![Fujitsu B24LDC Service Instruction Download Page 41](http://html.mh-extra.com/html/fujitsu/b24ldc/b24ldc_service-instruction_2343847041.webp)
Summary of R407C and R410A characteristics
Pressure (Mpa) Temp ( C)
2.20
37.9
2.25
38.7
2.30
39.6
2.35
40.5
2.40
41.3
2.45
42.1
2.55
43.8
2.60
44.6
2.65
45.3
2.70
46.1
2.75
46.8
2.80
47.6
2.85
48.3
2.90
49.0
2.95
49.8
3.00
50.5
3.05
51.2
3.10
51.9
3.15
52.6
3.20
53.2
3.25
53.9
3.30
54.6
3.35
55.3
3.40
55.9
3.45
56.5
3.50
57.1
2.55
57.8
3.60
58.4
3.65
59.0
3.70
59.6
3.75
60.2
3.80
60.8
3.85
61.4
3.90
52.0
3.95
62.5
4.00
63.1
4.05
63.6
4.10
64.2
4.15
64.8
Temp ( C) Pressure (Mpa)
39
2.27
40
2.32
41
2.38
42
2.44
44
2.57
45
2.63
46
2.69
47
2.76
48
2.83
49
2.90
51
3.04
52
3.11
53
3.18
54
3.26
56
3.41
57
3.49
58
3.57
59
3.65
61
3.82
62
3.90
63
3.99
64
4.08
Desighed pressure of R410A refrigerant
< Pressure Temp >
Relation between R410A condensing temperature and saturated pressure.
< Temp Pressure >
Advantage
Disadvantage
Suitable for
R410A
higher system
performance
Near-Azeotropic
refrigerant
1.6 times higher
(difficult to design against
pressure resistance)
Small Air-Conditioners
pressure than R22
R407C
similar pressure as R22
(possible to design
large equipment)
Zeotropic refrigerant
(handle with care)
Large Air-Conditioners
*
05-07
Summary of Contents for B24LDC
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 11: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 13: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 34: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 64: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 65: ...REPLACEMENT PARTS Models AS B24LDC INDOOR UNIT 09 01 ...
Page 66: ......
Page 67: ......
Page 68: ...REPLACEMENT PARTS 09 04 Models AS B24LDC ...
Page 69: ...REPLACEMENT PARTS 09 05 Model AO S24LDC ...
Page 70: ......
Page 88: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 91: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS20032006 FEB 2006 Printed in Japan ...