Fujitsu AUXG24KRLB Design & Technical Manual Download Page 48

8-4. Details of function

¢

Control input function

When function setting is "Operation/Stop" mode 1

• In the case of "Edge" input

Function

setting /

Rotary SW of

External input and

output PCB

External input

Input signal

Command

46-00

-

Input of indoor unit

Terminal

Off → On

Operation

On → Off

Stop

60-00 / 1

External input and

output PCB

Input 1

Off → On

Operation

On → Off

Stop

Operation

Stop

Remote controller

On

Off

Indoor unit

On

Input

• In the case of "Pulse" input

Function

setting /

Rotary SW of

External input and

output PCB

External input

Input signal

Command

46-00

60-00 / 1

External input and

output PCB

Input 1

Pulse

Operation

Input 2

Pulse

Stop

On

On

Off

Operation

Stop

Remote controller

On

Off

Indoor unit

Input 1

Input 2

NOTES:

• The last command has priority.
• The indoor units within the same remote controller group operates in the same mode.

- 42 -

8-4. Details of function

8. External input and output

C

A

SSET

TE 

TYPE

A

U

XG

24

-5

4K

R

LB

C

A

SSET

TE 

TYPE

A

U

XG

24

-5

4K

R

LB

Summary of Contents for AUXG24KRLB

Page 1: ...IR CONDITIONER Cassette type DESIGN TECHNICAL MANUAL INDOOR AUXG24KRLB AUXG30KRLB AUXG36KRLB AUXG45KRLB AUXG54KRLB OUTDOOR AOYG24KBTB AOYG30KBTB AOYG36KBTB AOYG45KBTB AOYG54KBTB DR_AU023EF_02 2019 04 26 ...

Page 2: ...please check with our authorized dealer Trademarks FGLair is trademark of Fujitsu General Limited in the United States other countries or both Google Play is trademark of Google Inc App Store is a service mark of Apple Inc registered in the U S and other countries Copyright 2019 Fujitsu General Limited All rights reserved ...

Page 3: ...w 24 5 3 Fresh air characteristics 28 5 4 Duct connection 29 6 Operation noise sound pressure 32 6 1 Noise level curve 32 6 2 Sound level check point 35 7 Safety devices 36 8 External input and output 37 8 1 External input 38 8 2 External output 39 8 3 Combination of external input and output 40 8 4 Details of function 42 9 Function settings 48 9 1 Function settings on indoor unit 48 9 2 Function ...

Page 4: ... for pipe length and height difference 78 6 1 Model AOYG24KBTB 78 6 2 Model AOYG30KBTB 79 6 3 Model AOYG36KBTB 80 6 4 Models AOYG45KBTB and AOYG54KBTB 81 7 Additional charge calculation 82 7 1 Model AOYG24KBTB 82 7 2 Models AOYG30KBTB and AOYG36KBTB 82 7 3 Models AOYG45KBTB and AOYG54KBTB 82 8 Airflow 83 8 1 Model AOYG24KBTB 83 8 2 Models AOYG30KBTB and AOYG36KBTB 83 8 3 Models AOYG45KBTB and AOYG...

Page 5: ...13 2 Local setting procedure 97 14 Accessories 99 14 1 Model AOYG24KBTB 99 14 2 Models AOYG30KBTB AOYG36KBTB AOYG45KBTB and AOYG54KBTB 99 15 Optional parts 100 CONTENTS continued ...

Page 6: ......

Page 7: ...Part 1 INDOOR UNIT CASSETTE TYPE AUXG24KRLB AUXG30KRLB AUXG36KRLB AUXG45KRLB AUXG54KRLB ...

Page 8: ...3 Main1 252 2 131 13 3 Main2 252 2 064 13 3 Main3 252 1 999 13 3 Fin pitch 1 2 1 3 Rows Stages 1 10 1 12 1 12 Pipe type Copper tube Fin type Aluminum Dimensions H W D Net mm 246 840 840 288 840 840 Gross 298 960 950 340 960 950 Weight Net kg 24 26 29 Gross 29 32 34 Connection pipe Size Liquid mm in Ø 6 35 Ø 1 4 Ø 9 52 Ø 3 8 Gas Ø 12 70 Ø 1 2 Ø 15 88 Ø 5 8 Method Flare Drain hose Material PVC Size ...

Page 9: ... C 8 5 35 C 9 5 35 C Heating Average 6 0 10 C 8 0 10 C 8 7 10 C SEER Cooling kWh kWh 6 60 6 70 6 55 SCOP Heating Average 4 20 4 30 4 30 Annual energy consump tion QCE kWh a 360 444 507 QHE Average 1 999 2 601 2 828 Sound power level Cooling HIGH dB A 49 54 58 Heating 49 54 58 3 1 Specifications CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...

Page 10: ... type Copper tube Fin type Aluminum Dimensions H W D Net mm 288 840 840 Gross 340 960 950 Weight Net kg 29 Gross 34 Connection pipe Size Liquid mm in Ø 9 52 Ø 3 8 Gas Ø 15 88 Ø 5 8 Method Flare Drain hose Material PVC VP25 Size mm Ø 25 I D Ø 32 O D Operation range Cooling C 18 to 32 RH 80 or less Heating C 16 to 30 Cassette grille Option Material Polystyrene Color White Approximate color of MUNSEL...

Page 11: ... bolt position Hanging bolt position Indoor unit Drain hose View B View C A B C Ceiling 200 to 205 200 342 45 40 140 256 Wire hole 237 40 40 163 Fresh air inlet cut out 100 83 100 83 352 109 163 90 4 Ø3 2 hole Ø95 80 80 5 2 1 Model AUXG24KRLB 2 Dimensions CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...

Page 12: ... Drain hose View B View C A B C Ceiling Wire hole 950 620 768 420 293 342 45 40 140 298 200 to 205 10 39 200 to 205 200 237 40 40 164 Fresh air inlet cut out 100 83 100 83 352 109 164 90 950 4 Ø3 2 hole Ø95 80 80 6 2 2 Models AUXG30KRLB AUXG36KRLB AUXG45KRLB and AUXG54KRLB 2 Dimensions CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...

Page 13: ...ful about the maintenance space To set 3 direction Air outlet shutter plate option must be installed and the outlet direction need to be switched to 3 way by the remote controller 100 or more 4 directions 3 directions Piping position To ceiling height cannot be set in the 3 way outlet mode Therefore ceiling height setting change by function setting 20 is prohibited For details refer to Contents of...

Page 14: ...height 3 200 mm Detecting position 800 mm from floor surface NOTE When the installation height gets higher the temperature sensitivity decreases CAUTION Do not place large objects near the human sensor Keep any other heating units outside the sensor s detection area 8 2 3 Installation space requirement 2 Dimensions CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...

Page 15: ...m 3 1 Models AUXG24KRLB AUXG30KRLB AUXG36KRLB AUXG45KRLB and AUXG54KRLB 9 3 1 Models AUXG24KRLB AUXG30KRLB AUXG36KRLB AUXG45KRLB and AUXG54KRLB 3 Wiring diagram CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...

Page 16: ...96 1 89 7 21 4 94 1 91 7 62 5 26 1 93 40 5 09 4 06 1 97 5 67 4 08 2 00 5 87 4 44 2 02 6 26 4 45 2 04 6 45 4 81 2 05 6 84 4 79 2 07 7 22 5 10 2 09 46 4 18 3 59 1 70 4 66 3 61 1 73 4 82 3 93 1 74 5 13 3 94 1 76 5 29 4 25 1 77 5 61 4 24 1 78 5 93 4 51 1 80 Model AUXG30KRLB AFR m3 h 1 600 Indoor temperature CDB 18 21 23 25 27 29 32 CWB 12 15 16 18 19 21 23 Outdoor temperature CDB TC SHC IP TC SHC IP T...

Page 17: ...6 8 17 1 96 15 8 27 6 54 1 89 8 98 6 87 1 94 9 45 7 09 1 96 9 91 7 38 1 99 10 38 7 68 2 02 10 82 7 83 2 02 11 47 8 04 2 02 20 11 05 8 32 3 07 11 99 8 73 3 14 12 61 9 01 3 19 13 24 9 39 3 23 13 86 9 77 3 28 14 44 9 95 3 28 15 31 10 22 3 28 25 10 58 8 11 3 18 11 48 8 51 3 25 12 08 8 78 3 29 12 68 9 15 3 34 13 28 9 52 3 39 13 83 9 70 3 39 14 66 9 97 3 39 30 10 11 7 90 3 28 10 97 8 29 3 35 11 54 8 56 ...

Page 18: ...7 9 07 2 97 8 83 2 98 8 25 2 99 0 2 9 71 3 19 9 67 3 20 9 63 3 20 9 38 3 21 8 76 3 22 5 3 10 84 3 24 10 80 3 25 10 75 3 25 10 47 3 25 9 78 3 27 7 6 11 30 3 26 11 25 3 27 11 20 3 27 10 91 3 27 10 19 3 29 10 8 11 64 3 26 11 59 3 27 11 54 3 27 11 25 3 27 10 50 3 29 15 10 12 11 3 26 12 06 3 27 12 01 3 27 11 70 3 27 10 93 3 29 20 15 12 90 3 27 12 84 3 27 12 79 3 28 12 46 3 28 11 64 3 29 24 18 13 53 3 2...

Page 19: ... 01 4 19 20 50 4 22 20 00 4 24 19 54 4 24 18 38 4 24 Model AUXG54KRLB AFR m3 h 2 100 Indoor temperature CDB 16 18 20 22 24 Outdoor temperature CDB CWB TC IP TC IP TC IP TC IP TC IP kW kW kW kW kW 15 16 12 26 4 49 11 97 4 51 11 67 4 53 11 40 4 53 10 72 4 53 10 11 13 62 4 68 13 29 4 70 12 97 4 72 12 66 4 72 11 91 4 72 5 7 14 97 4 87 14 61 4 89 14 26 4 92 13 93 4 92 13 10 4 92 0 2 15 77 5 06 15 39 5 ...

Page 20: ...w Vertical airflow direction louver position 1 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 2 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 4 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 14 5 1...

Page 21: ...tion louver position 1 m m Unit m s 3 2 2 1 0 1 1 1 1 2 2 2 2 0 3 3 4 4 5 5 6 6 7 7 0 5 0 5 0 25 0 25 Side view Vertical airflow direction louver position 2 m m Unit m s 3 2 2 1 0 1 1 1 1 2 2 2 2 0 3 3 4 4 5 5 6 6 7 7 0 5 0 5 0 25 0 25 Side view Vertical airflow direction louver position 4 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 15 5 1 Air velocity distributi...

Page 22: ...tion louver position 1 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 2 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 4 m 3 2 2 1 0 m 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Unit m s 16 5 1 Air velocity distributi...

Page 23: ...tion louver position 1 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 2 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 4 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 17 5 1 Air velocity distributi...

Page 24: ...irection louver position 1 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 2 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 4 m 3 2 2 1 0 0 25 0 5 1 2 0 5 0 25 1 2 m 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 18 5 1 Air velocity distributions 5...

Page 25: ... louver position 1 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 2 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 4 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 19 5 1 Air velocity distributions ...

Page 26: ... louver position 1 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 2 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 4 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 20 5 1 Air velocity distributions ...

Page 27: ... louver position 1 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 2 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 4 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 21 5 1 Air velocity distributions ...

Page 28: ... louver position 1 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 2 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 4 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 22 5 1 Air velocity distributions ...

Page 29: ... louver position 1 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 2 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 Side view Vertical airflow direction louver position 4 m m Unit m s 3 2 2 1 0 1 1 2 2 0 3 3 4 4 5 5 6 6 7 7 0 25 0 5 1 2 0 5 0 25 1 2 23 5 1 Air velocity distributions ...

Page 30: ... LOW m3 h 980 l s 272 CFM 577 QUIET m3 h 870 l s 242 CFM 512 Model AUXG30KRLB 4 way outlet Cooling Heating Fan speed Airflow HIGH m3 h 1 600 l s 444 CFM 942 MED m3 h 1 400 l s 389 CFM 824 LOW m3 h 1 270 l s 353 CFM 748 QUIET m3 h 1 150 l s 319 CFM 677 24 5 2 Airflow 5 Fan performance CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...

Page 31: ...ating Fan speed Airflow HIGH m3 h 2 000 l s 556 CFM 1 177 MED m3 h 1 650 l s 458 CFM 971 LOW m3 h 1 460 l s 406 CFM 859 QUIET m3 h 1 300 l s 361 CFM 765 Model AUXG54KRLB 4 way outlet Cooling Heating Fan speed Airflow HIGH m3 h 2 100 l s 583 CFM 1 236 MED m3 h 1 780 l s 494 CFM 1 048 LOW m3 h 1 600 l s 444 CFM 942 QUIET m3 h 1 320 l s 367 CFM 777 25 5 2 Airflow 5 Fan performance CASSETTE TYPE AUXG2...

Page 32: ...ting Fan speed Airflow HIGH m3 h 1 390 l s 386 CFM 818 MED m3 h 1 220 l s 339 CFM 718 LOW m3 h 1 100 l s 306 CFM 647 QUIET m3 h 1 000 l s 278 CFM 589 Model AUXG36KRLB 3 way outlet Cooling Heating Fan speed Airflow HIGH m3 h 1 660 l s 461 CFM 977 MED m3 h 1 390 l s 386 CFM 818 LOW m3 h 1 240 l s 344 CFM 730 QUIET m3 h 1 030 l s 286 CFM 606 26 5 2 Airflow 5 Fan performance CASSETTE TYPE AUXG24 54KRL...

Page 33: ...h 1 270 l s 353 CFM 748 QUIET m3 h 1 130 l s 314 CFM 665 Model AUXG54KRLB 3 way outlet Cooling Heating Fan speed Airflow HIGH m3 h 1 830 l s 508 CFM 1 077 MED m3 h 1 550 l s 431 CFM 912 LOW m3 h 1 390 l s 386 CFM 818 QUIET m3 h 1 150 l s 319 CFM 677 27 5 2 Airflow 5 Fan performance CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...

Page 34: ...Static pressure required to take in fresh air Duct fan Installation Duct flange 2 Flexible duct 2 Fan 2 Flexible duct 2 Insulation 1 1 In case of fresh air intake remove the insulation 2 Locally purchased parts Fresh air inlet position For the fresh air inlet position refer to Dimensions on page 5 28 5 3 Fresh air characteristics 5 Fan performance CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 5...

Page 35: ...m L 5m L 1m Fan Speed Quiet 2 way Fan Speed Quiet 1 way Fan Speed High 1 way Fan Speed High 2 way 0 10 20 30 40 50 60 70 80 90 100 0 2 4 6 8 10 12 14 Duct static pressure Pa Airflow m3 min Model AUXG36KRLB 0 10 20 30 40 50 60 70 80 90 100 110 0 2 4 6 8 10 12 14 Duct static pressure Pa Airflow m3 min Fan Speed High 1 way Fan Speed High 2 way Fan Speed Quiet 1 way Fan Speed Quiet 2 way L 10m L 5m L ...

Page 36: ... 6 8 10 12 14 Duct static pressure Pa Airflow m3 min Model AUXG54KRLB L 10m L 5m L 1m Fan Speed High 1 way Fan Speed High 2 way Fan Speed Quiet 1 way Fan Speed Quiet 2 way 0 10 20 30 40 50 60 70 80 90 100 110 0 2 4 6 8 10 12 14 Duct static pressure Pa Airflow m3 min 30 5 4 Duct connection 5 Fan performance CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...

Page 37: ...n 2 directions connect the ducts in a straight line Air outlet duct Air outlet duct Close Close Air outlet duct Air outlet duct Close Close Once the ducted direction is decided be sure to close the outlet in the direction Use optional Air outlet shutter plate UTR YDZK to close the outlet Duct locally purchased Close the outlet here 31 5 4 Duct connection 5 Fan performance CASSETTE TYPE AUXG24 54KR...

Page 38: ...Pa Octave band center frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 High Quiet Model AUXG30KRLB Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Octave band sound pressure level dB 0dB 20μPa Octave band center frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 High Quiet Heating 0 10 20 30 40 50 60 70 80 63 125 250 50...

Page 39: ...NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 High Quiet Model AUXG45KRLB Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Octave band sound pressure level dB 0dB 20μPa Octave band center frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 High Quiet Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Octave band sound pressure level dB 0dB 20μ...

Page 40: ...NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 High Quiet Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Octave band sound pressure level dB 0dB 20μPa Octave band center frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 High Quiet 34 6 1 Noise level curve 6 Operation noise sound pressure CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...

Page 41: ...6 2 Sound level check point Microphone Microphone 1 5 m 35 6 2 Sound level check point 6 Operation noise sound pressure CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...

Page 42: ...LB AUXG45KRLB and AUXG54KRLB Circuit protection Current fuse PCB 250 V 3 15 A Fan motor protection Thermal protection program Activate 125 10 C Fan motor stop Reset 120 10 C Fan motor restart Printed Circuit Board 36 7 Safety devices CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...

Page 43: ...nit Operation Stop Terminal Dry contact Edge Operation status CN47 UTY XWZXZG Error status Indoor unit fan operation status External heater output External input and output UTY XCSX Operation Stop Input 1 Input 2 Dry contact Apply voltage Edge Pulse Forced thermostat off Input 1 Edge Operation status Output 1 Output 2 Output 3 Error status Indoor unit status External heater output 37 8 External in...

Page 44: ... Input select Use either one of these types of terminals according to the application Both types of terminals cannot be used simultaneously Dry contact In case of internal power supply set the slide switch of SW1 to NON VOL side 1 2 C Input 1 Input 2 PCB Connected unit 1 The switches can be used on the following condition DC 12 V to 24 V 1 mA to 15 mA Apply voltage In case of external power supply...

Page 45: ... unit When connecting with a device equipped with a power supply Example Function setting 60 is set to 00 1 2 Connected device CN47 PCB Connected unit Relay Operation status External input and output PCB A twisted pair cable 22AWG should be used Permissible voltage and current DC 5 V to 30 V 3 A AC 30 V to 250 V 3 A For details refer to Chapter 8 3 Combination of external input and output on page ...

Page 46: ...FF Not available Edge Mode Function setting External input and output PCB Rotary SW External output Indoor unit Output External input and output PCB CN47 Output 1 Output 2 Output 3 0 1 60 00 1 Operation Stop Operation Stop Error status Indoor unit fan operation status 0 2 60 00 2 Operation Stop Error status Indoor unit fan operation status External heater output 1 8 60 01 to 60 08 3 9 A Setting pr...

Page 47: ... type can be selected Signal type edge or pulse can be switched by the DIP switch 2 SW2 on the External input and output PCB Edge Pulse The width of pulse must be longer than 200 msec 41 8 3 Combination of external input and output 8 External input and output CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...

Page 48: ...Stop Remote controller On Off Indoor unit On Input In the case of Pulse input Function setting Rotary SW of External input and output PCB External input Input signal Command 46 00 60 00 1 External input and output PCB Input 1 Pulse Operation Input 2 Pulse Stop On On Off Operation Stop Remote controller On Off Indoor unit Input 1 Input 2 NOTES The last command has priority The indoor units within t...

Page 49: ...otary SW of External input and output PCB External input Input signal Command 46 02 60 00 1 External input and output PCB Input 1 Pulse Forced stop Input 2 Pulse Normal On Off Operation Stop Remote controller On Off Forced stop Normal Input 1 Input 2 On On On Indoor unit NOTES When the forced stop is triggered indoor unit stops and Operation Stop operation by the re mote controller is restricted W...

Page 50: ...roller On On Off In the case of Pulse input Function setting Rotary SW of External input and output PCB External input Input signal Command 46 03 60 00 1 External input and output PCB Input 1 Pulse Operation Input 2 Pulse Stop R C disabled On On Off Operation Stop Remote controller On Off Indoor unit Input 1 Input 2 R C disabled Off On NOTES When Operation Stop mode 2 function is used with forming...

Page 51: ...trol output function Function setting Rotary SW of External input and output PCB External output Output signal Command 60 00 1 2 Output of indoor unit CN47 Low High Operation High Low Stop 60 00 1 External input and output PCB Output 1 Off On Operation 60 09 B 60 10 C On Off Stop 60 11 D The output is low when the unit is stopped Operation Stop High Low CN47 On Off Output 1 Indoor unit 45 8 4 Deta...

Page 52: ... fan operation status Function setting Rotary SW of External input and output PCB External output Output signal Command 60 10 C Output of indoor unit CN47 Low High Fan run High Low Fan stop 60 00 2 60 09 B 60 11 D External input and output PCB Output 2 Off On Fan run On Off Fan stop 60 00 1 Output 3 Off On Fan run On Off Fan stop Output signal Condition On The indoor unit fan is operating Low High...

Page 53: ...eating temperature Other than Heating mode On Off Error occurred Forced thermo off Fan stop protection Specifications of the signal output performance are as shown as follows Example When set temperature Ts is set at 22 C And room temperature Tr increase above 12 C signal output is on And Tr increase above 21 C signal output is off And Tr decrease below 19 C signal output is on And Tr decrease bel...

Page 54: ...malfunction 9 1 Function settings on indoor unit By using some components on the PCB you can change the function settings Component location Components on the indoor unit main PCB used for the function settings are located as shown in the following figure SW100 1 2 3 4 SW101 1 2 3 48 9 1 Function settings on indoor unit 9 Function settings CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...

Page 55: ... 07 ON ON ON OFF 08 OFF OFF OFF ON 09 ON OFF OFF ON 10 OFF ON OFF ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14 OFF ON ON ON 15 ON ON ON ON NOTES When connecting Polar 3 core wired remote controller set the remote controller address in the order of 0 1 2 and 15 When different type of indoor units such as wall mounted type and cassette type cas sette type and duct type or other combination...

Page 56: ... 1 11 Filter sign 2 20 Ceiling height 3 22 Outlet directions 4 23 Vertical airflow direction range control 5 30 31 Room temperature control for indoor unit sensor 6 35 36 Room temperature control for wired remote controller sensor 7 40 Auto restart 8 42 Room temperature sensor switching 9 44 Remote controller custom code 10 46 External input control 11 48 Room temperature sensor switching Aux 12 4...

Page 57: ...t the appropriate number of outlet directions according to the installation conditions Function number Setting value Setting description Factory setting 22 00 4 way 01 3 way 4 Vertical airflow direction range control To prevent draft change the setting to Upward 01 Note that the airflow in certain usage conditions may leave the ceiling dirty In such cases the use of the optional Panel spacer is re...

Page 58: ... 0 C 16 3 5 C 17 4 0 C 6 Room temperature control for wired remote controller sensor Depending on the installed environment correction of the wire remote temperature sensor may be required Select the appropriate control setting according to the installed environment To change this setting set Function 42 to Both 01 Ensure that the Thermo Sensor icon is displayed on the remote controller screen Fun...

Page 59: ...or wireless remote controller The indoor unit custom code can be changed Select the appropriate custom code Function number Setting value Setting description Factory setting 44 00 A 01 B 02 C 03 D 10 External input control Operation Stop mode or Forced stop mode can be selected Function number Setting value Setting description Factory setting 46 00 Operation Stop mode 1 01 Setting prohibited 02 Fo...

Page 60: ... setting NOTES As the factory setting this setting is initially activated Set to 00 or 01 when connecting a remote controller that cannot set the Fan control for ener gy saving function or connecting a network converter To confirm if the remote controller has this setting refer to the operating manual of each remote controller 13 Switching functions for external output terminal Functions of the ex...

Page 61: ...ting manual CD ROM 1 Drain hose 1 Installation manual 1 Hose band 1 Template Carton top 1 Drain hose heat insulation 1 Washer 8 Cable tie large 4 Coupler heat insulation large 1 Cable tie small 2 Coupler heat insulation small 1 55 10 1 Models AUXG24KRLB AUXG30KRLB AUXG36KRLB AUXG45KRLB and AUXG54KRLB 10 Accessories CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...

Page 62: ... RNNYM Room temperature can be controlled by detecting the temperature accurately with built in thermo sensor Wire type Polar 3 wire Simple remote controller UTY RSRY Compact remote controller concentrates on the basic functions such as Start Stop fan control temperature setting and operation mode Wire type Non polar 2 wire Simple remote controller UTY RHRY Compact remote controller concentrates o...

Page 63: ...tte grille UTG UKYA W This cassette grille to blow airflow in 360º direction by unique seamless airflow louver design Wired remote controller UTY RNRYZ is included Cassette grille UTG UKYA B This cassette grille to blow airflow in 360º direction by unique seamless airflow louver design Black color model Cassette grille UTG UKYC W This cassette grille to blow airflow in 360º direction by unique sea...

Page 64: ...between the cassette grille and the ceiling surface the height of the unit body goes into the ceiling space become 50 mm lower Fresh air intake kit UTZ VXRA By attaching Fresh air intake kit to the indoor unit it can be taken in fresh air of up to 10 of high air volume of the indoor unit Insulation for high humidity UTZ KXRA Install when the under roof condition is expected to be the humidity of o...

Page 65: ...Modbus open network KNX converter UTY VKSX For connection between indoor unit with UART interface and a KNX open network External switch controller UTY TERX Air conditioner switching can be controlled by connecting other external sensor switches NOTE Combined use of following optional parts and Wireless LAN adapter UTY TFSXZ1 is not allowed External input and output PCB UTY XCSX Modbus converter K...

Page 66: ... 60 11 3 Others 11 Optional parts CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...

Page 67: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG24KBTB AOYG30KBTB AOYG36KBTB AOYG45KBTB AOYG54KBTB ...

Page 68: ...1 0 Dimensions H W D Net mm 716 820 315 Gross 776 961 450 Weight Net kg 42 Gross 46 Connection pipe Size Liquid mm in Ø6 35 1 4 Gas Ø12 70 1 2 Method Flare Pre charge length m 20 Max length 30 Max height difference 25 Operation range Cooling C 15 to 46 Heating 15 to 24 Drain hose Material PP Size mm Ø13 0 I D Ø16 0 to Ø16 8 O D NOTES Specifications are based on the following conditions Cooling Ind...

Page 69: ... 5 1 0 Dimensions H W D Net mm 788 940 320 Gross 966 1 027 445 Weight Net kg 52 Gross 60 Connection pipe Size Liquid mm in Ø9 52 3 8 Gas Ø15 88 5 8 Method Flare Pre charge length m 30 Max length 50 Max height difference 30 Operation range Cooling C 15 to 46 Heating 15 to 24 Drain hose Material LDPE Size mm Ø13 0 I D Ø16 0 to Ø16 8 O D NOTES Specifications are based on the following conditions Cool...

Page 70: ...Munsell 10YR 7 5 1 0 Dimensions H W D Net mm 998 940 320 Gross 1 176 1 027 445 Weight Net kg 67 Gross 75 Connection pipe Size Liquid mm in Ø9 52 3 8 Gas Ø15 88 5 8 Method Flare Pre charge length m 30 Max length 50 Max height difference 30 Operation range Cooling C 15 to 46 Heating 15 to 24 Drain hose Material LDPE Size mm Ø13 0 I D Ø16 0 to Ø16 8 O D NOTES Specifications are based on the following...

Page 71: ...6 315 20 18 Airflow 600 109 353 330 Pitch of bolts for installation Pitch of bolts for installation 4 M10 hole 820 19 68 716 20 Drain port Ø42 37 410 Bottom view Side view Valve part 119 184 194 65 2 1 Model AOYG24KBTB 2 Dimensions OUTDOOR UNIT AOYG24 54KBTB OUTDOOR UNIT AOYG24 54KBTB ...

Page 72: ...iquid valve Ф28 Cable port Ф28 Cable port 89 650 35 7 48 143 147 39 8 53 9 Liquid 40 320 354 8 62 9 Gas 320 139 8 Ф28 Cable port Ф28 Cable port 96 50 120 Pipe port 55 25 40 5 264 6 351 9 Pipe Cable port 47 6 15 2 62 6 15 6 Rear view 50 Ф28 Cable port Ф28 Cable port 25 141 9 70 67 Pipe port 66 2 2 Models AOYG30KBTB and AOYG36KBTB 2 Dimensions OUTDOOR UNIT AOYG24 54KBTB OUTDOOR UNIT AOYG24 54KBTB ...

Page 73: ...40 320 354 8 62 9 Gas 12 9 297 2 Gas valve Liquid valve Ф28 Cable port 1 1 8 29 Pipe port 23 4 129 1 85 3 50 29 Pipe port A 95 89 A 3 Way valve Liquid 3 Way valve Gas 320 139 8 96 40 5 Ф28 Cable port 120 Pipe port 55 25 50 B B 50 25 141 9 70 67 Pipe port 264 6 351 9 47 6 15 2 62 6 15 6 67 2 3 Models AOYG45KBTB and AOYG54KBTB 2 Dimensions OUTDOOR UNIT AOYG24 54KBTB OUTDOOR UNIT AOYG24 54KBTB ...

Page 74: ...ation When the upper space is open Unit mm Obstacles at rear only Obstacles at rear and sides 100 or more 250 or more 100 or more 100 or more Obstacles at front Obstacles at front and rear 600 or more 600 or more 100 or more When there is an obstruction in the upper space Unit mm Obstacles at rear and above Obstacles at rear sides and above 100 or more Max 200 600 or more 250 or more 100 or more M...

Page 75: ...ce as shown in the following ex ample When an obstruction in the upper space When the upper space is open Unit mm Obstacles at rear only Obstacles at front only 200 or more 250 or more 1 000 or more 250 or more Obstacles at front and rear 200 or more 1 000 or more 250 or more When an obstruction in the upper space Unit mm Obstacles at rear and above 1 500 or more 200 or more 250 or more 250 or mor...

Page 76: ...unit in two stage where the drain water could freeze Otherwise the drainage from the upper unit may form ice and cause a malfunction of the lower unit When the outdoor temperature is 0 C or less do not use the accessory drain pipe and drain cap If the drain pipe and drain cap are used the drain water in the pipe may freeze in extremely cold climate For reverse cycle model only In area with heavy s...

Page 77: ...ore 100 or more When there are obstacles at the front only When there are obstacles at the front and rear 500 or more 500 or more 100 or more When there is an obstruction in the upper space Unit mm When there are obstacles at the rear and above When there are obstacles at the rear sides and above 300 or more Max 500 1 000 or more 1 000 or more 200 or more 250 or more 500 or more Max 500 71 3 2 Mod...

Page 78: ...r more When there are obstacles at the front and rear 500 or more 1 500 or more 250 or more When there is an obstruction in the upper space Unit mm When there are obstacles at the rear and above 1 500 or more 500 or more 250 or more 250 or more Max 300 1 500 or more 72 3 2 Models AOYG30KBTB AOYG36KBTB AOYG45KBTB and AOYG54KBTB 3 Installation space OUTDOOR UNIT AOYG24 54KBTB OUTDOOR UNIT AOYG24 54K...

Page 79: ...r unit in two stage where the drain water could freeze Otherwise the drainage from the upper unit may form ice and cause a malfunction of the lower unit When the outdoor temperature is 0 C or less do not use the accessory drain pipe and drain cap If the drain pipe and drain cap are used the drain water in the pipe may freeze in extremely cold climate For reverse cycle model only In area with heavy...

Page 80: ...ing Pressure switch Sub accumulator ThC ThR ThD ThPI ThO ThHO ThC Thermistor Compressor temperature Thermistor Discharge temperature Thermistor Outdoor temperature Thermistor Heat Exchanger Out temperature ThD ThO ThHO Thermistor Room temperature Thermistor Pipe temperature ThR ThPI 74 4 1 Models AOYG24KBTB and AOYG30KBTB 4 Refrigerant circuit OUTDOOR UNIT AOYG24 54KBTB OUTDOOR UNIT AOYG24 54KBTB ...

Page 81: ... Sub accumulator ThC ThR ThD ThPI ThO ThHO ThC Thermistor Compressor temperature Thermistor Discharge temperature Thermistor Outdoor temperature Thermistor Heat Exchanger Out temperature ThD ThO ThHO Thermistor Room temperature Thermistor Pipe temperature ThR ThPI Pressure sensor 75 4 2 Models AOYG36KBTB AOYG45KBTB and AOYG54KBTB 4 Refrigerant circuit OUTDOOR UNIT AOYG24 54KBTB OUTDOOR UNIT AOYG24...

Page 82: ...5 Wiring diagrams 5 1 Model AOYG24KBTB 5 2 Model AOYG30KBTB 76 5 1 Model AOYG24KBTB 5 Wiring diagrams OUTDOOR UNIT AOYG24 54KBTB OUTDOOR UNIT AOYG24 54KBTB ...

Page 83: ...5 3 Model AOYG36KBTB 5 4 Models AOYG45KBTB and AOYG54KBTB 77 5 3 Model AOYG36KBTB 5 Wiring diagrams OUTDOOR UNIT AOYG24 54KBTB OUTDOOR UNIT AOYG24 54KBTB ...

Page 84: ... 0 930 0 914 Indoor unit is lower than outdoor unit 2 5 1 000 0 991 0 981 0 963 0 946 0 930 0 914 7 5 0 991 0 981 0 963 0 946 0 930 0 914 10 0 981 0 963 0 946 0 930 0 914 20 0 946 0 930 0 914 25 0 930 0 914 HEATING Pipe length m 5 7 5 10 15 20 25 30 Height difference H m Indoor unit is higher than outdoor unit 1 25 0 871 0 855 20 0 887 0 871 0 855 10 0 952 0 903 0 887 0 871 0 855 7 5 0 976 0 952 0...

Page 85: ... 0 995 0 984 0 973 0 962 0 951 20 0 984 0 973 0 962 0 951 30 0 973 0 962 0 951 HEATING Pipe length m 5 7 5 10 20 30 40 50 Height difference H m Indoor unit is higher than outdoor unit 1 30 0 931 0 914 0 899 20 0 954 0 931 0 914 0 899 10 0 990 0 954 0 931 0 914 0 899 7 5 1 000 0 990 0 954 0 931 0 914 0 899 5 1 000 1 000 0 990 0 954 0 931 0 914 0 899 0 1 000 1 000 0 990 0 954 0 931 0 914 0 899 Indoo...

Page 86: ... 0 989 0 968 0 947 0 926 0 905 20 0 968 0 947 0 926 0 905 30 0 947 0 926 0 905 HEATING Pipe length m 5 7 5 10 20 30 40 50 Height difference H m Indoor unit is higher than outdoor unit 1 30 0 978 0 968 0 958 20 0 988 0 978 0 968 0 958 10 0 998 0 988 0 978 0 968 0 958 7 5 1 000 0 998 0 988 0 978 0 968 0 958 5 1 000 1 000 0 998 0 988 0 978 0 968 0 958 0 1 000 1 000 0 998 0 988 0 978 0 968 0 958 Indoo...

Page 87: ... 0 989 0 967 0 945 0 923 0 901 20 0 967 0 945 0 923 0 901 30 0 945 0 923 0 901 HEATING Pipe length m 5 7 5 10 20 30 40 50 Height difference H m Indoor unit is higher than outdoor unit 1 30 0 978 0 968 0 958 20 0 988 0 978 0 968 0 958 10 0 998 0 988 0 978 0 968 0 958 7 5 1 000 0 998 0 988 0 978 0 968 0 958 5 1 000 1 000 0 998 0 988 0 978 0 968 0 958 0 1 000 1 000 0 998 0 988 0 978 0 968 0 958 Indoo...

Page 88: ...rigerant type R32 Refrigerant amount g 1 900 Refrigerant charge Total pipe length m 30 or less 40 50 Max 40 g m Additional charge amount g 0 400 800 7 3 Models AOYG45KBTB and AOYG54KBTB Refrigerant type R32 Refrigerant amount g 2 700 Refrigerant charge Total pipe length m 30 or less 40 50 Max 40 g m Additional charge amount g 0 400 800 82 7 1 Model AOYG24KBTB 7 Additional charge calculation OUTDOO...

Page 89: ...odels AOYG30KBTB and AOYG36KBTB Cooling m3 h 3 750 l s 1 042 CFM 2 207 Heating m3 h 3 750 l s 1 042 CFM 2 207 8 3 Models AOYG45KBTB and AOYG54KBTB Cooling m3 h 4 450 l s 1 236 CFM 2 619 Heating m3 h 4 450 l s 1 236 CFM 2 619 83 8 1 Model AOYG24KBTB 8 Airflow OUTDOOR UNIT AOYG24 54KBTB OUTDOOR UNIT AOYG24 54KBTB ...

Page 90: ...ncy Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Model AOYG30KBTB Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 0002 μbar Octave band center frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band s...

Page 91: ... 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Model AOYG45KBTB Cooling 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 0002 μbar Octave band center frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB...

Page 92: ...NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Heating 0 10 20 30 40 50 60 70 80 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 0002 μbar Octave band center frequency Hz NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 86 9 1 Noise level curve 9 Operation noise sound pressure OUTDOOR UNIT AOYG24 54KBTB OUTDOOR UNIT AOYG24 54KBTB ...

Page 93: ...Rear Airflow Rear view Side view NOTE Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above 87 9 2 Sound level check point 9 Operation noise sound pressure OUTDOOR UNIT AOYG24 54KBTB OUTDOOR UNIT AOYG24 54KBTB ...

Page 94: ... Model name AOYG45KBTB AOYG54KBTB Power supply Voltage V 230 Frequency Hz 50 Max operating current 1 A 28 5 Starting current A 16 0 19 4 Wiring spec 2 Circuit breaker current A 32 Power cable mm2 4 0 Connection cable 3 Cross sectional area mm2 1 5 Limited wiring length m 51 1 Maximum current is the total current of the indoor unit and the outdoor unit 2 Selected sample based on Japan Electrotechni...

Page 95: ...Y mode Activate 20 C Compressor stop Reset 15 C Compressor restart Type of protection Protection form Model AOYG30KBTB AOYG36KBTB Circuit protection Current fuse Main PCB 250 V 30 A 250 V 3 15 A 250 V 10 A 2 Fan motor protection Thermal protection program Activate 122 8 C Fan motor stop Reset 116 9 C Fan motor restart Compressor protection Thermal protection program Discharge temp Activate 110 C C...

Page 96: ...r restart Compressor protection Thermal protection program Discharge temp Activate 110 C Compressor stop Reset After 7 minutes Compressor restart Thermal protection program Compressor temp Activate 108 C Compressor stop Reset 80 C or less Compressor restart Thermal protection program Outdoor temp Only in COOL or DRY mode Activate 20 C Compressor stop Reset 15 C Compressor restart 90 11 Safety devi...

Page 97: ...imer or on off switch to a connector on the control PCB of the outdoor unit NOTE Product performance may drop depending on some conditions such as the outdoor temper ature Circuit diagram example Outdoor unit control PCB Connected unit Locally purchased Example Switch Signal 10m Connector 1 2 1 2 P580 PA580 Contact capacity DC 24 V or more 10 mA or more Make the distance from the PCB to the connec...

Page 98: ...1 2 P580 PA580 Contact capacity DC 24 V or more 10 mA or more Make the distance from the PCB to the connected unit within 10 m Construct a circuit as shown in this figure with using optional parts mentioned below Input signal On in Peak cut mode Input signal Off in normal operation To set the level of Peak cut mode refer to Peak cut mode on page 98 On Off On Off Input signal Peak cut mode Optional...

Page 99: ...it control PCB Example Relay unit Connected unit Locally purchased Example Fan Signal Connector 1 2 1 2 10m 12 V On Off P590 On Off PA590 Output voltage Vcc DC 12 V 50 mA or less Make the distance from the PCB to the connected unit within 10 m Error Normal On Off Error status Output signal Optional part Part name Model name Exterior External connect kit UTY XWZXZ3 External output wire 93 12 2 Exte...

Page 100: ... Connector 1 2 1 2 10m 12 V On Off P590 On Off PA590 Output voltage Vcc DC 12 V 50 mA or less Make the distance from the PCB to the connected unit within 10 m Operation Stop On Off Compressor status Output signal Optional part Part name Model name Exterior External connect kit UTY XWZXZ3 External output wire 94 12 2 External output 12 External input and output 30 54 models OUTDOOR UNIT AOYG24 54KB...

Page 101: ...ttons discharge the static electricity from your body Never touch the terminals or the patterns on the parts that are mounted on the PCB 13 1 Control PCB and switch buttons location Control PCB of the outdoor unit is located as shown in the following figure LED lamps Switch buttons 95 13 1 Control PCB and switch buttons location 13 Function settings 30 54 models OUTDOOR UNIT AOYG24 54KBTB OUTDOOR ...

Page 102: ...s low noise level 5 PEAK CUT MODE L4 L5 and L6 Orange Lights on during Peak cut mode when local setting is activated Lighting pattern of L4 L5 and L6 indicates peak cut level Switch button Function or operation method S134 MODE Switches between Local setting and Error code display S133 SELECT Switches between the individual Local settings and the Error code displays S132 ENTER Switches between the...

Page 103: ...tton S133 and adjust the LED lamps as shown below PEAK CUT MODE 1 Low MODE 2 Lower Blink Blink L4 L5 L6 6 Press the ENTER switch button S132 and fix it PEAK CUT MODE 1 Low MODE 2 Lower L4 L5 L6 7 To return to Operating status display Normal operation press the EXIT switch button S131 In case of missing how many times you pressed the SELECT and ENTER switch buttons 1 To return to Operation status d...

Page 104: ...adjust the LED lamps as shown below 100 of rated input ratio 75 of rated input ratio 50 of rated input ratio 0 of rated input ratio Blink Blink Blink Blink Blink PEAK CUT L4 L5 L6 6 Press the ENTER switch button S132 and fix it 100 of rated input ratio 75 of rated input ratio 50 of rated input ratio 0 of rated input ratio PEAK CUT L4 L5 L6 7 To return to Operating status display Normal operation p...

Page 105: ...ation manual 1 Drain pipe 1 14 2 Models AOYG30KBTB AOYG36KBTB AOYG45KBTB and AOYG54KBTB Part name Exterior Q ty Part name Exterior Q ty Installation manual 1 Drain cap 3 Drain pipe 1 One touch bush 2 99 14 1 Model AOYG24KBTB 14 Accessories OUTDOOR UNIT AOYG24 54KBTB OUTDOOR UNIT AOYG24 54KBTB ...

Page 106: ...r Part name Model name Summary External connect kit UTY XWZXZ3 Use to operate the external input and output functions of outdoor unit For 30 54 models 100 15 Optional parts OUTDOOR UNIT AOYG24 54KBTB OUTDOOR UNIT AOYG24 54KBTB ...

Reviews: