosure
482
´
809
´
133mm (3U)
Drive enclosure
2.5" type
482
´
540
´
88mm (2U)
3.5" type
482
´
560
´
88mm (2U)
Power distribution unit (*1)
Horizontal type
485
´
280
´
43mm
´
2 (2U) (*2),
485
´
123
´
44mm
´
2 (2U) (*3)
Maximum weight Controller enclosure
54kg
Drive enclosure (*4)
2.5" type
35kg
3.5" type
35kg
Power distribution unit (*1)
Horizontal type
(6.0kg)
´
2 (*2),
(3.0kg)
´
2 (*3)
Power
Voltage
AC 100 – 120V, AC 200 – 240V
Phase
Single
Frequency
50Hz/60Hz
Maximum power
consumption
Controller enclosure
AC 100 – 120V
870W (880VA)
AC 200 – 240V
870W (880VA)
Drive enclosure
(*4)
2.5" type
AC 100 – 120V
430W (440VA)
AC 200 – 240V
430W (440VA)
3.5" type
AC 100 – 120V
340W (350VA)
AC 200 – 240V
340W (350VA)
Maximum heat
generation
Controller enclosure
AC 100 – 120V
3,120kJ/h
AC 200 – 240V
3,120kJ/h
Drive enclosure
(*4)
2.5" type
AC 100 – 120V
1,600kJ/h
AC 200 – 240V
1,600kJ/h
3.5" type
AC 100 – 120V
1,300kJ/h
AC 200 – 240V
1,300kJ/h
Maximum
amount of ex-
haust air
Controller enclosure
6.2m
3
/min
Drive enclosure (*4)
2.5" type
4.0m
3
/min
3.5" type
4.0m
3
/min
10
FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide
Copyright 2020 FUJITSU LIMITED
P3AM-9422-13ENZ0
Summary of Contents for ETERNUS DX8100 S3
Page 81: ......