- (02 - 01) -
OU
TDOOR
UNIT
AO
T
G
0
9
-1
2
K
M
C
A
OU
TDOOR
UNIT
AO
T
G
0
9
-1
2
K
M
C
A
SPECIFICATIONS
1.
Type
INVERTER HEAT PUMP
Model name
AOTG09KMCA
AOTG12KMCA
Power source
240 V ~ 50 Hz
Available voltage range
198 V - 264 V
Starting current
A
3.3
4.2
Fan
Air
fl
ow
rate
Cooling
I/s
(m
3
/h)
472 (1700)
539 (1940)
Heating
428 (1540)
428 (1540)
Type × Q'ty
Propeller fan × 1
Motor output
W
50
50
Sound pressure level
Cooling
dB (A)
47
49
Heating
47
49
Sound power level
64
67
Heat exchanger type
Dimensions
(H × W × D)
mm
504 × 896 × 36.4
Fin pitch
1.3
Rows × Stages
2 × 24
Pipe type
Copper
Fin
Type (Material)
Corrugate (Aluminum)
Surface treatment
Corrosion resistance (Blue
fi
n)
Compressor
Type × Q'ty
Rotary × 1
Motor output
W
750
Refrigerant
Type
R32
Charge
g
850
Refrigerant oil
Type
POE
Enclosure
Material
Steel
Colour
Beige
Approximate colour of MUNSELL 10YR7.5/1.0
Dimensions
(H × W × D)
Net
mm
540 × 790 × 290
Gross
633 × 945 × 395
Weight
Net
kg
34
Gross
37
Connection pipe
Size
Liquid
mm
Ø 6.35
Gas
Ø 9.52
Method
Flare
Pre-charge length
m
20
Max. length
20
Max. height difference
15
Operation range
Cooling
°C
10 to 46
Heating
-15 to 24
International protection rating
IPX4
NOTES :
Speci
fi
cations are based on the following conditions.
•
Cooling: Indoor temperature of 27 °CDB / 19 °CWB and outdoor temperature of 35 °CDB / 24 °CWB.
Heating: Indoor temperature of 20 °CDB / 15 °CWB and outdoor temperature of 7 °CDB / 6 °CWB.
Pipe length: 7.5 m, Height difference: 0 m. (Outdoor unit - Indoor unit)
The protective function may work when using it in environment out of the temperature range mentioned above.
•