- (02 - 11) -

OU

TDOOR

 UNIT

AO

T

G

0

9

-1

2

K

M

C

A

OU

TDOOR

 UNIT

AO

T

G

0

9

-1

2

K

M

C

A

ELECTRICAL CHARACTERISTICS

9.

Model name

AOTG09KMCA

AOTG12KMCA

Power supply

Voltage

V

240 ~

Frequency

Hz

50

Max. operating current *

1

A

7.5

9.0

Starting current

A

3.3

4.2

Wiring spec. *

2

Main fuse (Circuit 
breaker) current

A

10

16

Power cable

mm

2

1.5

Use conformed cable with Type 60245  IEC 57.

*1: The maximum current is the total current of indoor unit and outdoor unit.

*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.

Summary of Contents for AOTG09KMCA

Page 1: ...AIR CONDITIONER Wall Mounted type DESIGN TECHNICAL MANUAL INDOOR OUTDOOR ASTG09KMCA ASTG12KMCA AOTG09KMCA AOTG12KMCA ...

Page 2: ...1 INDOOR UNIT WALL MOUNTED TYPE ASTG09KMCA ASTG12KMCA DTR_AS081E_01 2013 07 19 ...

Page 3: ...Y 01 09 6 2 HEATING CAPACITY 01 10 7 FAN PERFORMANCE 01 11 7 1 AIR VELOCITY DISTRIBUTION 01 11 7 2 AIRFLOW 01 13 8 OPERATION NOISE SOUND PRESSURE 01 15 8 1 NOISE LEVEL CURVE 01 15 8 2 SOUND LEVEL CHECK POINT 01 16 9 ELECTRICAL CHARACTERISTICS 01 17 10 SAFETY DEVICES 01 18 11 EXTERNAL INPUT OUTPUT 01 19 11 1 EXTERNAL INPUT 01 19 11 2 EXTERNAL OUTPUT 01 20 12 FUNCTION SETTINGS 01 22 13 OPTIONAL PART...

Page 4: ...ed airflow setting is possible 21dB only at cooling operation 22dB at heating operation Fan speed Noise level Quiet 21dB A Outdoor unit low noise When air conditioner operates in large capacity operation noise of outdoor unit will be suppressed In case of room temperature being close to setting temperature operation noise may not decrease Noise level in Max power operating 3dB Down Low noise mode ...

Page 5: ... C when the temperature drops below 10 C Economy operation Example Cooling operation Temp Economy operation Shift setting temp Control maximum current Normal operation Time Set temperature Low outdoor air temperature correspondence Corresponds to cooling operation at 10 C outdoor air temperature Corresponds to heating operation at 15 C outdoor air temperature Cooling Heating 10 to 46 C 15 to 24 C ...

Page 6: ...ature thermostat setting according to the timer setting to prevent excessive cooling and heating while sleeping 60min 1 C 2 C Timer setting 1 C 30min 60min 90min 2 C 3 C 4 C Timer setting Cooling operation dry operation When the sleep timer is set the set temperature automatically rises 1 C every hour The set temperature can rise up to a maximum of 2 C Heating operation When the sleep timer is set...

Page 7: ...anel To facilitate explanation the accompanying illustration has been drawn to show all possible indicators in actual operation however the display will only show those indicators appropriate to the current operation Mode indicator Energy Saving Mode indicator Low Noise Mode indicator Turns on when the SENSOR button is operated Clock Timer indicator Send indicator Temperature indicator Transmit in...

Page 8: ...4 520 Quiet 92 330 92 330 Type Q ty Crossflow fan 1 Motor output W 44 Sound pressure level Cooling High dB A 40 42 Med 36 37 Low 31 32 Quiet 21 21 Heating High 40 42 Med 34 37 Low 31 33 Quiet 22 22 Heat exchanger type Dimensions H W D mm Main 320 630 20 Sub 84 630 13 3 Fin pitch Main 1 1 Sub 1 4 Rows Stages Main 2 20 Sub 1 4 Pipe type Copper Fin type Aluminium Enclosure Material Polystyrene Colour...

Page 9: ... 01 06 WALL MOUNTED TYPE ASTG09 12KMCA WALL MOUNTED TYPE ASTG09 12KMCA DIMENSIONS 4 MODELS ASTG09KMCA ASTG12KMCA Unit mm ...

Page 10: ... 01 07 WALL MOUNTED TYPE ASTG09 12KMCA WALL MOUNTED TYPE ASTG09 12KMCA INSTALLATION PLACE Unit mm ...

Page 11: ... 01 08 WALL MOUNTED TYPE ASTG09 12KMCA WALL MOUNTED TYPE ASTG09 12KMCA WIRING DIAGRAMS 5 MODELS ASTG09KMCA ASTG12KMCA ...

Page 12: ...52 40 1 83 1 32 0 54 2 03 1 33 0 55 2 10 1 45 0 56 2 24 1 45 0 56 2 31 1 57 0 56 2 45 1 56 0 57 2 59 1 66 0 57 46 1 68 1 30 0 62 1 87 1 31 0 63 1 93 1 42 0 64 2 06 1 43 0 64 2 13 1 54 0 65 2 25 1 54 0 65 2 38 1 64 0 66 AFR 12 0 Indoor temperature CDB 18 21 23 25 27 29 32 CWB 12 15 16 18 19 21 23 Outdoor temperature CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP 20 3 28 2...

Page 13: ... 4 67 1 50 4 55 1 53 4 44 1 56 7 6 5 57 1 54 5 43 1 57 5 30 1 60 5 17 1 63 5 04 1 66 10 8 5 80 1 46 5 66 1 49 5 52 1 52 5 38 1 55 5 24 1 58 15 10 5 87 1 31 5 73 1 34 5 59 1 36 5 45 1 39 5 31 1 42 AFR 12 0 Indoor temperature CDB 16 18 20 22 24 Outdoor temperature CDB CWB TC IP TC IP TC IP TC IP TC IP 15 16 3 03 1 14 2 96 1 17 2 89 1 19 2 82 1 21 2 74 1 24 10 11 3 50 1 24 3 42 1 27 3 33 1 29 3 25 1 ...

Page 14: ...m s m m TOP VIEW Vertical flap Up Horizontal flap Center 0 1 2 3 4 5 6 7 8 9 2 0 1 0 1 0 0 5 0 5 3 2 1 0 1 2 3 Unit m s m TOP VIEW Vertical flap Up Horizontal flap Right Left m 0 1 2 3 4 5 6 7 8 9 2 0 1 0 0 5 3 2 1 0 Unit m s m SIDE VIEW Vertical flap Up Horizontal flap Center m 0 1 2 3 4 5 6 7 8 9 2 0 1 0 0 5 3 2 1 0 Unit m s m SIDE VIEW Vertical flap Down Horizontal flap Center m 0 1 2 3 4 5 6 7...

Page 15: ...l flap Up Horizontal flap Center 0 1 2 3 4 5 6 7 8 9 2 0 1 0 1 0 0 5 0 5 3 2 1 0 1 2 3 Unit m s m TOP VIEW Vertical flap Up Horizontal flap Right Left m 0 1 2 3 4 5 6 7 8 9 2 0 1 0 0 5 3 2 1 0 Unit m s m SIDE VIEW Vertical flap Up Horizontal flap Center m 0 1 2 3 4 5 6 7 8 9 2 0 1 0 0 5 3 2 1 0 Unit m s m SIDE VIEW Vertical flap Down Horizontal flap Center m 0 1 2 3 4 5 6 7 8 9 ...

Page 16: ...otations r p m Airflow HIGH 1240 m3 h 700 l s 194 CFM 412 MED 1050 m3 h 560 l s 156 CFM 330 LOW 880 m3 h 450 l s 125 CFM 265 QUIET 680 m3 h 310 l s 86 CFM 182 Fan speed Number of rotations r p m Airflow HIGH 1240 m3 h 700 l s 194 CFM 412 MED 1050 m3 h 560 l s 156 CFM 330 LOW 910 m3 h 470 l s 131 CFM 277 QUIET 710 m3 h 330 l s 92 CFM 194 ...

Page 17: ...ns r p m Airflow HIGH 1280 m3 h 720 l s 200 CFM 424 MED 1120 m3 h 610 l s 169 CFM 359 LOW 930 m3 h 480 l s 133 CFM 283 QUIET 680 m3 h 310 l s 86 CFM 182 Fan speed Number of rotations r p m Airflow HIGH 1280 m3 h 720 l s 200 CFM 424 MED 1120 m3 h 610 l s 169 CFM 359 LOW 980 m3 h 520 l s 144 CFM 306 QUIET 710 m3 h 330 l s 92 CFM 194 ...

Page 18: ... center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 μbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0 dB 0 0002 μbar Octave band center frequency Hz 80 70 60 50 4...

Page 19: ... 01 16 WALL MOUNTED TYPE ASTG09 12KMCA WALL MOUNTED TYPE ASTG09 12KMCA SOUND LEVEL CHECK POINT 8 2 ...

Page 20: ...equency Hz 50 Max operating current A 7 5 9 0 Wiring spec Connection cable mm2 1 5 Limited wiring length m 21 NOTES on Wiring spec Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005 Limited wiring length Limit voltage drop to less than 2 Increase cable gauge if voltage drop is 2 or more Use conformed cable with Type 60245 IEC 57 ...

Page 21: ...G09 12KMCA WALL MOUNTED TYPE ASTG09 12KMCA SAFETY DEVICES 10 Protection form Model ASTG09KMCA ASTG12KMCA Circuit protection Current fuse PC board 250 V 3 15 A Fan motor protection Thermal protector program OFF 160 25 C ON 110 25 C ...

Page 22: ...Airflow mode AUTO Mode at previous operation Up down air direction swing Standard air direction swing OFF Air direction at previous operation Left right air direction swing Standard air direction swing OFF Air direction at previous operation Circuit diagram example Signal Field supply Indoor unit control PC board Communication kit Optional parts Connector 1 3 10 m Connected unit Ex Switch When fun...

Page 23: ...mA to less than 500 mA Field supply Optional parts Ex Display Indoor unit control PC board Communication kit Connected unit Ex Relay unit 1 2 Signal Relay power supply V Connector 10 m DC 24 V ON OFF Operation Stop Indoor unit Output signal Parts Optional Parts name Model name External connect kit UTY XWZXZ5 Communication kit UTY XCBXZ2 For operating the EXTERNAL function the wall mounted type req...

Page 24: ...n 500 mA Field supply Optional parts Ex Display Indoor unit control PC board Communication kit Connected unit Ex Relay unit 1 2 Signal Relay power supply V Connector 10 m DC 24 V ON OFF Error Normal Error status Output signal Parts Optional Parts name Model name External connect kit UTY XWZXZ5 Communication kit UTY XCBXZ2 For operating the EXTERNAL function the wall mounted type requires the commu...

Page 25: ...he outdoor unit is in place When using optional wired remote controller refer to the installation manual shipped with the remote controller Adjust the signal code of the indoor unit and the signal code of the remote controller Entering the Function Setting Mode While pressing the POWERFUL button and SET TEMP simultaneously press the RESET button to enter the function setting mode Selecting the Fun...

Page 26: ...Setting value Standard 400 hours 11 00 Long interval 1000 hours 01 Short interval 200 hours 02 No indication 03 2 Room temperature control for cooling Depending on the installed environment correction of the room temperature sensor may be required Select the appropriate control setting according to the installed environment Factory setting Setting description Function number Setting value Standard...

Page 27: ... active 6 Remote controller signal code Only for wireless remote controller The indoor unit signal code can be changed Select the appropriate signal code Factory setting Setting description Function number Setting value A 44 00 B 01 C 02 D 03 7 External input control Operation Stop mode or Forced stop mode can be selected Factory setting Setting description Function number Setting value Operation ...

Page 28: ...ntroller display 2 Press the MODE button for at least 5 seconds to display the current signal code initially set to 3 Press the SET TEMP buttons to change the signal code between Match the code on the display to the air conditioner signal code 4 Press the MODE button again to return to the clock display The signal code will be changed If no button is pressed within 30 seconds after the signal code...

Page 29: ... by detecting the temperature accurately with built in thermo sensor Optional communication kit is necessary for installation Simple remote controller UTY RSNYN Compact remote controller concentrates on the basic functions such as Start Stop Fan Control Temperature Setting and Operation mode Optional communication kit is necessary for installation Exterior Parts name Model No Summary Communication...

Page 30: ...2 OUTDOOR UNIT SINGLE TYPE AOTG09KMCA AOTG12KMCA DTR_AO143E_01 2013 07 19 ...

Page 31: ...ERANT CIRCUIT 02 03 4 WIRING DIAGRAMS 02 04 5 CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE 02 05 6 ADDITIONAL CHARGE CALCULATION 02 07 7 AIRFLOW 02 08 8 OPERATION NOISE SOUND PRESSURE 02 09 8 1 NOISE LEVEL CURVE 02 09 8 2 SOUND LEVEL CHECK POINT 02 10 9 ELECTRICAL CHARACTERISTICS 02 11 10 SAFETY DEVICES 02 12 ...

Page 32: ...or output W 750 Refrigerant Type R32 Charge g 850 Refrigerant oil Type POE Enclosure Material Steel Colour Beige Approximate colour of MUNSELL 10YR7 5 1 0 Dimensions H W D Net mm 540 790 290 Gross 633 945 395 Weight Net kg 34 Gross 37 Connection pipe Size Liquid mm Ø 6 35 Gas Ø 9 52 Method Flare Pre charge length m 20 Max length 20 Max height difference 15 Operation range Cooling C 10 to 46 Heatin...

Page 33: ...rger than stated the condition will be the same as those without any obstacles Height above the floor level should be 50 mm or more 600 or more 100 or more 200 or more 100 or more 250 or more Service space 790 290 352 72 20 10 18 Top view 540 320 209 Side view Side view Front view Airflow 175 110 9 20 540 4 ø11 3 mm hole Bottom view 45 4 Drain port Ø20 395 ...

Page 34: ... 02 03 OUTDOOR UNIT AOTG09 12KMCA OUTDOOR UNIT AOTG09 12KMCA REFRIGERANT CIRCUIT 3 MODELS AOTG09KMCA AOTG12KMCA Refrigerant pipe diameter Liquid 1 4 6 35 mm Gas 3 8 9 52 mm ...

Page 35: ... 02 04 OUTDOOR UNIT AOTG09 12KMCA OUTDOOR UNIT AOTG09 12KMCA WIRING DIAGRAMS 4 MODELS AOTG09KMCA AOTG12KMCA ...

Page 36: ...70 0 919 0 869 7 5 0 993 0 968 0 917 0 866 10 0 966 0 915 0 864 15 0 906 0 856 COOLING Pipe length m 5 7 5 10 15 20 Height difference H m 1 Indoor unit is higher than outdoor unit 15 0 931 0 907 10 0 971 0 947 0 922 7 5 0 988 0 975 0 950 0 926 5 1 005 0 992 0 979 0 953 0 930 0 1 013 1 000 0 987 0 962 0 937 2 Indoor unit is lower than outdoor unit 5 1 013 1 000 0 987 0 962 0 937 7 5 1 000 0 987 0 9...

Page 37: ...0 7 5 1 000 0 974 0 922 0 870 5 1 006 1 000 0 974 0 922 0 870 0 1 006 1 000 0 974 0 922 0 870 2 Indoor unit is lower than outdoor unit 5 1 001 0 995 0 969 0 917 0 866 7 5 0 993 0 967 0 915 0 863 10 0 965 0 913 0 861 15 0 904 0 853 COOLING Pipe length m 5 7 5 10 15 20 Height difference H m 1 Indoor unit is higher than outdoor unit 15 0 917 0 883 10 0 966 0 932 0 897 7 5 0 988 0 970 0 936 0 901 5 1 ...

Page 38: ... AOTG09 12KMCA OUTDOOR UNIT AOTG09 12KMCA ADDITIONAL CHARGE CALCULATION 6 MODELS AOTG09KMCA AOTG12KMCA Refrigerant charge Refrigerant type R32 Refrigerant amount g 850 Total pipe length m 20 or less Additional charge g 0 ...

Page 39: ...Heating MODEL AOTG12KMCA Cooling Heating Number of rotations r p m Airflow 750 m3 h 1700 l s 472 CFM 1001 Number of rotations r p m Airflow 680 m3 h 1540 l s 428 CFM 906 Number of rotations r p m Airflow 850 m3 h 1940 l s 539 CFM 1142 Number of rotations r p m Airflow 680 m3 h 1540 l s 428 CFM 906 ...

Page 40: ...ve band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Heating Octave band sound pressure level dB 0 dB 0 0002 μbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound...

Page 41: ... 02 10 OUTDOOR UNIT AOTG09 12KMCA OUTDOOR UNIT AOTG09 12KMCA SOUND LEVEL CHECK POINT 8 2 ...

Page 42: ...equency Hz 50 Max operating current 1 A 7 5 9 0 Starting current A 3 3 4 2 Wiring spec 2 Main fuse Circuit breaker current A 10 16 Power cable mm2 1 5 Use conformed cable with Type 60245 IEC 57 1 The maximum current is the total current of indoor unit and outdoor unit 2 Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005 ...

Page 43: ...Circuit protection Current fuse Near the terminal Current fuse Main PC board 250 V 20 A 250 V 5 A Fan motor protection Thermal protection program OFF 150 15 C ON 120 15 C Compressor protection Thermal protection program Discharge temp OFF 110 C ON After 2min 20sec Thermal protection Thermal protection fuse Terminal 1 A 70 C ...