6.5.  Forming the drain hose and pipe

[Rear piping, Right piping, Bottom piping]

•  Install the indoor unit piping in the direction of the wall hole and bind the drain hose and 

pipe together with vinyl tape. 

•  Install the piping so that the drain hose is at the bottom.
•  Wrap the pipes of the indoor unit that are visible from the outside with decorative tape.

[For Left rear piping, Left piping]

Interchange the drain cap and the drain hose.

  CAUTION

Insert drain hose and drain cap securely. Drain should slope down to avoid water 
leakage.

When inserting, be sure not to attach any material besides water. If any other 
material is attached, it will cause deterioration and water leakage.

After removing drain hose, be sure not to forget mounting drain cap.

Be sure to 

fi

 x the drain hose with tape to the bottom of piping.

Prevent drain water freezing under low temperature environment.

When installing indoor unit’s drain hose outdoors, necessary measure for frost protec-
tion should be taken to prevent drain water freezing.
Under low temperature environment (when outdoor temperature under 0 °C), after cool-
ing operation is executed, water in the drain hose could be frozen. Once drain water is 
frozen, the drain hose will be blocked and water leakage may result at the indoor unit.

Right piping

Bind with vinyl tape

Indoor unit drain hose 
(bottom)

Pipe (top)
Rear piping

Bottom piping

Drain cap

Indoor unit 
drain hose

Remove the drain cap by pull-
ing at the projection at the end 
of the cap with pliers, etc.

For left outlet piping, cut 
off the piping outlet cutting 
groove with a hacksaw.

  CAUTION

Insert the drain hose and drain cap into the drain port, making sure that it comes 
in contact with the back of the drain port, and then mount it. If the drain hose is 
not connected properly, leaking will occur.

• Attach the Drain hose insulation to the drain hose.

Drain hose insulation

Drain hose

•  For left piping and left rear piping, align the marks on the wall hook bracket and shape 

the connection pipe.

•  Bend the connection piping at the bend radius of 100 mm or more and install no more 

than 35 mm from the wall.

•  After passing the indoor piping and drain hose through the wall hole, hang the indoor unit 

on the hooks at the top and bottom of the wall hook bracket.

[Installing the indoor unit]

•  Hang the indoor unit from the hooks at the top 

of the wall hook bracket.

•  Insert the spacer, etc. between the indoor unit and 

the wall hook bracket and separate the bottom of 
the indoor unit from the wall.

Indoor unit

Wall hook bracket

(Spacer)

Wall hook 
bracket

Alignment marks

Small piping

Connection 
piping

Large piping

Top hooks

Indoor 
unit

(Fitting)

Bottom hooks

Wall hook 
bracket

After hooking the indoor unit to the top hook, hook the 

fi

 ttings of the indoor unit to the 2 

bottom hooks while lowering the unit and pushing it against the wall.

6.6.  Flare connection (Pipe connection)

  WARNING

 Tighten the 

fl

 are nuts with a torque wrench using the speci

fi

 ed tightening method. 

Otherwise, the 

fl

 are nuts could break after a prolonged period, causing refrigerant to 

leak and generate hazardous gas if the refrigerant comes into contact with a 

fl

 ame.

6.6.1. Flaring

Use special pipe cutter and 

fl

 are tool exclusive for R410A.

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3)  Insert the 

fl

 are nut (always use the 

fl

 are nut attached to the indoor unit(s) and outdoor 

unit or branch box respectively) onto the pipe and perform the 

fl

 are processing with a 

fl

 are tool. Use the special R410A 

fl

 are tool, or the conventional 

fl

 are tool. Leakage of re-

frigerant may result if other 

fl

 are nuts are used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from enter-

ing the pipes.

L

Check if [L] is flared uniformly and 
is not cracked or scratched.

Pipe

Die

Pipe outside diameter 

[mm (in.)]

Dimension A [mm]

Dimension B

-

0
0.4

 

[mm]

Flare tool for R410A, 

clutch type

6.35 (1/4)

0 to 0.5

9.1

9.52 (3/8)

13.2

12.70 (1/2)

16.6

15.88 (5/8)

19.7

19.05 (3/4)

24.0

When using conventional 

fl

 are tools to 

fl

 are R410A pipes, the dimension A should be approxi-

mately 0.5 mm more than indicated in the table (for 

fl

 aring with R410A 

fl

 are tools) to achieve 

the speci

fi

 ed 

fl

 aring. Use a thickness gauge to measure the dimension A.

Width across flats

flats

Pipe outside

diameter [mm (in.)]

Width across flats

of Flare nut [mm]

6.35 (1/4)

17

9.52 (3/8)

22

12.70 (1/2)

26

15.88 (5/8)

29

19.05 (3/4)

36

9318739084_IM.indb   4

9318739084_IM.indb   4

9/27/2012   1:43:53 PM

9/27/2012   1:43:53 PM

Summary of Contents for AOYG18LFC

Page 1: ...e autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Μόνο για εξουσιοδοτημένο προσωπικό του σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos de assistência autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Только для авторизованного обслуживающего персонала MONTAJ KILAVUZU Sadece yetkili servis personeli içindir INSTALLATION MANUAL AIR CONDITIONER INDOOR UNIT Wall Mounted Type PART NO 9318739084 h c s t u e D s i a ç n a r F...

Page 2: ... port thread diameter to prevent erroneous charging with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread diameter for R410A is 1 2 inch Be more careful that foreign matter oil water etc does not enter the piping than with refrigerant R22 models Also when storing the piping securely seal the opening by pinching taping etc When charging the refrigerant...

Page 3: ...arts Parts name Model No Application Wired Remote Controller UTY RNN M For air conditioner operation Simple Remote Controller UTY RSN M For air conditioner operation External connect kit UTY XWZX For control input output port 3 GENERAL This INSTALLATION MANUAL briefly outlines where and how to install the air conditioning system Please read over the entire set of instructions for the indoor and ou...

Page 4: ...e installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Install the indoor unit on the wall where the height from the floors more than 1800 mm 6 INSTALLATION WORK 1 6 1 Installation dimensions Remote controller Remote controller holder Tapping screw sm...

Page 5: ...r piping and drain hose through the wall hole hang the indoor unit on the hooks at the top and bottom of the wall hook bracket Installing the indoor unit Hang the indoor unit from the hooks at the top of the wall hook bracket Insert the spacer etc between the indoor unit and the wall hook bracket and separate the bottom of the indoor unit from the wall Indoor unit Wall hook bracket Spacer Wall hoo...

Page 6: ...wire must be connected firmly No wire should be allowed to touch refrigerant tubing the compressor or any moving part Loose wiring may cause the terminal to overheat or result in unit malfunction A fire hazard may also exist Therefore be sure all wiring is tightly connected Connect wires to the matching numbers of terminals 7 2 Indoor unit wiring 1 Remove the cable clamp 2 Bend the end of the conn...

Page 7: ...n pipe heat insulation Vinyl tape Indoor unit pipe heat insulation Wrap with cloth tape Pipe Drain hose Cloth tape Left piping Connection cable Pipe Drain hose For connection from the left rear Connection cable Wall pipe Connection pipe Drain hose Check the following GOOD Saddle Drain hose Lifted up Wave End in water PROHIBITED 1 9 FRONT PANEL REMOVAL AND INSTALLATION 9 1 Intake grille removal 1 O...

Page 8: ...rts External input output wire Cable Field supply Insulated connection 10 TEST RUN WARNING Do not turn on the power until all installation work is complete CAUTION When restarting after a long period of disuse in the winter turn the power switch on at least 12 hours before starting the unit Check items 1 Is operation of each button on the remote controller normal 2 Does each lamp light normally 3 ...

Page 9: ...de Use the following steps to select the signal code of the re mote controller Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code The signal codes that are set through this process are ap plicable only to the signals in the FUNCTION SETTING For details on how to set the signal codes through the normal process refer to Remote contr...

Page 10: ...onditioner signal code setting try each of the signal codes until you find the code which operates the air conditioner 14 CUSTOMER GUIDANCE Explain the following to the customer in accordance with the operating manual 1 Starting and stopping method operation switching temperature adjustment timer air flow switching and other remote control unit operations 2 Air filter removal and cleaning and how ...

Page 11: ...door unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve ...

Reviews: