En-4

4.  INSTALLATION WORK

 

WARNING

Do not turn on the power until all installation work is complete.

Carrying and installation of the unit should be performed by a sufficient number of 

people and with sufficient equipment that is adequate for the weight of the unit.

Performing such work with an insufficient number of people or with inadequate equip

-

ment could result in dropping of the unit or personal injury.

 

CAUTION

For installation details, refer to the technical data.

4.1. Selecting an installation location

Decide the mounting position together with the customer as follows.

 

WARNING

Select installation locations that can properly support the weight of the indoor unit 

and which will not amplify sound or vibration. If the installation location is not strong 

enough, the indoor unit may fall and cause injuries. 
Install the units securely so that they do not topple or fall.

 

CAUTION

Do not install the indoor unit in the following areas:

• 

Area with high salt content, such as at the seaside.  

It will deteriorate metal parts, causing the parts to fall or the unit to leak water.

•  Area filled with mineral oil or containing a large amount of splashed oil or steam, 

such as a kitchen.  

It will deteriorate plastic parts, causing the parts to fall or the unit to leak water.

• 

Area that generates substances that adversely affect the equipment, such as sulfuric 

gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to 

corrode, which can cause refrigerant leakage.

•  Area that can cause combustible gas to leak, contains suspended carbon fibers or 

flammable dust, or volatile inflammables such as paint thinner or gasoline. If gas 

leaks and settles around the unit, it can cause a fire.

• 

Area where animals may urinate on the unit or ammonia may be generated.

Do not use the unit for special purposes, such as storing food, raising animals, growing 

plants, or preserving precision devices or art objects. It can degrade the quality of the 

preserved or stored objects.
Do not install where there is the danger of combustible gas leakage.

Do not install the unit near a source of heat, steam, or flammable gas.

Install the unit where drainage does not cause any trouble.
Install the indoor unit, outdoor unit, power supply cable, connection cable, and remote 

control cable at least 1 m away from a television or radio receivers. The purpose of this 

is to prevent TV reception interference or radio noise. 

 

(Even if they are installed more than 1 m apart, you could still receive noise under 

some signal conditions.)

Install the unit where ambient temperature does not reach 60°C or more. 

 

Take a measure such as ventilation for an environment in which heat is retained.

If children under 10 years old may approach the unit, take preventive measures so that 

they cannot reach the unit.

(1)  The inlet and outlet ports should not be obstructed; the air should be able to blow all 

over the room.

(2)  Leave the space required to service the air conditioner.

(3)  Install the unit where connection to the outdoor unit is easy.

(4)  Install the unit where the connection pipe can be easily installed.

(5)  Install the unit where the drain pipe can be easily installed.

(6)  Install the unit where noise and vibrations are not amplified.

(7)  Take servicing, etc., into consideration and leave the spaces. Also install the unit where 

the filter can be removed.

(8) 

Do not install the unit where it will be exposed to direct sunlight.  

Correct initial installation location is important because it is difficult to move unit after it is 

installed.

4.2. Installation dimension

Install at least 20mm from the ceiling.

2500 or more

(When no

ceiling)

Floor

(Service space)

Unit : mm

450

20 

or more

(For maintenance)

(1)  Maintenance work of the control box is possible with the maintenance hole of the 

measurement shown in the figure.

(2)  If maintenance work is to be done from the bottom side, the maintenance hole needs 

to be larger than the outside dimension of the indoor unit.

(3)  If maintenance work is to be done from the top, keep the space of the more than  

500 mm between the indoor unit and ceiling.

450

500

500

Control box

Maintenance hole

Unit : mm

4.3. Installing the unit

 

WARNING

Carrying and installation of the unit should be performed by a sufficient number of 

people and with sufficient equipment that is adequate for the weight of the unit. Per

-

forming such work with an insufficient number of people or with inadequate equipment 

could result in dropping of the unit or personal injury.
If the job is done with the panel frame only, there is a risk that the unit will come loose. 

Please take care.
When fastening the hangers, make the bolt positions uniform.

 

CAUTION

Confirm the directions of the air intake and outlet before installing the unit.

 

The unit takes in air from the fan side, and expels it from the evaporator side.
Check that duct work does not exceed the range of external static pressure of equip-

ment.

Make sure to insulate ducts to avoid the dew condensation.

Make sure to insulate between ducts and walls if metal ducts are used.

Please explain handling and washing methods of locally purchased materials to the 

customer.

To prevent people from touching the parts inside the unit, be sure to install grilles on 

the inlet and outlet ports. The grilles must be designed in such a way that cannot be 

removed without tools.

When connecting the duct to the outlet port of the indoor unit, be sure to insulate the 

outlet port and the installation screws to prevent water from leaking around the port.

RECOMMENDED RANGE OF

EXTERNAL STATIC PRESSURE [Pa]

100 - 250

9379123143_IM.indb   4

10/16/2017   08:54:41

Summary of Contents for ARYG LHTA 1ph

Page 1: ... ducto Únicamente para personal de servicio autorizado MANUALE D INSTALLAZIONE Unità interna Tipo di condotto A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Εσωτερική μονάδα Τύπος αγωγού Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO Unidade interior Tipo conduta Somente para o pessoal do serviço técnico autorizado РУКОВОДСТВО ПО УСТАНОВКЕ Внутренний мод...

Page 2: ...e display range 0 1 to 3 8 MPa Charging hose To increase pressure resistance the hose material and base size were changed Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Gas leakage detector Special gas leakage detector for HFC refrigerant R410A 1 SAFETY PRECAUTIONS Be sure to read this Manual thoroughly before installation The warnings and precautions indica...

Page 3: ...ise the expansion valve or capillary tube may become blocked with contaminants Improper pipe selection will degrade performance As an air conditioner using R410A in curs pressure higher than when using conventional refrigerant it is necessary to choose adequate materials Thicknesses of copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the...

Page 4: ...nder 10 years old may approach the unit take preventive measures so that they cannot reach the unit 1 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 2 Leave the space required to service the air conditioner 3 Install the unit where connection to the outdoor unit is easy 4 Install the unit where the connection pipe can be easily installed 5 Inst...

Page 5: ...r filter is not installed the heat exchanger may be clogged and its performance may decrease 4 4 Installing the drain hose CAUTION Install the drain hose in accordance with the instructions in this installation manual and keep the area warm enough to prevent condensation Problems with the piping may lead to water leaks Be sure to properly insulate the drain hose so that the water will not drip fro...

Page 6: ...ed to provide a trap for the safety drain pipe If the safety drain pipe is connected to the main drain pipe make the connection below the trap on the main drain pipe Drain pipe main Drain pipe safety Unit Once installation is complete check the flow of the drain water 5 PIPE INSTALLATION WARNING During installation make sure that the refrigerant pipe is attached firmly before you run the compresso...

Page 7: ...electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoor unit Erroneous wiring may cause burning of the electric parts Securely connect the connection cables to the terminal board In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire...

Page 8: ...oor units by attaching an earth ground cable Unit shall be grounded in compliance with the country or region s regulations CAUTION Be sure to refer to the above diagram for do correct field wiring Wrong wiring causes malfunction of the unit Check local electrical rules and also any specific wiring instructions or limitation 6 2 Connection cable preparation Keep the earth ground wire longer than th...

Page 9: ...se connect the connector to the front case Screws SET BACK Front case back side Rear case Connector When remote controller cable is concealed 1 Conceal the remote controller cable 2 Pass the remote controller cable through the hole in the rear case and connect the remote controller cable to the remote controller terminal board specified in figure 3 Clamp the remote controller cable sheath with the...

Page 10: ...R SET button for a few seconds until the setting value stops flashing If the setting value display changes or if is displayed when the flashing stops the setting value has not been set correctly An invalid setting value may have been selected for the indoor unit 6 Repeat steps 2 to 5 to perform additional settings Press the SET TEMP buttons and FAN button simultaneously again for more than 5 secon...

Page 11: ... 1 Filter sign 2 Cooling room temperature correction 3 Heating room temperature correction 4 Auto restart 5 Indoor room temperature sensor switching function 6 External input control 7 Room temperature control switching 8 Indoor unit fan control for energy saving for cooling After completing the Function Setting be sure to turn off the power and turn it on again SETTING THE ROOM TEMPERATURE DETECT...

Page 12: ...troller setting again NOTE When different indoor unit models are connected using the group control system some functions may no longer be available If the group control system contains multiple units that are operated simultaneously con nect and set the units as shown below Auto changeover operates under the same mode with model unit number 00 It should not be connected to any other Gr that is not...

Page 13: ...ts free of any obstacles No cooling No heating After installation is completed has the proper operation and handling been explained to the user 11 TEST RUN CHECK ITEMS 1 Is operation of each button on the remote controller normal 2 Is the drain normal 3 Is there any abnormal noise and vibration during operation Do not operate the air conditioner in test run for a long time OPERATION METHOD For the...

Page 14: ...le temp sensor error Indoor unit fan motor error Drain pump error Damper error Indoor unit error Outdoor unit main PCB model information error or communication error Inverter error Active filter error PFC circuit error Trip terminal L error Display PCB microcomputers communication error Discharge temp sensor error Compressor temp sensor error Outdoor unit Heat Ex liquid temp sensor error Outdoor t...

Page 15: ...9379123143_IM indb 15 10 16 2017 08 55 11 ...

Reviews: