( Fig.1 : Outdoor temperature zone )
1. COOLING OPERATION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
Minimum
frequency
Maximum
frequency
Maximum
frequency
14rps
60rps
64rps
84rps
90rps
14rps
12rps
90rps
89rps
78rps
77rps
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
Indoor fan mode
Me
Lo
Quiet
A zone
84rps
49rps
36rps
24rps
B zone
84rps
49rps
36rps
24rps
C zone
84rps
49rps
36rps
24rps
D zone
60rps
44rps
34rps
22rps
E zone
60rps
44rps
34rps
22rps
F zone
60rps
44rps
34rps
22rps
( Table 1 : Compressor frequency range )
01-01
E zone
F zone
10°C
0°C
12°C
2°C
* When the room temperature is b6°C to -1°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Fig.1 based on the indoor
fan mode and the outdoor temperature.
* If the room temperature is some degrees lower than a set temperature,
the compressor will be stopped.
AO*G09KMTA
AO*G12KMTA
AO*G14KMTA
A zone
90rps
52rps
36rps
24rps
B zone
90rps
52rps
36rps
24rps
C zone
90rps
52rps
36rps
24rps
D zone
64rps
46rps
34rps
22ps
E zone
64rps
46rps
34rps
22rps
F zone
64rps
46rps
34rps
22rps
A zone
89rps
44rps
34rps
22rps
B zone
89rps
44rps
34rps
22rps
C zone
89rps
34rps
22rps
D zone
62rps
40rps
32rps
20rps
E zone
62rps
40rps
32rps
20rps
F zone
62rps
40rps
32rps
20rps
44rps
Outdoor
temperature
Outdoor
temperature
( Table 2 : Limit of maximum speed based on outdoor temperature )
AO*G07KMTA
AO*G09KMTA
AO*G07KMTA
AO*G12KMTA
AO*G14KMTA
Outdoor
temp. zone
Hi
* If the room temperature is 6°C higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
When the compressor operates for 30 minutes continuously at over the maximum frequency ,
the maximum frequency is changed from Maximum Frequency to Maximum Frequency .
Summary of Contents for AOYG07KMTA
Page 35: ...1801G4693 ...
Page 39: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Page 61: ...2 TROUBLE SHOOTING WALL MOUNTED type INVERTER ...
Page 97: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Page 105: ...March 2018 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...