background image

En-3

 CAUTION

5-Cabling

•  Check that cabling will not be subject to wear, corrosion, excessive pressure, vibra-

tion, sharp edges or any other adverse environmental effects.

•  The check shall also take into account the effects of aging or continual vibration from 

sources such as compressors or fans.

6-Detection of 

fl

 ammable refrigerants

•  Under no circumstances shall potential sources of ignition be used in the searching 

for or detection of refrigerant leaks.

•  A halide torch (or any other detector using a naked 

fl

 ame) shall not be used.

7-Leak detection methods

•  Electronic leak detectors shall be used to detect 

fl

 ammable refrigerants, but the 

sensitivity may not be adequate, or may need re-calibration. (Detection equipment 
shall be calibrated in a refrigerant-free area.)

•  Ensure that the detector is not a potential source of ignition and is suitable for the 

refrigerant used.

•  Leak detection equipment shall be set at a percentage of the LFL of the refrigerant 

and shall be calibrated to the refrigerant employed and the appropriate percentage of 
gas (25 % maximum) is con

fi

 rmed.

• Leak detection 

fl

 uids are suitable for use with most refrigerants but the use of 

detergents containing chlorine shall be avoided as the chlorine may react with the 
refrigerant and corrode the copper pipe-work.

•  If a leak is suspected, all naked 

fl

 ames shall be removed/extinguished.

•  If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall 

be recovered from the system, or isolated (by means of shut off valves) in a part of 
the system remote from the leak. 
Oxygen free nitrogen (OFN) shall then be purged through the system both before 
and during the brazing process.

8-Removal and evacuation

•  When breaking into the refrigerant circuit to make repairs – or for any other 

purpose –conventional procedures shall be used. 
However, it is important that best practice is followed since 

fl

 ammability is a consid-

eration. 
The following procedure shall be adhered to:

• remove refrigerant
•  purge the circuit with inert gas
• evacuate
•  purge again with inert gas
•  open the circuit by cutting or brazing

•  The refrigerant charge shall be recovered into the correct recovery cylinders. 
•  The system shall be “

fl

 ushed” with OFN to render the unit safe. 

•  This process may need to be repeated several times. 
•  Compressed air or oxygen shall not be used for this task.
•  Flushing shall be achieved by breaking the vacuum in the system with OFN and 

continuing to 

fi

 ll until the working pressure is achieved, then venting to atmosphere, 

and 

fi

 nally pulling down to a vacuum. 

•  This process shall be repeated until no refrigerant is within the system. 
• When the 

fi

 nal OFN charge is used, the system shall be vented down to atmospheric 

pressure to enable work to take place.

•  This operation is absolutely vital if brazing operations on the pipe work are to take 

place.

•  Ensure that the outlet for the vacuum pump is not close to any ignition sources and 

there is ventilation available.

9-Charging procedures

•  In addition to conventional charging procedures, the following requirements shall be 

followed.

-  Ensure that contamination of different refrigerants does not occur when using 

charging equipment. 
 Hoses or lines shall be as short as possible to minimize the amount of refrigerant 
contained in them.

-  Cylinders shall be kept upright.
-  Ensure that the refrigeration system is earthed prior to charging the system with 

refrigerant.

-  Label the system when charging is complete (if not already).
-  Extreme care shall be taken not to over

fi

 ll the refrigeration system.

•  Prior to recharging the system it shall be pressure tested with OFN. 
•  The system shall be leak tested on completion of charging but prior to commission-

ing. 

•  A follow up leak test shall be carried out prior to leaving the site.

 CAUTION

10-Decommissioning

•  Before carrying out this procedure, it is essential that the technician is completely 

familiar with the equipment and all its details.

•  It is recommended good practice that all refrigerants are recovered safely.
•  Prior to the task being carried out, an oil and refrigerant sample shall be taken in 

case analysis is required prior to re-use of reclaimed refrigerant.

•  It is essential that electrical power is available before the task is commenced.

a)  Become familiar with the equipment and its operation.
b)  Isolate system electrically.
c)  Before attempting the procedure ensure that:

•  mechanical handling equipment is available, if required, for handling refriger-

ant cylinders;

•  all personal protective equipment is available and being used correctly; 
•  the recovery process is supervised at all times by a competent person; 
•  recovery equipment and cylinders conform to the appropriate standards.

d)  Pump down refrigerant system, if possible.
e)  If a vacuum is not possible, make a manifold so that refrigerant can be removed 

from various parts of the system.

f)   Make sure that cylinder is situated on the scales before recovery takes place.
g)  Start the recovery machine and operate in accordance with manufacturer’s 

instructions.

h)  Do not over

fi

 ll cylinders. (No more than 80 % volume liquid charge).

i)   Do not exceed the maximum working pressure of the cylinder, even temporarily.
j)   When the cylinders have been 

fi

 lled correctly and the process completed, make 

sure that the cylinders and the equipment are removed from site promptly and all 
isolation valves on the equipment are closed off.

k)  Recovered refrigerant shall not be charged into another refrigeration system un-

less it has been cleaned and checked.

