4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum
mode from among the HEATING, COOLING, DRY and MONITORING modes. During operation, the
optimum mode is automatically switched in accordance with temperature changes. The temperature
can be set between 18°C and 30°C in 1°C steps.
.When operation starts, only the indoor and outdoor fans are operated for 1 minute. After 1 minute,
the room temperature and outside air temperature are sensed and the operation mode is
selected in accordance with the table below.
C zone
32°C
B zone
-10°C
A zone
( Table.4 Operation mode selection table)
Outside air temperature (To)
Room temperature (Tb)
A zone
B zone
C zone
Tb > Ts+2°C
Tb < Ts - 2°C
Monitoring
Cooling
(automatic dry)
Cooling
(automatic dry)
Ts+2°C
Tb
Ts - 2°C
Monitoring
Monitoring
Monitoring
Heating
Heating
Monitoring
.When COOING was selected at
, the air conditioner operates as follow:
The same operation as COOLING OPERATION of item 1 above is performed.
When the room temperature has remained at (set temperature -1°C) for 8 minutes, operation is
automatically switched to DRY and the same operation as DRY OPERATION of item 3 above
is performed.
If the room temperature reaches (set tempe2°C during DRY operation, operation returns to
COOLING operation.
.When HEATING was selected at
, the same operation as HEATING OPERATION of item 2
above is performed.
When the compressor was stopped for 6 consecutive minutes by the temperature control function
after the COOLING or HEATING operation mode was selected at
above, operation is switched
to MONITORING and the operation mode is selected again.
1
1
2
3
1
4
1
( Fig.5 : Outside air temperature zone selection )
05-04
Summary of Contents for AW?Z24LBC
Page 4: ...1 SPECIFICATIONS R410A CEILING WALL type INVERTER ...
Page 6: ...2 DIMENSIONS R410A CEILING WALL type INVERTER ...
Page 7: ... Unit mm DIMENSIONS INDOOR UNIT 02 01 Models AW Z24LBC 300 298 899 250 170 40 ...
Page 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CEILING WALL type INVERTER ...
Page 11: ...4 CIRCUIT DIAGRAM R410A CEILING WALL type INVERTER ...
Page 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CEILING WALL type INVERTER ...
Page 36: ...6 REFRIGERANT CAUTION R410A R410A CEILING WALL type INVERTER ...
Page 63: ...9 REPLACEMENT PARTS R410A CEILING WALL type INVERTER ...
Page 64: ...REPLACEMENT PARTS 09 01 Models AW Z24LBC ...
Page 65: ...REPLACEMENT PARTS 09 02 Models AW Z24LBC ...
Page 66: ...REPLACEMENT PARTS 09 03 Models AW Z24LBC ...
Page 67: ...REPLACEMENT PARTS 09 04 Models AO Z24LBT ...
Page 68: ...REPLACEMENT PARTS 09 05 Models AO Z24LBT ...
Page 91: ...REPLACEMENT PARTS 09 28 PROCESS Wiring ...
Page 92: ...REPLACEMENT PARTS 09 29 PROCESS Wiring ...
Page 93: ...REPLACEMENT PARTS 09 30 Model AO Z24LBT PROCESS Wiring ...
Page 94: ...10 INSTALLATION MANUAL R410A CEILING WALL type INVERTER ...
Page 97: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan FEB 2007 Printed in Japan ...