background image

En-4

When an obstruction is present also in the upward area 

(Unit : mm)

(1)  Obstacles at rear and above only

(2)  Obstacles at rear, sides, and above 

only

 

100 
or more

Max. 500

1000 
or more

1500 
or more

80 
or more 100 

or more

300 
or more

3.3.2. Multiple outdoor unit installation

•  Provide at least 100 mm of space between the outdoor units if multiple units are 

installed.

•  When routing the piping from the side of an outdoor unit, provide space for the piping.

•  No more than 3 units must be installed side by side.

When 3 units or more are arranged in a line, provide the space as shown in the 
following example when an obstruction is present also in the upward area.

When the upward area is open 

(Unit : mm)

(1)  Obstacles at rear only

(2)  Obstacles at front only

1500 or more

300 or more

(3)  Obstacles at front and rear only

500 or more

1500 or more

When an obstruction is present also in the upward area 

(Unit : mm)

•  Obstacles at rear and above only

1500 or more

500 or more

Max. 300

1500 or more

3.3.3. Outdoor unit installation in multi row

*  The following settings are not recommended in case of cooling by a low outside tem-

perature. (Unit: mm)

(1)  Single parallel unit arrangement

(2)  Multiple parallel unit arrangement

100 or 
more

600 or more

1000 or more

2000 or 
more

500 or 
more

600 or more

1500 or more

3000 or 
more

3.4. Transporting the unit

 

WARNING

Do not touch the 

fi

 ns. Otherwise, personal injury could result.

 

CAUTION

When carrying the unit, hold the handles on the right and left sides and be careful.
If the outdoor unit is carried from the bottom, hands or 

fi

 ngers may be pinched.

Hoisting method

• When hoisting the outdoor unit, hook the rope on the outside of the foot as shown in 

the 

fi

 gure.

• Use suf

fi

 ciently strong rope to bear the unit’s weight.

• Place protective board or 

fi

 ller cloth at the place where the cabinet may come into 

contact with the rope to prevent damages. Without using them, the cabinet may be 
damaged or deformed.

• The center of gravity of the outdoor unit is shifted to the right. Be careful not to tilt to 

the heavy side causing it to fall.

• To prevent accidents caused by the unit swinging or falling down, do not apply any 

impact to the unit when it is hanging.

• When hoisting, do not hook the rope to the thermistor holder on the back of the 

outdoor unit.

Protective 
boards

Foot

Light 
side

Heavy 
side

700 to 
1000 mm

Lifting by forklift

• When using the forklift to lift the unit, pass 

the forklift arms through the opening space 
of the wooden delivery pallet.

• Be careful not to damage.

Wooden delivery 
pallet

Carrying by hand

• Carry slowly in the manner 

as shown on “Fig. B” hold-
ing the handles “Fig. A” 
in right and left sides. (Be 
careful not to touch with 
hands or objects.)

• Be sure to hold the 

handles on the sides of 
the unit. Otherwise, the 
suction grilles on the 
sides of the unit may be 
deformed.

Handle

Handle

Handle

Fig. A

Fig. B

3.5. Installing the unit

• Install 4 anchor bolts at the locations indicated with arrows in the figure.
• To reduce vibration, do not install the unit directly on the ground. Install it on a secure 

base (such as concrete blocks).

• The foundation shall support the legs of the unit and have a width of 80 mm or more.
• Depending on the installation conditions, the outdoor unit may spread its vibration during 

operation, which may cause noise and vibration. Therefore, attach damping materials 
(such as damping pads) to the outdoor unit during installation.

• Install the foundation, making sure that there is enough space for installing the connec-

tion pipes.

• Secure the unit to a solid block using foundation bolts. (Use 4 sets of commercially avail-

able M10 to M12 bolts, nuts, and washers.)

• The bolts should protrude 20 mm. (Refer to the figure.)
• If overturning prevention is required, purchase the necessary commercially available 

items.

Air

688

195

195

80

80

19

20

516

Unit: mm

Bolt

Nut

Base

Model

Product mass

(Kg)

72 model

163

90 model

172

9380545231_IM.indb   4

9380545231_IM.indb   4

7/14/2017   8:53:11 AM

7/14/2017   8:53:11 AM

Summary of Contents for AOYG72LRLA

Page 1: ...amente para personal de servicio autorizado MANUALE D INSTALLAZIONE UNITÀ ESTERNA A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΞΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE EXTERIOR Somente para o pessoal do serviço técnico autorizado РУКОВОДСТВО ПО УСТАНОВКЕ ВНЕШНИЙ МОДУЛЬ Только для авторизованного обслуживающего персонала K...

Page 2: ...used as the packaging material away from young children CAUTION Indicates a potentially hazardous situation that may result in minor or moderate injury or damage to property For the air conditioner to work appropriately install it as written in this manual This product must be installed by qualified personnel with a capacity certification of handling refrigerant fluids Refer to regulation and laws...

Page 3: ... the area If the refrigerant comes in contact with a flame it produces a toxic gas The basic installation work procedures are the same as conventional refrigerant models However pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 models some of the piping and installation and service tools are special See the table ...

Page 4: ...reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping 3 2 Dr...

Page 5: ... using them the cabinet may be damaged or deformed The center of gravity of the outdoor unit is shifted to the right Be careful not to tilt to the heavy side causing it to fall To prevent accidents caused by the unit swinging or falling down do not apply any impact to the unit when it is hanging When hoisting do not hook the rope to the thermistor holder on the back of the outdoor unit Protective ...

Page 6: ...ct the pipe size in accordance with local rules 1 Allowable tensile stress 33 N mm2 2 Allowable tensile stress 61 N mm2 3 Endurance pressure of the pipes 4 2MPa 4 2 Protection of pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit Location Working period Protection metho...

Page 7: ... 4 3 2 Simultaneous operation multi type installation Triple type Capacity Btu h class 72 000 90 000 Main piping mm in Liquid pipes 12 70 1 2 Gas pipes 22 22 7 8 25 40 1 Branch piping mm in Liquid pipes 9 52 3 8 Gas pipes 15 88 5 8 Piping length m m Max piping length L1 L2 L3 L4 1 Pre charge length 100 30 100 30 1 Refer to View in Triple type of 4 3 2 Simultaneous operation multi type installation...

Page 8: ... side and gas side pinch pipe and vent the gas inside the pinch pipe 3 After all the gas is vented melt the brazing filler metal on connecting part using a torch and remove the pinch pipe 3 way valves Pinch pipes End of pinch pipes 5 3 4 Pipe connection CAUTION Seal the pipe route hole with putty locally purchased such that there are no gaps Small insects or animals that are trapped in the outdoor...

Page 9: ... perform a sealing test Make sure that the 3 way valves are closed before performing a sealing test Pressurize nitrogen gas to 4 15 MPa to perform the sealing test Add nitrogen gas to both the liquid pipes and the gas pipes Check all flare connections and welds Then check that the pressure has not decreased Compare the pressures after pressurizing and letting it stand for 24 hours and check that t...

Page 10: ...40 Example 1 L2 10 m L1 30 m L3 7 m Liquid pipe diameter mm Piping length m Coefficient 12 70 30 A 30 9 52 17 B 17 6 35 0 C 0 Additional charging amount Applying the formula 30 x 110 17 x 50 0 x 30 3300 850 The additional charging amount is 850 g Liquid pipe diameter mm Piping length m Coefficient 12 70 10 A 10 9 52 15 B 15 6 35 0 C 0 Additional charging amount Applying to the formula 10 x 110 15 ...

Page 11: ... install the electrical box cover on the unit An improperly installed service panel can cause serious accidents such as electric shock or fire through exposure to dust or water If the supply cable is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard CAUTION The primary power supply capacity is for the air conditioner itself ...

Page 12: ...e blue wire to the N terminal 6 4 2 Connection cable preparation Keep the earth wire longer than the other wires Earth wire 30 mm Power supply cable or Connection cable 35 mm 6 4 3 Wiring procedure 1 Remove the service panel the terminal cover and connect the wires to the terminal in accordance with the terminal nameplate Fig A Fig B 2 Secure the cables using the cable clamps under the terminal bl...

Page 13: ...ric shock CAUTION Once refrigerant charging is completed be sure to open the valve prior to performing the local settings Otherwise the compressor may fail Discharge any static electricity from your body before touching the push buttons Never touch any terminal or pattern of any parts on the control board Remove the front panel of the outdoor unit to access the print circuit board of the display u...

Page 14: ...just LED lamp as shown in below figure PEAK CUT L4 L5 L6 Level 1 Low Blink Level 2 Lower Blink Sign Lights off The noise of Level 2 is lower than the one of Level 1 6 Press ENTER button SW109 and fix it PEAK CUT L4 L5 L6 Level 1 Low Level 2 Lower Sign Lights off Lights on 7 Return to Operating status display Normal operation by pressing EXIT button SW112 In case of missing how many times SELECT an...

Page 15: ...Low noise mode Off Normal operation Input Signal Low noise mode On On Off Off 10 1 3 Peak cut mode CN132 Operation that suppressed the current value can be performed by means of the connected unit The air conditioner is set to the Peak cut mode by applying the contact input of a commercial On Off switch to a connector on the outdoor control PC board Set the Peak cut mode level refer to 9 1 Functio...

Page 16: ... of various pipes flange connection brazing Is the heat insulation done completely Gas pipe liquid pipe drain hose extension on indoor unit side etc Is the water discharging from drain without any problems Are the cables connected correctly Are the cables as per specifications Is the earth wire connected accurately Are there any obstacles blocking the suction gate and outlet of the indoor outdoor ...

Page 17: ... Discharge temp sensor 1 error 2 7 2 Compressor temp sensor error Compressor temp sensor 1 error 2 7 3 Outdoor unit Heat Ex sensor error Heat Ex middle temp sensor error 2 7 3 Outdoor unit Heat Ex liquid temp sensor error 2 7 4 Outdoor temp sensor error Outdoor temp sensor error 2 7 7 Heat sink temp sensor error Heat sink temp sensor error 2 8 4 Current sensor error Current sensor 1 error stoppage...

Page 18: ...ssor is operating the compressor will stop then start again in about 3 minutes 4 LED display will change as shown below about 3 minutes after the compressor starts Fully close the 3 way valve on the liquid pipe side at this stage POWER MODE ERROR PUMP DOWN LOW NOISE PEAK CUT L1 L2 L3 L4 L5 L6 Sign Lights off Lights on If the valve on the liquid pipe side is not closed the pump down cannot be perfo...

Reviews: