En-7

Tighten with 2 wrenches.

Holding wrench

Flare nut 

Connection pipe

Torque wrench

Indoor unit pipe  

(Body side)

Flare nut [mm (in.)]

Tightening torque [N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1,100)

5.2. Installing heat insulation

After checking for gas leaks, insulate by wrapping insulation around the two parts (Gas 

and Liquid) of the indoor unit coupling, using the coupler heat insulation.

After installing the coupler heat insulation, wrap both ends with vinyl tape so that there is 

no gap.

Secure both ends of the heat insulation material using nylon fasteners.

Coupler heat insulation (Small)

Coupler heat insulation (Large)

Indoor unit side

 

CAUTION

There should be no gaps between the insulation and the product.

 

 

CAUTION

After connecting the piping, check the all joints for gas leakage with gas leak detector.
Once the pressure checking has been completed using nitrogen, please refer to the 

outdoor unit installation manual to complete the evacuation process.
Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to 

do so may cause water leaks.

6.  ELECTRICAL WIRING

 

WARNING

•  Electrical  work  must  be  performed  in  accordance  with  this  Manual  by  a  person 

certified under the national or regional regulations. Be sure to use a dedicated circuit 

for the unit. 

  An insufficient power supply circuit or improperly performed electrical work can cause 

serious accidents such as electric shock or fire.

•  Before starting work, check that power is not being supplied to the indoor unit and 

outdoor unit.

•  For wiring, use the prescribed type of cables, connect them securely, making sure 

that there are no external forces of the cables applied to the terminal connections.

  Improperly  connected  or  secured  cables  can  cause  serious  accidents  such  as 

overheating the terminals, electric shock, or fire.

•  Securely install the electrical box cover on the unit. 

  An  improperly  installed  electrical  box  cover  can  cause  serious  accidents  such  as 

electric shock or fire through exposure to dust or water.

 

WARNING

•  Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit 

could result.

•  Use  the  included  connection  cables  and  power  cables  or  ones  specified  by  the 

manufacturer.  Improper  connections,  insufficient  insulation,  or  exceeding  the 

allowable current can cause electric shock or fire.

•  Do not modify the power cables, use extension cables, or use any branches in the 

wiring.  Improper  connections,  insufficient  insulation,  or  exceeding  the  allowable 

current can cause electric shock or fire.

 

Match  the  terminal  block  numbers  and  connection  cable  colors  with  those  of  the 

outdoor unit. Erroneous wiring may cause burning of the electric parts.

•  Securely connect the connection cables to the terminal board. In addition, secure the 

cables with wiring holders. Improper connections, either in the wiring or at the ends 

of the wiring, can cause a malfunction, electric shock, or fire.

  Always fasten the outside covering of the connection cable with the cable clamp. (If 

the insulator is chafed, electric leakage may occur.)

•  Install a earth leakage breaker. In addition, install the earth leakage breaker so that 

the entire AC main power supply is cut off at the same time. Otherwise, electric shock 

or fire could result.

  Always connect the earth (ground) cable.

  Improper earthing (grounding) work can cause electric shocks.

  Install the remote controller cables so as not to be direct touched with your hand.

•  Perform wiring work in accordance with standards so that the air conditioner can be 

operated safely and positively.

•  Connect the connection cable firmly to the terminal board. Imperfect installation may 

cause a fire.

 

CAUTION

•  Earth (Ground) the unit. 

  Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a 

telephone earth (ground) cable. 

  Improper earthing (grounding) may cause electric shock.

•  Do not connect power supply cables to the connection or remote controller terminals, 

as this will damage the product.

•  Never bundle the power supply cable and connection cable, remote controller cable 

together.

  Separate these cable by 50 mm or more.

  Bundling these cables together will cause miss operation or breakdown.

•  When handling PCB, static electricity charged in the body may cause malfunction of 

the PCB. Follow the cautions below:

•  Establish a ground for the indoor and outdoor units and peripheral devices.
•  Cut power (breaker) off.
•  Touch  metal  part  of  the  indoor  and  outdoor  units  for  more  than  10  seconds  to 

discharge static electricity charged in the body.

•  Do not touch terminals of parts and patterns implemented on PCB.

(1)  Use ring terminals with insulating sleeves as shown in the figure below to connect to 

the terminal block.

(2)  Securely clamp the ring terminals to the cables using an appropriate tool so that the 

cables do not come loose.

(3)  Use the specified cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws.

 

Do not use a screwdriver that is too small, otherwise, the screw heads may be 

damaged and prevent the screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.

(6)  See the table for the terminal screw tightening torques.
(7)  Please do not fix 2 power supply cables with 1 screw.

9379123143_IM.indb   7

10/16/2017   08:54:48

Summary of Contents for ARYG LHTA 1ph

Page 1: ... ducto Únicamente para personal de servicio autorizado MANUALE D INSTALLAZIONE Unità interna Tipo di condotto A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Εσωτερική μονάδα Τύπος αγωγού Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO Unidade interior Tipo conduta Somente para o pessoal do serviço técnico autorizado РУКОВОДСТВО ПО УСТАНОВКЕ Внутренний мод...

Page 2: ...e display range 0 1 to 3 8 MPa Charging hose To increase pressure resistance the hose material and base size were changed Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Gas leakage detector Special gas leakage detector for HFC refrigerant R410A 1 SAFETY PRECAUTIONS Be sure to read this Manual thoroughly before installation The warnings and precautions indica...

Page 3: ...ise the expansion valve or capillary tube may become blocked with contaminants Improper pipe selection will degrade performance As an air conditioner using R410A in curs pressure higher than when using conventional refrigerant it is necessary to choose adequate materials Thicknesses of copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the...

Page 4: ...nder 10 years old may approach the unit take preventive measures so that they cannot reach the unit 1 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 2 Leave the space required to service the air conditioner 3 Install the unit where connection to the outdoor unit is easy 4 Install the unit where the connection pipe can be easily installed 5 Inst...

Page 5: ...r filter is not installed the heat exchanger may be clogged and its performance may decrease 4 4 Installing the drain hose CAUTION Install the drain hose in accordance with the instructions in this installation manual and keep the area warm enough to prevent condensation Problems with the piping may lead to water leaks Be sure to properly insulate the drain hose so that the water will not drip fro...

Page 6: ...ed to provide a trap for the safety drain pipe If the safety drain pipe is connected to the main drain pipe make the connection below the trap on the main drain pipe Drain pipe main Drain pipe safety Unit Once installation is complete check the flow of the drain water 5 PIPE INSTALLATION WARNING During installation make sure that the refrigerant pipe is attached firmly before you run the compresso...

Page 7: ...electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoor unit Erroneous wiring may cause burning of the electric parts Securely connect the connection cables to the terminal board In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire...

Page 8: ...oor units by attaching an earth ground cable Unit shall be grounded in compliance with the country or region s regulations CAUTION Be sure to refer to the above diagram for do correct field wiring Wrong wiring causes malfunction of the unit Check local electrical rules and also any specific wiring instructions or limitation 6 2 Connection cable preparation Keep the earth ground wire longer than th...

Page 9: ...se connect the connector to the front case Screws SET BACK Front case back side Rear case Connector When remote controller cable is concealed 1 Conceal the remote controller cable 2 Pass the remote controller cable through the hole in the rear case and connect the remote controller cable to the remote controller terminal board specified in figure 3 Clamp the remote controller cable sheath with the...

Page 10: ...R SET button for a few seconds until the setting value stops flashing If the setting value display changes or if is displayed when the flashing stops the setting value has not been set correctly An invalid setting value may have been selected for the indoor unit 6 Repeat steps 2 to 5 to perform additional settings Press the SET TEMP buttons and FAN button simultaneously again for more than 5 secon...

Page 11: ... 1 Filter sign 2 Cooling room temperature correction 3 Heating room temperature correction 4 Auto restart 5 Indoor room temperature sensor switching function 6 External input control 7 Room temperature control switching 8 Indoor unit fan control for energy saving for cooling After completing the Function Setting be sure to turn off the power and turn it on again SETTING THE ROOM TEMPERATURE DETECT...

Page 12: ...troller setting again NOTE When different indoor unit models are connected using the group control system some functions may no longer be available If the group control system contains multiple units that are operated simultaneously con nect and set the units as shown below Auto changeover operates under the same mode with model unit number 00 It should not be connected to any other Gr that is not...

Page 13: ...ts free of any obstacles No cooling No heating After installation is completed has the proper operation and handling been explained to the user 11 TEST RUN CHECK ITEMS 1 Is operation of each button on the remote controller normal 2 Is the drain normal 3 Is there any abnormal noise and vibration during operation Do not operate the air conditioner in test run for a long time OPERATION METHOD For the...

Page 14: ...le temp sensor error Indoor unit fan motor error Drain pump error Damper error Indoor unit error Outdoor unit main PCB model information error or communication error Inverter error Active filter error PFC circuit error Trip terminal L error Display PCB microcomputers communication error Discharge temp sensor error Compressor temp sensor error Outdoor unit Heat Ex liquid temp sensor error Outdoor t...

Page 15: ...9379123143_IM indb 15 10 16 2017 08 55 11 ...

Reviews: