9. External input and output
With using external input and output functions, this product can be operated inter-connectedly
with an external device.
Connector
Input
Output
Remarks
CNA01
Control input
—
See external input/output
settings for details.
CNB01
—
Operation status output
CNB02
—
Error status output
9-1. External input
With using external input function, some functions on this product can be controlled from an exter-
nal device.
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor
unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
¢
Control input (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
Unit operation is started at the following contents by adding the contact input of a commercial
on/off switch to a connector on the external control PCB and turning it on.
Unit operation
Initial setting after power is on
Starting mode other than initial
setting
Operation mode
Auto changeover
Mode at previous operation
Set temperature
24 °C
Temperature at previous operation
Airflow mode
AUTO
Mode at previous operation
Air direction (swing)
Standard air direction (swing OFF)
Air direction at previous operation
Circuit diagram example
Signal
Locally purchased
Indoor unit
control PCB
Communication kit
Optional parts
Connector
1
3
10 m*
Connected unit
Example: Switch
• Contact capacity: DC 24 V or
more, 10 mA or more.
• *: Make the distance from the PCB
to the connected unit within 10 m.
• Use non-polar relays and switches.
When function setting is "Operation/Stop" mode
Operation
Stop
On
Off
Input signal
Indoor unit
- 19 -
WALL MOUNTED
ASYG07-14LMCE
Summary of Contents for AOYG07LMCE
Page 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE ...
Page 19: ...6 2 Sound level check point 0 8 m 1 m Microphone Microphone 15 WALL MOUNTED ASYG07 14LMCE ...
Page 35: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE ...
Page 43: ...5 Wiring diagrams 5 1 Models AOYG07LMCE and AOYG09LMCE 39 OUTDOOR UNIT AOYG07 14LMCE ...
Page 44: ...5 2 Model AOYG12LMCE 40 OUTDOOR UNIT AOYG07 14LMCE ...
Page 45: ...5 3 Model AOYG14LMCE 41 OUTDOOR UNIT AOYG07 14LMCE ...