Self - diagnosis function and Checking points
Error Indication
Operation
(RED)
Timer
(GREEN)
Error
(Protection)
Diagnosis Method
0.5 sec
2 times
When the indoor unit does not receive the signal for 10 consecutive seconds during the operation >Permanent stop after 30
seconds.
The outdoor unit does not receive the signal for 10 consecutive seconds from the time when the power relay was ON.
>Outdoor unit stops.
OFF
07-03
Serial forward transfer error
during the operation
Serial forward transfer error
at starting up operation
Serial reverse transfer error
during the operation
Serial reverse transfer error
at starting up operation
At the start up, the indoor unit does not receive the signal for 10 consecutive seconds from the time when the power relay was
ON.
>Permanent stop after 30 seconds.
[Diagnosis Point]
Check the indoor /outdoor cable connection (in order). If the cable wiring is not abnormal, measure the voltage of the outdoor
unit terminals and diagnose the defective location.
(Refer to the after mentioned [Serial Signal Diagnosis] for the voltage measuring method and diagnosis method.)
[Diagnosis Point]
Check the indoor /outdoor cable connection (in order). If the cable wiring is not abnormal, measure the voltage of the outdoor
unit terminals and diagnose the defective location.
(Refer to the after mentioned [Serial Signal Diagnosis] for the voltage measuring method and diagnosis method.)
[Diagnosis Point]
Check the indoor /outdoor cable connection (in order). If the cable wiring is not abnormal, measure the voltage of the outdoor
unit terminals and diagnose the defective location.
(Refer to the after mentioned [Serial Signal Diagnosis] for the voltage measuring method and diagnosis method.)
When
the
outdoor
unit
does not receive the signal for 10 consecutive seconds during the operation >
Outdoor
unit stops.
[Diagnosis Point]
Check the indoor /outdoor cable connection (in order). If the cable wiring is not abnormal, measure the voltage of the outdoor
unit terminals and diagnose the defective location.
(Refer to the after mentioned [Serial Signal Diagnosis] for the voltage measuring method and diagnosis method.)
The room temperature thermistor detective a abnormai temperature when the power was turned on. > Remote control does not
operate.
[Diagnosis Point]
Check thermistor resistance value (Refer to "Themistor characteristics table").
Controller PCB defective.
The detection value of the indoor heat exchanger thermistor is either open or shoted when the power is ON. > Remote control do
se
not operate.
[Diagnosis Point]
Check thermistor resistance value (Refer to "Themistor characteristics table").
Controller PCB defective.
Room temperature therm-
istor defective
Indoor heat exchanger
thermistor error
0.5 sec
3 times
0.5 sec
4 times
0.5 sec
5 times
0.5 sec
2 times
0.5 sec
3 times
0.5 sec
2 times
Summary of Contents for AW?Z24LBC
Page 4: ...1 SPECIFICATIONS R410A CEILING WALL type INVERTER ...
Page 6: ...2 DIMENSIONS R410A CEILING WALL type INVERTER ...
Page 7: ... Unit mm DIMENSIONS INDOOR UNIT 02 01 Models AW Z24LBC 300 298 899 250 170 40 ...
Page 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CEILING WALL type INVERTER ...
Page 11: ...4 CIRCUIT DIAGRAM R410A CEILING WALL type INVERTER ...
Page 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CEILING WALL type INVERTER ...
Page 36: ...6 REFRIGERANT CAUTION R410A R410A CEILING WALL type INVERTER ...
Page 63: ...9 REPLACEMENT PARTS R410A CEILING WALL type INVERTER ...
Page 64: ...REPLACEMENT PARTS 09 01 Models AW Z24LBC ...
Page 65: ...REPLACEMENT PARTS 09 02 Models AW Z24LBC ...
Page 66: ...REPLACEMENT PARTS 09 03 Models AW Z24LBC ...
Page 67: ...REPLACEMENT PARTS 09 04 Models AO Z24LBT ...
Page 68: ...REPLACEMENT PARTS 09 05 Models AO Z24LBT ...
Page 91: ...REPLACEMENT PARTS 09 28 PROCESS Wiring ...
Page 92: ...REPLACEMENT PARTS 09 29 PROCESS Wiring ...
Page 93: ...REPLACEMENT PARTS 09 30 Model AO Z24LBT PROCESS Wiring ...
Page 94: ...10 INSTALLATION MANUAL R410A CEILING WALL type INVERTER ...
Page 97: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan FEB 2007 Printed in Japan ...