Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : AW * Z24LBC
[Condition]
Ambient
temperature
Indoor / Outdoor - Same temperature
Refrigerant
amount
Standard amount
Piping
length
7.5m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
condition
TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Colling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
AW * Z24LBC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AW * Z24LBC
Measure the low pressure with the pressure meter at the service valve. Measure the outdoor
unit overall current with the current clamp meter at Power Cable.
08-02
[50Hz-230V]
0.6
0.7
0.8
0.9
1.0
1.1
18
20
22
24
26
28
30
32
In/outdoor ambient temparature[ C]
L
o
w
-p
re
ssu
re
o
f o
u
td
o
o
r u
n
it
[
M
P
a
]
RH50%
RH60%
RH70%
[50Hz-230V]
5.0
5.2
5.4
5.6
5.8
6.0
6.2
6.4
6.6
6.8
7.0
18
20
22
24
26
28
30
32
In/outdoor ambient temparature [ C]
O
u
td
o
o
r t
o
ta
l el
ect
ri
c
current
[
A
]
RH50%
RH60%
RH70%
Summary of Contents for AW?Z24LBC
Page 4: ...1 SPECIFICATIONS R410A CEILING WALL type INVERTER ...
Page 6: ...2 DIMENSIONS R410A CEILING WALL type INVERTER ...
Page 7: ... Unit mm DIMENSIONS INDOOR UNIT 02 01 Models AW Z24LBC 300 298 899 250 170 40 ...
Page 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CEILING WALL type INVERTER ...
Page 11: ...4 CIRCUIT DIAGRAM R410A CEILING WALL type INVERTER ...
Page 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CEILING WALL type INVERTER ...
Page 36: ...6 REFRIGERANT CAUTION R410A R410A CEILING WALL type INVERTER ...
Page 63: ...9 REPLACEMENT PARTS R410A CEILING WALL type INVERTER ...
Page 64: ...REPLACEMENT PARTS 09 01 Models AW Z24LBC ...
Page 65: ...REPLACEMENT PARTS 09 02 Models AW Z24LBC ...
Page 66: ...REPLACEMENT PARTS 09 03 Models AW Z24LBC ...
Page 67: ...REPLACEMENT PARTS 09 04 Models AO Z24LBT ...
Page 68: ...REPLACEMENT PARTS 09 05 Models AO Z24LBT ...
Page 91: ...REPLACEMENT PARTS 09 28 PROCESS Wiring ...
Page 92: ...REPLACEMENT PARTS 09 29 PROCESS Wiring ...
Page 93: ...REPLACEMENT PARTS 09 30 Model AO Z24LBT PROCESS Wiring ...
Page 94: ...10 INSTALLATION MANUAL R410A CEILING WALL type INVERTER ...
Page 97: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan FEB 2007 Printed in Japan ...