1. Specifications
Type
Wall mounted
Inverter heat pump
Model name
ASYG07LMCE
ASYG09LMCE
ASYG12LMCE
ASYG14LMCE
Power supply
230 V ~ 50 Hz
Available voltage range
198—264 V
Capacity
Cooling
Rated
kW
2.00
2.50
3.40
4.00
Btu/h
6,800
8,500
11,600
13,600
Min.—Max.
kW
0.5—3.0
0.5—3.2
0.9—3.9
0.9—4.4
Btu/h
1,700—10,200
1,700—10,900
3,100—13,300
3,100—15,000
Heating
Rated
kW
3.00
3.20
4.00
5.00
Btu/h
10,200
10,900
13,600
17,000
Min.—Max.
kW
0.5—3.4
0.5—4.0
0.9—5.3
0.9—6.0
Btu/h
1,700—11,600
1,700—13,600
3,100—18,000
3,100—20,400
Input power
Cooling
Rated
kW
0.465
0.65
0.97
1.135
Min.—Max.
0.25—1.29
0.25—1.29
0.25—1.40
0.25—1.98
Heating
Rated
0.685
0.730
1.02
1.365
Min.—Max.
0.25—1.63
0.25—1.63
0.25—1.98
0.25—2.32
Fan
HIGH
W
30
32
MED
20
23
LOW
10
12
QUIET
4
6
Current
Cooling
Rated
A
2.5
3.2
4.6
5.3
Heating
3.3
3.5
4.8
6.3
EER
Cooling
kW/kW
4.30
3.85
3.50
3.52
COP
Heating
4.38
4.38
3.92
3.66
Sensible capacity
Cooling
kW
1.2
1.6
2.2
3.2
Power factor
Cooling
%
81
88
91
93
Heating
90
90
92
94
Moisture removal
L/h (pints/h)
1.0 (1.8)
1.3 (2.3)
1.8 (3.2)
2.1 (3.7)
Maximum operating current *1
Cooling
A
6.0
6.0
6.5
9.0
Heating
7.5
7.5
9.0
10.5
Fan
Airflow rate
Cooling
HIGH
m
3
/h
750
770
MED
640
680
LOW
480
530
QUIET
310
360
Heating
HIGH
750
770
MED
640
680
LOW
520
560
QUIET
330
380
Type × Q'ty
Cross flow fan × 1
Motor output
W
30
Sound pressure level *2
Cooling
HIGH
dB (A)
43
44
MED
40
40
LOW
32
33
QUIET
21
25
Heating
HIGH
43
44
MED
38
40
LOW
33
35
QUIET
22
27
Heat exchanger type
Dimensions (H × W × D)
mm
Main: 320 × 630 × 20
Sub: 84 × 630 × 13.3
Fin pitch
Man: 1.1, Sub: 1.4
Rows × Stages
Main: 2 × 20, Sub: 1 × 4
Pipe type
Copper tube
Fin type
Aluminum
Enclosure
Material
Polystyrene
Color
White + Pearl white (painted)
Approximate color of Munsell N 9.25/
Dimensions
(H × W × D)
Net
mm
270 × 870 × 204
Gross
270 × 925 × 336
Weight
Net
kg
8.5
Gross
11
Connection pipe
Size
Liquid
mm (in)
Ø 6.35 (Ø 1/4)
Gas
Ø 9.52 (Ø 3/8)
Ø 12.7 (Ø 1/2)
Method
Flare
Drain hose
Material
PP+LLDPE
Size
mm
Ø 13.8 (I.D.), Ø 15.8 to Ø 16.7 (O.D.)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Remote controller type
Wireless (Wired [option])
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum current is maximum value when operated within the operation range.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
DESIGN & TECHNICAL MANUAL
- 2 -
WALL MOUNTED
ASYG07-14LMCE
Summary of Contents for AOYG07LMCE
Page 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE ...
Page 19: ...6 2 Sound level check point 0 8 m 1 m Microphone Microphone 15 WALL MOUNTED ASYG07 14LMCE ...
Page 35: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE ...
Page 43: ...5 Wiring diagrams 5 1 Models AOYG07LMCE and AOYG09LMCE 39 OUTDOOR UNIT AOYG07 14LMCE ...
Page 44: ...5 2 Model AOYG12LMCE 40 OUTDOOR UNIT AOYG07 14LMCE ...
Page 45: ...5 3 Model AOYG14LMCE 41 OUTDOOR UNIT AOYG07 14LMCE ...