background image

En-8

]1

12.4.  

Front panel, control box cover and display case 
removal

(1)  Refer to “FRONT PANEL REMOVAL AND INSTALLATION” to remove the front panel.
(2) Remove the screw then remove the control box cover.
(3) Remove the display case and connector.

control box cover 

screw

display case

connector

12.5. Connecting cable to control board connector

(1) Pass the cable from the hole in the back of indoor unit.
(2) Connect the cable to the control board connector.
(3) Hook the cable to the rib.

connect the wire

Rib

CN6

CN16

CN14

PCB

hole

(4)  Use cable clamper and screw to fasten the cable of wired remote controller.

cable of wired 
remote controller 

cable clamper

screw

(5)  Fix the cable tie holder with the screw and bind the wire of external kit with the cable 

tie.

external connect wire

cable tie holder

screw

cable tie

]1

12.6.  

Front panel, control box cover and display case 
installation

Install front panel, control box cover and display case by the reverse procedures as stated 
in 12.4 Front panel, control box cover and display case removal.

13. FUNCTION SETTING

Perform the “FUNCTION SETTING” according to the installation conditions using the 
remote controller.

  CAUTION

Con

fi

 rm whether the wiring work for Outdoor unit or Branch box has been 

fi

 nished.

Con

fi

 rm that the cover for the electrical enclosure on the outdoor unit is in place.

•  

This procedure changes to the function settings used to control the indoor unit according to 
the installation conditions. Incorrect settings can cause the indoor unit to malfunction.

•  After the power is turned on, perform the “FUNCTION SETTING” according to the 

installation conditions using the remote controller.

•  The settings may be selected between the following two: Function Number or Setting 

Value.

•  Settings will not be changed if invalid numbers or setting values are selected.
•  Refer to the installation manual enclosed with the remote controller when the wired 

remote controller (option) is used.

Entering the Function Setting Mode

While pressing the FAN button and SET TEMP. (

) simultaneously, press the RESET 

button to enter the function setting mode.

STEP 1

Selecting the Remote Controller Signal Code

Use the following steps to select the signal code of the re-
mote controller. (Note that the air conditioner cannot receive 
a signal code if the air conditioner has not been set for the 
signal code.)
The signal codes that are set through this process are ap-
plicable only to the signals in the FUNCTION SETTING. For 
details on how to set the signal codes through the normal 
process, refer to Remote controller signal code.

(1)  Press SET TEMP. (

) (

) button to change the signal 

code  between 

. Match the code on the 

display to the air conditioner signal code. (Initially set 
to  ) (If the signal code does not need to be selected, 
press the MODE button and proceed to STEP 2.)

(2)  Press the TIMER MODE button and check that the indoor 

unit can receive signals at the displayed signal code.

(3)  Press the MODE button to accept the signal code, and 

proceed to STEP 2.

The air conditioner signal code is set to A prior to shipment. Contact your retailer to 
change the signal code.

The remote controller resets to signal code A when the batteries in the remote controller 
are replaced. If you use a signal code other than signal code A, reset the signal code 
after replacing the batteries.
If you do not know the air conditioner signal code setting, try each of the signal codes 
(

) until you 

fi

 nd the code which operates the air conditioner.

STEP 2

Selecting the Function Number and Setting Value

(1)  Press the SET TEMP. (

) (

) buttons to select the function number. (Press the 

MODE button to switch between the left and right digits.)

(2)  Press the FAN button to proceed to setting 

the value. (Press the FAN button again to 
return to the function number selection.)

(3)  Press the SET TEMP. (

) (

) buttons to 

select the setting value. (Press the MODE 
button to switch between the left and right 
digits.)

(4)  Press the TIMER MODE button, and START/

STOP button, in the order listed to con

fi

 rm the 

settings.

(5)  Press the RESET button to cancel the func-

tion setting mode.

(6)  After completing the FUNCTION SETTING, be 

sure to turn off the power and turn it on again.

 CAUTION

After turning off the power, wait 10 seconds or more before turning on it again.

The Function Setting does not become active unless the power is turned off then 
on again.

Option type

Connector 

No.

Wired remote controller 

Simple remote controller

CN6

External input

CN14

External output

CN16

Function number

Setting 
value

9318739084_IM.indb   8

9318739084_IM.indb   8

9/27/2012   1:43:56 PM

9/27/2012   1:43:56 PM

Summary of Contents for AOYG18LFC

Page 1: ...e autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Μόνο για εξουσιοδοτημένο προσωπικό του σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos de assistência autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Только для авторизованного обслуживающего персонала MONTAJ KILAVUZU Sadece yetkili servis personeli içindir INSTALLATION MANUAL AIR CONDITIONER INDOOR UNIT Wall Mounted Type PART NO 9318739084 h c s t u e D s i a ç n a r F...

Page 2: ... port thread diameter to prevent erroneous charging with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread diameter for R410A is 1 2 inch Be more careful that foreign matter oil water etc does not enter the piping than with refrigerant R22 models Also when storing the piping securely seal the opening by pinching taping etc When charging the refrigerant...

Page 3: ...arts Parts name Model No Application Wired Remote Controller UTY RNN M For air conditioner operation Simple Remote Controller UTY RSN M For air conditioner operation External connect kit UTY XWZX For control input output port 3 GENERAL This INSTALLATION MANUAL briefly outlines where and how to install the air conditioning system Please read over the entire set of instructions for the indoor and ou...

Page 4: ...e installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Install the indoor unit on the wall where the height from the floors more than 1800 mm 6 INSTALLATION WORK 1 6 1 Installation dimensions Remote controller Remote controller holder Tapping screw sm...

Page 5: ...r piping and drain hose through the wall hole hang the indoor unit on the hooks at the top and bottom of the wall hook bracket Installing the indoor unit Hang the indoor unit from the hooks at the top of the wall hook bracket Insert the spacer etc between the indoor unit and the wall hook bracket and separate the bottom of the indoor unit from the wall Indoor unit Wall hook bracket Spacer Wall hoo...

Page 6: ...wire must be connected firmly No wire should be allowed to touch refrigerant tubing the compressor or any moving part Loose wiring may cause the terminal to overheat or result in unit malfunction A fire hazard may also exist Therefore be sure all wiring is tightly connected Connect wires to the matching numbers of terminals 7 2 Indoor unit wiring 1 Remove the cable clamp 2 Bend the end of the conn...

Page 7: ...n pipe heat insulation Vinyl tape Indoor unit pipe heat insulation Wrap with cloth tape Pipe Drain hose Cloth tape Left piping Connection cable Pipe Drain hose For connection from the left rear Connection cable Wall pipe Connection pipe Drain hose Check the following GOOD Saddle Drain hose Lifted up Wave End in water PROHIBITED 1 9 FRONT PANEL REMOVAL AND INSTALLATION 9 1 Intake grille removal 1 O...

Page 8: ...rts External input output wire Cable Field supply Insulated connection 10 TEST RUN WARNING Do not turn on the power until all installation work is complete CAUTION When restarting after a long period of disuse in the winter turn the power switch on at least 12 hours before starting the unit Check items 1 Is operation of each button on the remote controller normal 2 Does each lamp light normally 3 ...

Page 9: ...de Use the following steps to select the signal code of the re mote controller Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code The signal codes that are set through this process are ap plicable only to the signals in the FUNCTION SETTING For details on how to set the signal codes through the normal process refer to Remote contr...

Page 10: ...onditioner signal code setting try each of the signal codes until you find the code which operates the air conditioner 14 CUSTOMER GUIDANCE Explain the following to the customer in accordance with the operating manual 1 Starting and stopping method operation switching temperature adjustment timer air flow switching and other remote control unit operations 2 Air filter removal and cleaning and how ...

Page 11: ...door unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve ...