19. OFF DEFROST OPEARTION CONTROL
(1). OFF DEFROST OPERATION CONDITION
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat
exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation
lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost,
and then stop.
In heating operation, the outdoor heat exchanger temperature is less than - 4 C, and compressor
operation integrating time lasts for more than 30 minutes.
AS*B24LDC
OFF Defrost Flow Chart
Heating operation stop
Outdoor heat exchanger temperature:
Below - 4 C
and
Compressor integrating operation:
Over 30 minutes
Defrost start
Defrost Indicater:
[Operation lamp]
Outdoor heat exchanger temperature:
Over 13 C
or
Compressor ON time:
Over 15 minutes
Defrost end
(2). OFF DEFROST END CONDITION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 13 C or
Compressor operation time has passed 15 minutes.
7 sec ON / 2 sec OFF
05-17
Summary of Contents for B24LDC
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 11: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 13: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 34: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 64: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 65: ...REPLACEMENT PARTS Models AS B24LDC INDOOR UNIT 09 01 ...
Page 66: ......
Page 67: ......
Page 68: ...REPLACEMENT PARTS 09 04 Models AS B24LDC ...
Page 69: ...REPLACEMENT PARTS 09 05 Model AO S24LDC ...
Page 70: ......
Page 88: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 91: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS20032006 FEB 2006 Printed in Japan ...