8) Room temperature control for wired remote controller sensor
NOTE:
Before performing this setting, refer to Function 95.
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to "Both" (01).
Ensure that the thermo sensor icon is displayed on the remote controller screen.
Function number
Setting value
Setting description
Factory
setting
92
(For cooling)
93
(For heating)
00
No correction 0.0 °F (0.0 °C)
♦
01
No correction 0.0 °F (0.0 °C)
02
-1 °F (-0.5 °C)
More cooling
Less heating
03
-2 °F (-1.0 °C)
04
-3 °F (-1.5 °C)
05
-4 °F (-2.0 °C)
06
-5 °F (-2.5 °C)
07
-6 °F (-3.0 °C)
08
-7 °F (-3.5 °C)
09
-8 °F (-4.0 °C)
10
+1 °F (+0.5 °C)
Less cooling
More heating
11
+2 °F (+1.0 °C)
12
+3 °F (+1.5 °C)
13
+4 °F (+2.0 °C)
14
+5 °F (+2.5 °C)
15
+6 °F (+3.0 °C)
16
+7 °F (+3.5 °C)
17
+8 °F (+4.0 °C)
9) Fixed operation mode switching
Sets the operation mode to heat pump, heating only, or cooling only.
Function number
Setting value
Setting description
Factory setting
94
00
Heat pump
♦
01
Heating only
02
Cooling only
10) Heat insulation condition (building insulation)
Heat insulation conditions differ according to the installed environment.
"Standard insulation" (00) allows system to rapidly respond to the cooling or heating load
changes.
"High insulation" (01) is when the heat insulation structure of the building is high and does not re-
quire system to rapidly respond to cooling or heating load changes.
When "High insulation" (01) is selected:
• Overheating (overcooling) is prevented at the start-up.
• All room-temperature control settings (Function 30, 31, 92, and 93) will reset to "No correction
0.0 °F (0.0 °C)".
Function number
Setting value
Setting description
Factory setting
95
00
Standard insulation
♦
01
High insulation
NOTE:
When changing Function 95, perform this setting before other room-temperature control
settings (Function 30, 31, 92, and 93). If Function 95 is not set first, room-temperature
control settings (Function 30, 31, 92, and 93) will be reset and you must re-do them
again.
- 27 -
WALL MOUNTED
ASU18, 24RLF
Summary of Contents for AOU18RLXFWH
Page 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASU18RLF ASU24RLF ...
Page 9: ...3 Wiring diagrams 3 1 Models ASU18RLF and ASU24RLF 5 WALL MOUNTED ASU18 24RLF ...
Page 35: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOU18RLXFWH AOU24RLXFWH ...
Page 42: ...5 Wiring diagrams 5 1 Model AOU18RLXFWH 38 OUTDOOR UNIT AOU18 24RLXFWH ...
Page 43: ...5 2 Model AOU24RLXFWH 39 OUTDOOR UNIT AOU18 24RLXFWH ...