13-2. Local setting procedure
NOTE:
Before performing the function setting, be sure to stop the operation of the air conditioner.
¢
Low noise mode
1.
Press the MODE switch button (S134) for 3 seconds or more to switch to “Local setting mode”.
2.
After confirming the LED lamp of POWER/MODE blinks 9 times, press the ENTER switch but-
ton (S132).
POWER
MODE
ERROR
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
PUMP
DOWN
LOW NOISE
PEAK CUT
Blinks
(9 times
)
Sign “
”: Lights off
3.
Press the SELECT switch button (S133), and adjust the LED lamp as shown below. Then the
LED lamp indicates the current setting.
(L2)
(L3)
LOW NOISE
Blink
LOW NOISE
MODE
4.
Press the ENTER switch button (S132).
(L2)
(L3)
LOW NOISE
LOW NOISE
MOD
E
Sign “ ”: Lights on
5.
Press the SELECT switch button (S133), and adjust the LED lamps as shown below.
PEAK CUT
MODE 1: Low
MODE 2: Lower
Blink
Blink
(L4)
(L5)
(L6)
6.
Press the ENTER switch button (S132) and fix it.
PEAK CUT
MODE 1: Low
MODE 2: Lower
(L4)
(L5)
(L6)
7.
To return to “Operating status display (Normal operation)”, press the EXIT switch button
(S131).
In case of missing how many times you pressed the SELECT and ENTER switch buttons:
1. To return to “Operation status display (Normal operation)”, press the EXIT switch button once.
2. Restart from the beginning of setting procedure.
NOTE:
In case of missing how many times you pressed the SELECT and ENTER switch buttons,
you must redo the setting procedure. Return to “Operation status display (Normal opera-
tion)” by pressing the EXIT switch button once, and restart from the beginning of the setting
procedure.
- 97 -
13-2. Local setting procedure
13. Function settings (30-54 models)
O
U
TD
O
O
R
U
N
IT
A
O
YG
24
-5
4K
B
TB
O
U
TD
O
O
R
U
N
IT
A
O
YG
24
-5
4K
B
TB
Summary of Contents for AUXG24KRLB
Page 6: ......
Page 7: ...Part 1 INDOOR UNIT CASSETTE TYPE AUXG24KRLB AUXG30KRLB AUXG36KRLB AUXG45KRLB AUXG54KRLB ...
Page 66: ... 60 11 3 Others 11 Optional parts CASSETTE TYPE AUXG24 54KRLB CASSETTE TYPE AUXG24 54KRLB ...
Page 67: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG24KBTB AOYG30KBTB AOYG36KBTB AOYG45KBTB AOYG54KBTB ...