6. OUTDOOR FAN CONTROL
( Table 8 : Outdoor fan speed )
* The outdoor fan speed mentioned above depends on the compressor frequency, outdoor heat
exchanger and outside temperature.
(When the compressor frequency increases, the outdoor fan speed also changes to the higher
speed. When the compressor frequency decreases, the outdoor fan speed also changes to the
lower speed.)
* After the defrost control is operated on the heating mode, the fan speed keeps at the higher speed
as table9 without relating to the compressor frequency.
01-07
( Table9 : Outdoor fan speed after the defrost )
1. Outdoor Fan Motor
2. Fan Speed
AC Motor
DC Motor
Following table shows the type of the outdoor fan motor. The control method is different
between AC motor and DC motor.
( Table 7 : Type of Motor )
930rpm
1020rpm
AO*G07/ 09KMTA
Refer to Fig.8
Cooling
Heating
09KMTA
07KMTA
14KMTA
12KMTA
Y
Z
Zone
(rpm)
F
G
Y
Z
F
G
Y
Z
F
G
Y
Z
F
G
Dry
950/ 270/ 240/ 210/ 190/ 170
950/ 780/ 680/ 610/ 580
930/ 690/ 550/ 510/ 480
930/ 690/ 550/ 510/ 480
1120/ 870/ 710/ 660/ 500
1020/ 790/ 730/ 630/ 530/ 470
950/ 780/ 540/ 360 /270
950/ 250/ 220/ 190/ 170
950/ 330/ 300/ 270/ 250
950/ 270/ 240/ 210/ 190/ 170
950/ 350/ 320/ 290/ 270/ 250
950/ 780/ 680/ 610/ 580
950/ 900/ 800/ 680/ 580/ 540
990/ 920/ 810/ 670/ 570/ 520
990/ 920/ 630/ 460/ 380
990/ 300/ 270/ 240/ 220/ 200
990/ 280/ 250/ 220/ 200
990/ 280/ 250/ 220/ 200
990/ 300/ 270/ 240/ 220/ 200
990/ 920/ 630/ 460/ 380
990/ 920/ 810/ 670/ 570/ 520
950/ 900/ 560/ 420/ 350
950/ 900/ 560/ 420/ 350
950/ 250/ 220/ 190/ 170
950/ 330/ 300/ 270/ 250
950/ 270/ 240/ 210/ 190/ 170
950/ 350/ 320/ 290/ 270/ 250
950/ 900/ 560/ 420/ 350
950/ 900/ 560/ 420/ 350
950/ 250/ 220/ 190/ 170
950/ 270/ 240/ 210/ 190/ 170
950/ 780/ 680/ 610/ 580
950/ 780/ 680/ 610/ 580
950/ 900/ 800/ 680/ 580/ 540
950/ 780/ 540/ 360 /270
950/ 250/ 220/ 190/ 170
AO*G12KMTA
1120rpm
AO*G14KMTA
( Fig.8 : Outside air temperature zone selection )
21°C
10°C
Outside air
temperature
Outside air
temperature
Z zone
Y zone
F zone
G zone
12°C
2°C
19°C
0°C
Summary of Contents for AOYG07KMTA
Page 35: ...1801G4693 ...
Page 39: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Page 61: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Page 97: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Page 105: ...March 2018 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...