10. Electrical characteristics
Model name
AOYG24KBTB
Power
supply
Voltage
V
230 ~
Frequency
Hz
50
Max operating current *1
A
13.6
Starting current
A
8.4
Wiring
spec. *2
Circuit breaker current
A
20
Power cable
mm
2
2.5
Connection
cable *3
Cross-sectional area
mm
2
1.5
Limited wiring length
m
31
Model name
AOYG30KBTB
AOYG36KBTB
Power
supply
Voltage
V
230 ~
Frequency
Hz
50
Max operating current *1
A
22.6
Starting current
A
11.1
12.9
Wiring
spec. *2
Circuit breaker current
A
25
Power cable
mm
2
4.0
Connection
cable *3
Cross-sectional area
mm
2
1.5
Limited wiring length
m
51
Model name
AOYG45KBTB
AOYG54KBTB
Power
supply
Voltage
V
230 ~
Frequency
Hz
50
Max operating current *1
A
28.5
Starting current
A
16.0
19.4
Wiring
spec. *2
Circuit breaker current
A
32
Power cable
mm
2
4.0
Connection
cable *3
Cross-sectional area
mm
2
1.5
Limited wiring length
m
51
*1: Maximum current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*3: Limit voltage drop to less than 2%. Increase conductor size if voltage drop is 2% or more.
- 88 -
10. Electrical characteristics
O
U
TD
O
O
R
U
N
IT
A
O
YG
24
-5
4K
B
TB
O
U
TD
O
O
R
U
N
IT
A
O
YG
24
-5
4K
B
TB
Summary of Contents for AUXG24KRLB
Page 6: ......
Page 7: ...Part 1 INDOOR UNIT CASSETTE TYPE AUXG24KRLB AUXG30KRLB AUXG36KRLB AUXG45KRLB AUXG54KRLB ...
Page 66: ... 60 11 3 Others 11 Optional parts CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...
Page 67: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG24KBTB AOYG30KBTB AOYG36KBTB AOYG45KBTB AOYG54KBTB ...