6-2. Model: AOYG30KBTB
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
20
30
40
50
H
ei
gh
t d
iff
ere
nce
H
(m)
Indoor unit is higher
than outdoor unit *1
30
—
—
—
—
0.926
0.916
0.906
20
—
—
—
0.953
0.942
0.931
0.920
10
—
—
0.979
0.968
0.958
0.946
0.936
7.5
—
0.988
0.983
0.972
0.961
0.951
0.939
5
0.992
0.992
0.987
0.976
0.965
0.954
0.943
0
1.000
1.000
0.995
0.984
0.973
0.962
0.951
Indoor unit is lower than
outdoor unit *2
-5
1.000
1.000
0.995
0.984
0.973
0.962
0.951
-7.5
—
1.000
0.995
0.984
0.973
0.962
0.951
-10
—
—
0.995
0.984
0.973
0.962
0.951
-20
—
—
—
0.984
0.973
0.962
0.951
-30
—
—
—
—
0.973
0.962
0.951
HEATING
Pipe length (m)
5
7.5
10
20
30
40
50
H
ei
gh
t d
iff
ere
nce
H
(m)
Indoor unit is higher
than outdoor unit *1
30
—
—
—
—
0.931
0.914
0.899
20
—
—
—
0.954
0.931
0.914
0.899
10
—
—
0.990
0.954
0.931
0.914
0.899
7.5
—
1.000
0.990
0.954
0.931
0.914
0.899
5
1.000
1.000
0.990
0.954
0.931
0.914
0.899
0
1.000
1.000
0.990
0.954
0.931
0.914
0.899
Indoor unit is lower than
outdoor unit *2
-5
0.995
0.995
0.986
0.949
0.926
0.909
0.895
-7.5
—
0.993
0.983
0.946
0.924
0.907
0.892
-10
—
—
0.981
0.944
0.921
0.904
0.890
-20
—
—
—
0.935
0.912
0.895
0.881
-30
—
—
—
—
0.903
0.886
0.872
- 79 -
6-2. Model: AOYG30KBTB
6. Capacity compensation rate for pipe length and height difference
O
U
TD
O
O
R
U
N
IT
A
O
YG
24
-5
4K
B
TB
O
U
TD
O
O
R
U
N
IT
A
O
YG
24
-5
4K
B
TB
Summary of Contents for AUXG24KRLB
Page 6: ......
Page 7: ...Part 1 INDOOR UNIT CASSETTE TYPE AUXG24KRLB AUXG30KRLB AUXG36KRLB AUXG45KRLB AUXG54KRLB ...
Page 66: ... 60 11 3 Others 11 Optional parts CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...
Page 67: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG24KBTB AOYG30KBTB AOYG36KBTB AOYG45KBTB AOYG54KBTB ...