background image

En-2

 1.1. Precautions for using R32 refrigerant

The basic installation work procedures are the same as conventional refrigerant (R410A, 
R22) models.
However, pay careful attention to the following points:

Since the working pressure is 1.6 times higher than that of refrigerant R22 models, 
some of the piping and installation and service tools are special. (Refer to “2.1. Instal-
lation tools”.)
Especially, when replacing a refrigerant R22 model with a new refrigerant R32 model, 
always replace the conventional piping and flare nuts with the R32 and R410A piping and 

fl

 are nuts on the outdoor unit side. 

For R32 and R410A, the same 

fl

 are nut on the outdoor unit side and pipe can be used.

Models that use refrigerant R32 and R410A have a different charging port thread diam-
eter to prevent erroneous charging with refrigerant R22 and for safety. Therefore, check 
beforehand. [The charging port thread diameter for R32 and R410A is 1/2-20 UNF.]

Be more careful than R22 so that foreign matter (oil, water, etc.) does not enter the 
piping. Also, when storing the piping ,securely seal the opening by pinching, taping, etc. 
(Handling of R32 is similar to R410A.)

 CAUTION

1-Installation (Space)

•  That the installation of pipe-work shall be kept to a minimum.
•  That pipe-work shall be protected from physical damage.
•  The appliance shall not be installed in an unventilated space, if that space is smaller 

than X m².

Amount of refrigerant charge 

M (kg)

Minimum room area 

X (m

2

)

 1.22

-

1.22 < M 

 1.23

1.45

1.23 < M 

 1.50

2.15

1.50 < M 

 1.75

2.92

1.75 < M 

 2.0

3.82

2.0 < M 

 2.5

5.96

2.5 < M 

 3.0

8.59

3.0 < M 

 3.5

11.68

3.5 < M 

 4.0

15.26

(IEC 60335-2-40)

•  That compliance with national gas regulations shall be observed.
•  That mechanical connections shall be accessible for maintenance purposes.
•  In cases that require mechanical ventilation, ventilation openings shall be kept clear 

of obstruction.

•  When disposing of the product is used, be based on national regulations, properly 

processed.

2-Servicing
2-1 Service personnel

•  Any person who is involved with working on or breaking into a refrigerant circuit 

should hold a current valid certi

fi

 cate from an industry-accredited assessment 

authority, which authorises their competence to handle refrigerants safely in accor-
dance with an industry recognised assessment speci

fi

 cation.

•  Servicing shall only be performed as recommended by the equipment manufacturer. 

Maintenance and repair requiring  the assistance of other skilled personnel shall be 
carried out under the supervision of the person competent in the use of 

fl

 ammable 

refrigerants.

•  Servicing shall be performed only as recommended by the manufacturer.

2-2 Work

•  Prior to beginning work on systems containing 

fl

 ammable refrigerants, safety checks 

are necessary to ensure that the risk of ignition is minimized. For repair to the refrig-
erating system, the precautions in 2-2 to 2-8 shall be complied with prior to conduct-
ing work on the system.

•  Work shall be undertaken under a controlled procedure so as to minimize the risk of 

fl

 ammable gas or vapour being present while the work is being performed.

•  All maintenance staff and others working in the local area shall be instructed on the 

nature of work being carried out.

•  Work in con

fi

 ned spaces shall be avoided.

•  The area around the workspace shall be sectioned off.
•  Ensure that the conditions within the area have been made safe by control of 

fl

 am-

mable material.

2-3 Checking for presence of refrigerant

•  The area shall be checked with an appropriate refrigerant detector prior to and during 

work, to ensure the technician is aware of potentially 

fl

 ammable atmospheres.

•  Ensure that the leak detection equipment being used is suitable for use with 

fl

 am-

mable refrigerants, i.e. nonsparking, adequately sealed or intrinsically safe.

2-4 Presence of 

fi

 re extinguisher

•  If any hot work is to be conducted on the refrigeration equipment or any associated 

parts, appropriate 

fi

 re extinguishing equipment shall be available at hand. 

•  Have a dry powder or CO

2

 

fi

 re extinguisher adjacent to the charging area.

 CAUTION

2-5 No ignition sources

•  No person carrying out work in relation to a refrigeration system which involves 

exposing any pipe work that contains or has contained 

fl

 ammable refrigerant shall 

use any sources of ignition in such a manner that it may lead to the risk of 

fi

 re or 

explosion.

•  All possible ignition sources, including cigarette smoking, should be kept suf

fi

 ciently 

far away from the site of installation, repairing, removing and disposal, during which 

fl

 ammable refrigerant can possibly be released to the surrounding space.

•  Prior to work taking place, the area around the equipment is to be surveyed to make 

sure that there are no 

fl

 ammable hazards or ignition risks. “No Smoking” signs shall 

be displayed.

2-6 Ventilated area

•  Ensure that the area is in the open or that it is adequately ventilated before breaking 

into the system or conducting any hot work.

•  A degree of ventilation shall continue during the period that the work is carried out.
•  The ventilation should safely disperse any released refrigerant and preferably expel 

it externally into the atmosphere.

2-7 Checks to the refrigeration equipment

•  Where electrical components are being changed, they shall be 

fi

 t for the purpose 

and to the correct speci

fi

 cation.

•  At all times the manufacturer’s maintenance and service guidelines shall be followed.
•  If in doubt consult the manufacturer’s technical department for assistance.
•  The following checks shall be applied to installations using 

fl

 ammable refrigerants.

-  The charge size is in accordance with the room size within which the refrigerant 

containing parts are installed.

-  The ventilation machinery and outlets are operating adequately and are not 

obstructed.

-  If an indirect refrigerating circuit is being used, the secondary circuit shall be 

checked for the presence of refrigerant. 

-  Marking to the equipment continues to be visible and legible. Markings and signs 

that are illegible shall be corrected.

-  Refrigeration pipe or components are installed in a position where they are unlikely 

to be exposed to any substance which may corrode refrigerant containing compo-
nents, unless the components are constructed of materials which are inherently 
resistant to being corroded or are suitably protected against being so corroded.

2-8 Checks to electrical devices

•  Repair and maintenance to electrical components shall include initial safety checks 

and component inspection procedures.

•  If a fault exists that could compromise safety, then no electrical supply shall be con-

nected to the circuit until it is satisfactorily dealt with.

•  If the fault cannot be corrected immediately but it is necessary to continue operation, 

an adequate temporary solution shall be used.

•  This shall be reported to the owner of the equipment so all parties are advised.
•  Initial safety checks shall include.

-  That capacitors are discharged: this shall be done in a safe manner to avoid pos-

sibility of sparking.

-  That there no live electrical components and wiring are exposed while charging, 

recovering or purging the system.

-  That there is continuity of earth bonding.

3-Repairs to sealed components

•  During repairs to sealed components, all electrical supplies shall be disconnected 

from the equipment being worked upon prior to any removal of sealed covers, etc.

•  If it is absolutely necessary to have an electrical supply to equipment during servic-

ing, then a permanently operating form of leak detection shall be located at the most 
critical point to warn of a potentially hazardous situation.

•  Particular attention shall be paid to the following to ensure that by working on electri-

cal components, the casing is not altered in such a way that the level of protection is 
affected.

•  This shall include damage to cables, excessive number of connections, terminals not 

made to original speci

fi

 cation, damage to seals, incorrect 

fi

 tting of glands, etc.

•  Ensure that apparatus is mounted securely.
•  Ensure that seals or sealing materials have not degraded such that they no longer 

serve the purpose of preventing the ingress of 

fl

 ammable atmospheres.

•  Replacement parts shall be in accordance with the manufacturer’s speci

fi

 cations.

NOTES:  The use of silicon sealant may inhibit the effectiveness of some types of leak 

detection equipment.
Intrinsically safe components do not have to be isolated prior to working on 
them.

4-Repair to intrinsically safe components

•  Do not apply any permanent inductive or capacitance loads to the circuit without 

ensuring that this will not exceed the permissible voltage and current permitted for 
the equipment in use.

•  Intrinsically safe components are the only types that can be worked on while live in 

the presence of a 

fl

 ammable atmosphere. 

•  The test apparatus shall be at the correct rating.
•  Replace components only with parts speci

fi

 ed by the manufacturer.

•  Other parts may result in the ignition of refrigerant in the atmosphere from a leak.

9374342532_IM.indb   2

9374342532_IM.indb   2

2018/12/11   10:11:29

2018/12/11   10:11:29

Summary of Contents for ARXG-KLLAP Series

Page 1: ...installed in an explo sive atmosphere To avoid getting an electric shock never touch the electrical components soon after the power supply has been turned off After turning off the power always wait 5 min utes or more before you touch the electrical components This product contains no user serviceable parts Always consult experienced service technicians for repairing When moving or relocating the ...

Page 2: ...ntly far away from the site of installation repairing removing and disposal during which flammable refrigerant can possibly be released to the surrounding space Prior to work taking place the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks No Smoking signs shall be displayed 2 6 Ventilated area Ensure that the area is in the open or th...

Page 3: ...ior to re use of reclaimed refrigerant It is essential that electrical power is available before the task is commenced a Become familiar with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that mechanical handling equipment is available if required for handling refriger ant cylinders all personal protective equipment is available and being us...

Page 4: ... fall water leakage electric shock or fire Keep the Installation manual in a safe place and do not discard any other accessories until the installation work has been completed The following installation accessories are supplied Use them as required Name and Shape Q ty Name and Shape Q ty Operating manual 1 Cable tie large 4 Operating manual CD ROM 1 Cable tie medium 3 Installation manual This manu...

Page 5: ...rol cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Decide the mounting position with the cus...

Page 6: ...sed Air Intake grille Locally purchased Side inlet Side outlet Duct Insulation material Locally purchased Aluminum tape Aluminum tape Tapping screw for flange connection M4 x 10mm Locally purchased Flange Locally purchased Flange Locally purchased Air Duct Locally purchased Air Intake grille Locally purchased Bottom inlet Side outlet Duct Locally purchased Intake grille Locally purchased Air Air O...

Page 7: ...OOD VP25 O D 32 mm or more Rise Air bleeding PROHIBITED Trap Observe the following procedures to construct centralized drain pipe fittings VP30 or more O D 38 mm or more Downward gradient 1 100 or more 700 mm or less When drain pump is not used natural drainage CAUTION Set Drainage function setting DIP switch 101 1 in 5 3 DIP switch 101 setting If the drain pump is not used please replace with the...

Page 8: ...se as in the figure 2 Be sure to connect Drain pipe with adhesive polyvinyl chloride so that there is no leakage Applying area of adhesive Joint pipe Locally purchased Drain pipe VP25 Locally purchased 4 mm or less CAUTION Do not connect to the Drain hole with adhesive Using adhesive may cause damage and water leaks 3 After installing the Drain hose check if the drainage is smooth CAUTION To preve...

Page 9: ...ipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break The pipes are shaped by your hands Be careful not to collapse them Bend R70 mm or more with a pipe bender Do not bend the pipes in an angle more than 90 When pipes are repeatedly bend or stretched the material will harden making it difficult to bend or stretch them anymore Do not bend or stretch the pipes more tha...

Page 10: ...ard Imperfect installation may cause a fire Use ring terminals and tighten the terminal screws to the specified torques otherwise abnormal overheating may be produced and possibly cause heavy damage inside the unit CAUTION Be careful not to generate a spark as follows for using a flammable refrigerant Do not remove the fuse while the power is on Do not disconnect the wiring while the power is on I...

Page 11: ...ultaneous triple 18 model only Wired remote controller cable 3 wire type only Connection cable Indoor unit Primary Indoor unit Secondary Outdoor unit Earth Ground line Control line Power line Wired remote controller Remote controller cable Bus wire Locally purchased remote controller cable Max length 500 m Junction box Locally purchased Earth Ground line Red White Black Indoor unit Secondary Indoo...

Page 12: ...1 8 12 to 18 3 6 4 Connection wiring CAUTION Be careful not to mistake the power supply cable and connection wires when install ing Install so that the wires for the remote controller will not come in contact with other connection wires 1 Remove the control box cover 2 Connect the connection cable Cover Screw Connection cable Y1 Y2 TO REMOTE CONTROL UNIT Ex IN Y3 1 2 Y1 Y2 TO REMOTE CONTROL UNIT E...

Page 13: ...eration Stop mode or Forced stop mode can be selected with function setting of indoor unit A twisted pair cable 22 AWG should be used Maximum length of cable is 150 m 492 ft Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Y1 Y2 TO REMOTE CONTROL UNIT Ex IN Y...

Page 14: ...onnected set the function setting of indoor unit as indicated below Function Number 30 Set the Setting Number to 00 Default Function Number 31 Set the Setting Number to 02 Refer to 6 FUNCTION SETTING for details about Function number and Setting value 4 4 IR receiver unit Optional parts For the installation method please refer to the installation manual of IR receiver unit 4 4 1 Connection method ...

Page 15: ...REMOTE CONTROL UNIT Ex IN Y3 1 2 1 2 3 SW100 a 2 wire type DIP switch RC AD SW Factory setting 00 Since the remote controller address settings are automatically configured you do not need to configure them If configuring manually it is necessary to configure both the indoor unit and the remote controller For details please refer to the remote controller installation manual b 3 wire type DIP switch...

Page 16: ...nnection cable Remote controller cable Outdoor unit 1 Outdoor unit 2 Outdoor unit 3 Outdoor unit 4 Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 7 5 2 Multiple remote control Up to 2 remote controllers can be used to operate one indoor unit CAUTION Multiple installation method described above is prohibited to combine 3 Wired type with 2 Wired Type ...

Page 17: ...ly 3 Set the primary and secondary Remote controller setting 1 Turn on all of the indoor units 2 Set the primary and secondary settings Set the indoor unit that is connected to the outdoor unit using a transmission cable as the primary Function Number Setting Value Primary 51 00 Secondary 01 3 After completing the function settings turn off all of the indoor units and then turn them back on If err...

Page 18: ... changed Select the appropriate custom code Factory setting Function number Setting value Setting description 44 00 A 01 B 02 C 03 D External input control Operation Stop mode or Forced stop mode can be selected Factory setting Function number Setting value Setting description 46 00 Operation Stop mode 1 01 Setting prohibited 02 Forced stop mode 03 Operation Stop mode 2 Room temperature sensor swi...

Page 19: ...in accordance with the operating manual 1 Starting and stopping method operation switching temperature adjustment timer air flow switching and other remote controller operations 2 Cleaning and maintenance of the product and other items such as air filters and air louvers if applicable 3 Give the operating and installation manuals to the customer 4 If the indoor unit custom code is changed and the ...

Page 20: ...5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor error 8 2 Sub cool Heat Ex gas inlet temp sensor error Sub cool Heat Ex gas outlet temp sensor error 8 3 Liquid pipe temp sensor error 8 4 Current sensor error 8 6 Discharge pressure sensor error Suction pressure sensor error High pressure switch error 9 4 Trip detection Error ...

Reviews: