Summary of R407C and R410A characteristics
Pressure (Mpa) Temp ( C)
2.20
37.9
2.25
38.7
2.30
39.6
2.35
40.5
2.40
41.3
2.45
42.1
2.55
43.8
2.60
44.6
2.65
45.3
2.70
46.1
2.75
46.8
2.80
47.6
2.85
48.3
2.90
49.0
2.95
49.8
3.00
50.5
3.05
51.2
3.10
51.9
3.15
52.6
3.20
53.2
3.25
53.9
3.30
54.6
3.35
55.3
3.40
55.9
3.45
56.5
3.50
57.1
2.55
57.8
3.60
58.4
3.65
59.0
3.70
59.6
3.75
60.2
3.80
60.8
3.85
61.4
3.90
52.0
3.95
62.5
4.00
63.1
4.05
63.6
4.10
64.2
4.15
64.8
Temp ( C) Pressure (Mpa)
39
2.27
40
2.32
41
2.38
42
2.44
44
2.57
45
2.63
46
2.69
47
2.76
48
2.83
49
2.90
51
3.04
52
3.11
53
3.18
54
3.26
56
3.41
57
3.49
58
3.57
59
3.65
61
3.82
62
3.90
63
3.99
64
4.08
Desighed pressure of R410A refrigerant
< Pressure Temp >
Relation between R410A condensing temperature and saturated pressure.
< Temp Pressure >
Advantage
Disadvantage
Suitable for
R410A
higher system
performance
Near-Azeotropic
refrigerant
1.6 times higher
(difficult to design against
pressure resistance)
Small Air-Conditioners
pressure than R22
R407C
similar pressure as R22
(possible to design
large equipment)
Zeotropic refrigerant
(handle with care)
Large Air-Conditioners
*
05-07
Summary of Contents for AW?Z24LBC
Page 4: ...1 SPECIFICATIONS R410A CEILING WALL type INVERTER ...
Page 6: ...2 DIMENSIONS R410A CEILING WALL type INVERTER ...
Page 7: ... Unit mm DIMENSIONS INDOOR UNIT 02 01 Models AW Z24LBC 300 298 899 250 170 40 ...
Page 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CEILING WALL type INVERTER ...
Page 11: ...4 CIRCUIT DIAGRAM R410A CEILING WALL type INVERTER ...
Page 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CEILING WALL type INVERTER ...
Page 36: ...6 REFRIGERANT CAUTION R410A R410A CEILING WALL type INVERTER ...
Page 63: ...9 REPLACEMENT PARTS R410A CEILING WALL type INVERTER ...
Page 64: ...REPLACEMENT PARTS 09 01 Models AW Z24LBC ...
Page 65: ...REPLACEMENT PARTS 09 02 Models AW Z24LBC ...
Page 66: ...REPLACEMENT PARTS 09 03 Models AW Z24LBC ...
Page 67: ...REPLACEMENT PARTS 09 04 Models AO Z24LBT ...
Page 68: ...REPLACEMENT PARTS 09 05 Models AO Z24LBT ...
Page 91: ...REPLACEMENT PARTS 09 28 PROCESS Wiring ...
Page 92: ...REPLACEMENT PARTS 09 29 PROCESS Wiring ...
Page 93: ...REPLACEMENT PARTS 09 30 Model AO Z24LBT PROCESS Wiring ...
Page 94: ...10 INSTALLATION MANUAL R410A CEILING WALL type INVERTER ...
Page 97: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan FEB 2007 Printed in Japan ...