11-Labelling

•  Equipment shall be labelled stating that it has been de-commissioned and emptied 

of refrigerant. 

•  The label shall be dated and signed. 
•  Ensure that there are labels on the equipment stating the equipment contains 

fl

 am-

mable refrigerant.

12-Recovery

•  When removing refrigerant from a system, either for servicing or decommissioning, it 

is recommended good practice that all refrigerants are removed safely.

•  When transferring refrigerant into cylinders, ensure that only appropriate refrigerant 

recovery cylinders are employed.

•  Ensure that the correct number of cylinders for holding the total system charge are 

available. 

•  All cylinders to be used are designated for the recovered refrigerant and labelled for 

that refrigerant (i.e. special cylinders for the recovery of refrigerant). 

•  Cylinders shall be complete with pressure relief valve and associated shut-off valves 

in good working order.

•  Empty recovery cylinders are evacuated and, if possible, cooled before recovery 

occurs.

•  The recovery equipment shall be in good working order with a set of instructions 

concerning the equipment that is at hand and shall be suitable for the recovery of 

fl

 ammable refrigerants.

•  In addition, a set of calibrated weighing scales shall be available and in good working 

order.

•  Hoses shall be complete with leak-free disconnect couplings and in good condition.
•  Before using the recovery machine, check that it is in satisfactory working order, has 

been properly maintained and that any associated electrical components are sealed 
to prevent ignition in the event of a refrigerant release. 
Consult manufacturer if in doubt.

•  The recovered refrigerant shall be returned to the refrigerant supplier in the correct 

recovery cylinder, and the relevant Waste Transfer Note arranged. 

•  Do not mix refrigerants in recovery units and especially not in cylinders.
•  If compressors or compressor oils are to be removed, ensure that they have been 

evacuated to an acceptable level to make certain that 

fl

 ammable refrigerant does not 

remain within the lubricant. 

•  The evacuation process shall be carried out prior to returning the compressor to the 

suppliers. 

•  Only electric heating to the compressor body shall be employed to accelerate this 

process. 

•  When oil is drained from a system, it shall be carried out safely.

Explanation of symbols displayed on the indoor unit or outdoor unit.

WARNING

This symbol shows that this appliance uses a 

fl

 ammable 

refrigerant. 
If the refrigerant is leaked and exposed to an external igni-
tion source, there is a risk of 

fi

 re.

CAUTION

This symbol shows that the operation manual should be 
read carefully.

CAUTION

This symbol shows that a service personnel should be 
handling this equipment with reference to the installation 
manual.

CAUTION

This symbol shows that information is available such as 
the operating manual or installation manual.

9374342532_IM.indb   3

9374342532_IM.indb   3

2018/12/11   10:11:29

2018/12/11   10:11:29

Summary of Contents for ARXG-KLLAP Series

Page 1: ...installed in an explo sive atmosphere To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 5 min utes or more before you touch the electrical components This product contains no user serviceable parts Always consult experienced service technicians for repairing When moving or relocating the ...

Page 2: ...ntly far away from the site of installation repairing removing and disposal during which flammable refrigerant can possibly be released to the surrounding space Prior to work taking place the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks No Smoking signs shall be displayed 2 6 Ventilated area Ensure that the area is in the open or th...

Page 3: ...ior to re use of reclaimed refrigerant It is essential that electrical power is available before the task is commenced a Become familiar with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that mechanical handling equipment is available if required for handling refriger ant cylinders all personal protective equipment is available and being us...

Page 4: ... fall water leakage electric shock or fire Keep the Installation manual in a safe place and do not discard any other accessories until the installation work has been completed The following installation accessories are supplied Use them as required Name and Shape Q ty Name and Shape Q ty Operating manual 1 Cable tie large 4 Operating manual CD ROM 1 Cable tie medium 3 Installation manual This manu...

Page 5: ...rol cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Decide the mounting position with the cus...

Page 6: ...sed Air Intake grille Locally purchased Side inlet Side outlet Duct Insulation material Locally purchased Aluminum tape Aluminum tape Tapping screw for flange connection M4 x 10mm Locally purchased Flange Locally purchased Flange Locally purchased Air Duct Locally purchased Air Intake grille Locally purchased Bottom inlet Side outlet Duct Locally purchased Intake grille Locally purchased Air Air O...

Page 7: ...OOD VP25 O D 32 mm or more Rise Air bleeding PROHIBITED Trap Observe the following procedures to construct centralized drain pipe fittings VP30 or more O D 38 mm or more Downward gradient 1 100 or more 700 mm or less When drain pump is not used natural drainage CAUTION Set Drainage function setting DIP switch 101 1 in 5 3 DIP switch 101 setting If the drain pump is not used please replace with the...

Page 8: ...se as in the figure 2 Be sure to connect Drain pipe with adhesive polyvinyl chloride so that there is no leakage Applying area of adhesive Joint pipe Locally purchased Drain pipe VP25 Locally purchased 4 mm or less CAUTION Do not connect to the Drain hole with adhesive Using adhesive may cause damage and water leaks 3 After installing the Drain hose check if the drainage is smooth CAUTION To preve...

Page 9: ...ipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break The pipes are shaped by your hands Be careful not to collapse them Bend R70 mm or more with a pipe bender Do not bend the pipes in an angle more than 90 When pipes are repeatedly bend or stretched the material will harden making it difficult to bend or stretch them anymore Do not bend or stretch the pipes more tha...

Page 10: ...ard Imperfect installation may cause a fire Use ring terminals and tighten the terminal screws to the specified torques otherwise abnormal overheating may be produced and possibly cause heavy damage inside the unit CAUTION Be careful not to generate a spark as follows for using a flammable refrigerant Do not remove the fuse while the power is on Do not disconnect the wiring while the power is on I...

Page 11: ...ultaneous triple 18 model only Wired remote controller cable 3 wire type only Connection cable Indoor unit Primary Indoor unit Secondary Outdoor unit Earth Ground line Control line Power line Wired remote controller Remote controller cable Bus wire Locally purchased remote controller cable Max length 500 m Junction box Locally purchased Earth Ground line Red White Black Indoor unit Secondary Indoo...

Page 12: ...1 8 12 to 18 3 6 4 Connection wiring CAUTION Be careful not to mistake the power supply cable and connection wires when install ing Install so that the wires for the remote controller will not come in contact with other connection wires 1 Remove the control box cover 2 Connect the connection cable Cover Screw Connection cable Y1 Y2 TO REMOTE CONTROL UNIT Ex IN Y3 1 2 Y1 Y2 TO REMOTE CONTROL UNIT E...

Page 13: ...eration Stop mode or Forced stop mode can be selected with function setting of indoor unit A twisted pair cable 22 AWG should be used Maximum length of cable is 150 m 492 ft Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Y1 Y2 TO REMOTE CONTROL UNIT Ex IN Y...

Page 14: ...onnected set the function setting of indoor unit as indicated below Function Number 30 Set the Setting Number to 00 Default Function Number 31 Set the Setting Number to 02 Refer to 6 FUNCTION SETTING for details about Function number and Setting value 4 4 IR receiver unit Optional parts For the installation method please refer to the installation manual of IR receiver unit 4 4 1 Connection method ...

Page 15: ...REMOTE CONTROL UNIT Ex IN Y3 1 2 1 2 3 SW100 a 2 wire type DIP switch RC AD SW Factory setting 00 Since the remote controller address settings are automatically configured you do not need to configure them If configuring manually it is necessary to configure both the indoor unit and the remote controller For details please refer to the remote controller installation manual b 3 wire type DIP switch...

Page 16: ...nnection cable Remote controller cable Outdoor unit 1 Outdoor unit 2 Outdoor unit 3 Outdoor unit 4 Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 7 5 2 Multiple remote control Up to 2 remote controllers can be used to operate one indoor unit CAUTION Multiple installation method described above is prohibited to combine 3 Wired type with 2 Wired Type ...

Page 17: ...ly 3 Set the primary and secondary Remote controller setting 1 Turn on all of the indoor units 2 Set the primary and secondary settings Set the indoor unit that is connected to the outdoor unit using a transmission cable as the primary Function Number Setting Value Primary 51 00 Secondary 01 3 After completing the function settings turn off all of the indoor units and then turn them back on If err...

Page 18: ... changed Select the appropriate custom code Factory setting Function number Setting value Setting description 44 00 A 01 B 02 C 03 D External input control Operation Stop mode or Forced stop mode can be selected Factory setting Function number Setting value Setting description 46 00 Operation Stop mode 1 01 Setting prohibited 02 Forced stop mode 03 Operation Stop mode 2 Room temperature sensor swi...

Page 19: ...in accordance with the operating manual 1 Starting and stopping method operation switching temperature adjustment timer air flow switching and other remote controller operations 2 Cleaning and maintenance of the product and other items such as air filters and air louvers if applicable 3 Give the operating and installation manuals to the customer 4 If the indoor unit custom code is changed and the ...

Page 20: ...5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error 8 2 Sub cool Heat Ex gas inlet temp sensor error Sub cool Heat Ex gas outlet temp sensor error 8 3 Liquid pipe temp sensor error 8 4 Current sensor error 8 6 Discharge pressure sensor error Suction pressure sensor error High pressure switch error 9 4 Trip detection Error ...

Reviews: