18. DEFROST OPERATION CONTROL
(1). CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor detects
the temperature lower than the values shown in Table 15.
(Table 15 : Condition of starting Defrost Operation)
AS*B24LDC
AS*B24LDC
AS*B24LDC
1 time defrosting
after starting
operation
ST
Defrosting after 2
time upon starting
operation
ND
Compressor operating time
Less than 17 minutes 17 to 60 minutes 60 minutes to 4 hours
After 4 hours
Does not operate
- 9 C
- 5 C
- 3 C
Less than 35 minutes
35 minutes to
4 hours
Does not operate
Compressor operating time
After 4 hours
- 3 C
- 6 C
(2). CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table 16.
(Table 16 : Defrost Release Condition)
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 13 C or
Compressor operation time has passed 15 minutes.
05-15
Summary of Contents for B24LDC
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 11: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 13: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 34: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 64: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Page 65: ...REPLACEMENT PARTS Models AS B24LDC INDOOR UNIT 09 01 ...
Page 66: ......
Page 67: ......
Page 68: ...REPLACEMENT PARTS 09 04 Models AS B24LDC ...
Page 69: ...REPLACEMENT PARTS 09 05 Model AO S24LDC ...
Page 70: ......
Page 88: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 91: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS20032006 FEB 2006 Printed in Japan ...