6.  ELECTRICAL WIRING

Cable

Cable size (mm

2

)

Type

Remarks

Connection cable

1.5

Type 60245 IEC57 Ground, 1φ230V

Max. Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage drop is 

2% or more.

 

WARNING

•  Electrical  work  must  be  performed  in  accordance  with  this  Manual  by  a  person 

certified under the national or regional regulations. Be sure to use a dedicated circuit 

for the unit. 

  An insufficient power supply circuit or improperly performed electrical work can cause 

serious accidents such as electric shock or fire.

•  Before starting work, check that power is not being supplied to the indoor unit and 

outdoor unit.

•  For wiring, use the prescribed type of cables, connect them securely, making sure 

that there are no external forces of the cables applied to the terminal connections.

  Improperly  connected  or  secured  cables  can  cause  serious  accidents  such  as 

overheating the terminals, electric shock, or fire.

•  Securely install the electrical box cover on the unit. 

  An  improperly  installed  electrical  box  cover  can  cause  serious  accidents  such  as 

electric shock or fire through exposure to dust or water.

•  Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit 

could result.

•  Use  the  included  connection  cables  and  power  cables  or  ones  specified  by  the 

manufacturer.  Improper  connections,  insufficient  insulation,  or  exceeding  the 

allowable current can cause electric shock or fire.

•  Do not modify the power cables, use extension cables, or use any branches in the 

wiring.  Improper  connections,  insufficient  insulation,  or  exceeding  the  allowable 

current can cause electric shock or fire.

 

Match  the  terminal  block  numbers  and  connection  cable  colors  with  those  of  the 

outdoor unit or branch box. Erroneous wiring may cause burning of the electric parts.

•  Securely connect the connection cables to the terminal board. In addition, secure the 

cables with wiring holders. Improper connections, either in the wiring or at the ends 

of the wiring, can cause a malfunction, electric shock, or fire.

 

Always fasten the outside covering of the connection cable with the cable clamp. (If 

the insulator is chafed, electric leakage may occur.)

•  Install a earth leakage breaker. In addition, install the earth leakage breaker so that 

the entire AC main power supply is cut off at the same time. Otherwise, electric shock 

or fire could result.

  Always connect the earth cable.

  Improper grounding work can cause electric shocks.

  Install the remote controller cables so as not to be direct touched with your hand.

•  Perform wiring work in accordance with standards so that the air conditioner can be 

operated safely and positively.

•  Connect the connection cable firmly to the terminal board. Imperfect installation may 

cause a fire.

 

CAUTION

•  Ground the unit. 

  Do not connect the earth cable to a gas pipe, water pipe, lightning rod, or a telephone 

earth cable. 

  Improper grounding may cause electric shock.

•  Do  not  connect  power  supply  cables  to  the  transmission  or  remote  controller 

terminals, as this will damage the product.

•  Never bundle the power supply cable and transmission cable, remote controller cable 

together.

  Separate these cable by 50 mm or more.

  Bundling these cables together will cause miss operation or breakdown.

•  When handling PCB, static electricity charged in the body may cause malfunction of 

the PCB. Follow the cautions below:

•  Establish a ground for the indoor and outdoor units and peripheral devices.

•  Cut power (breaker) off.

•  Touch  metal  part  of  the  indoor  and  outdoor  units  for  more  than  10  seconds  to 

discharge static electricity charged in the body.

•  Do not touch terminals of parts and patterns implemented on PCB.

(1)  Use ring terminals with insulating sleeves as shown in the figure below to connect to 

the terminal block.

(2)  Securely clamp the ring terminals to the cables using an appropriate tool so that the 

cables do not come loose.

(3)  Use the specified cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws.

 

Do not use a screwdriver that is too small, otherwise, the screw heads may be 

damaged and prevent the screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(6)  See the table for the terminal screw tightening torques.
(7)  Please do not fix 2 power supply cables with 1 screw.

Strip

 10

 mm

 Sleeve

Screw with spe

-

cial washer

Screw with 

special washer

Ring terminal

Cable

Cable

Terminal block

Ring terminal

Ring  

terminal

 

WARNING

•  Use ring terminals and tighten the terminal screws to the specified torques, otherwise, 

abnormal  overheating  may  be  produced  and  possibly  cause  heavy  damage  inside 

the unit.

Tightening torque

M4 screw

1.2 to 1.8 N·m

(12 to 18 kgf·cm)

9374815173-04_IM.indb   10

9/21/2011   1:45:23 PM

Summary of Contents for AOHG12LALL

Page 1: ...zzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION MANUAL AIR CONDITIONER INDOOR UNIT Duct Type h c s t u e D s i a ç n a r F l o ñ a p s E o n a i l a t I ά k I v η λ λ E s ê u g u t r o P h s i l g n E e ç k r ...

Page 2: ...l and base size were changed Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Gas leakage detector Special gas leakage detector for HFC refrigerant R410A 1 SAFETY PRECAUTIONS Be sure to read this Manual thoroughly before installation The warnings and precautions indicated in this Manual contain important information pertaining to your safety Be sure to observe...

Page 3: ...ALLATION WORK 3 1 Selecting an installation location Especially the installation place is very important for the split type air conditioner because it is very difficult to move from place to place after the first installation WARNING Select installation locations that can properly support the weight of the indoor Install the units securely so that they do not topple or fall CAUTION Do not install ...

Page 4: ... mm or more Inlet air Inlet air Strong and durable floor Strong and durable floor 10 mm or less Right side PIPE side Right side PIPE side Grille Duct Grille Strong and durable floor 3 3A Installation the unit Ceiling concealed type WARNING Install the air conditioner in a location which can withstand a load do at least 5 times the weight of the main unit and which will not amplify sound or vibration ...

Page 5: ...utlet side Inlet side 7000 9000 12000 14000 BTU h 18000 BTU h A 650 mm 850 mm B P200 2 400 mm P200 3 600 mm CAUTION Be sure to install the air inlet grille and the air outlet grille for air circulation The correct temperature cannot be detected Grills must be fixed so that man cannot touch indoor unit fan and exchanger and cannot be removed by only hand operation without tool Be sure to install th...

Page 6: ...d the dew condensation Make sure to insulate between ducts and walls if metal ducts are used Please explain handling and washing methods of locally purchased materials to the customer To prevent people from touching the parts inside the unit be sure to install grilles on the inlet and outlet ports The grilles must be designed in such a way that cannot be removed without tools When connecting the d...

Page 7: ...electing the pipe material CAUTION Do not use existing pipes Use pipes that have clean external and internal sides without any contamination which may cause trouble during use such as sulfur oxide dust cutting waste oil or water It is necessary to use seamless copper pipes Material Phosphor deoxidized seamless copper pipes It is desirable that the amount of residual oil is less than 40 mg 10 m Do ...

Page 8: ...e careful not to collapse them Do not bend the pipes in an angle more than 90 When pipes are repeatedly bend or stretched the material will harden making it difficult to bend or stretch them any more Do not bend or stretch the pipes more than 3 times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break 4 3 3 Pipe connection CAUTIO...

Page 9: ... BAD Trap Observe the following procedures to construct centralized drain pipe fittings VP30 or more O D 38 mm or more Downward gradient 1 100 or more 700 mm or less WARNING Do not insert the drain piping into the sewer where sulfurous gas occurs Heat exchange erosion may occur Insulate the parts properly so that water will not drip from the connection parts Check for proper drainage after the con...

Page 10: ...o avoid space with Drain hose 1 and Hose band 2 press firmly the Drain hose insulation B 3 When drain pump is used Ceiling concealed type only 3 Drain hose insulation B Ensure there is no space When drain pump is not used Natural drainage 3 Drain hose insulation B Ensure there is no space STEP1 STEP3 Butt the insulation against the unit STEP 1 Unit Slit Press firmly Press firmly STEP 2 Slit Press fi...

Page 11: ...t the same time Otherwise electric shock or fire could result Always connect the earth cable Improper grounding work can cause electric shocks Install the remote controller cables so as not to be direct touched with your hand Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively Connect the connection cable firmly to the terminal board I...

Page 12: ...r branch box units by attaching a earth cable Unit shall be grounded in compliance with the applicable local and national cables CAUTION Be sure to refer to the above diagram for do correct field wiring Wrong wiring causes malfunction of the unit Check local electrical rules and also any specific wiring instructions or limitation 6 2 Connection cable preparation Keep the earth wire longer than the...

Page 13: ...ct the connector to the front case Screws SET BACK Front case back side Rear case Connector When remote controller cable is concealed 1 Conceal the remote controller cable 2 Pass the remote controller cable through the hole in the rear case and connect the remote controller cable to the remote controller terminal board specified in figure 3 Clamp the remote controller cable sheath with the binder ...

Page 14: ...er and turn it on again Function Details 1 Filter Sign The indoor unit has a sign to inform the user that it is time to clean the filter Select the time setting for the filter sign display interval in the table below according to the amount of dust or debris in the room If you do not wish the filter sign to be displayed select the setting value for No indication Factory setting Setting description...

Page 15: ...oom temperature can be selected from the following 2 examples Choose the detection location that is best for the installation location A Indoor unit setting factory setting The room temperature is detected by the indoor unit temperature sensor 1 When the THERMO SENSOR button is pressed the lock display flashes because the function is locked at the factory A Indoor unit B Indoor unit remote control...

Page 16: ...DIP SW 1 No 2 DIP SW 1 No 2 1 Normal OFF 2 Dual OFF ON 8 TEST RUN CAUTION Always turn on the power 12 hours prior to the start of the operation in order to ensure compressor protection CHECK ITEMS 1 Is operation of each button on the remote controller normal 2 Does each lamp light normally 3 Do not air flow direction louvers operate normally 4 Is the drain normal 5 Is there any abnormal noise and ...

Page 17: ...erminals Output terminal CN103 Input No Voltage terminal CN102 Wiring arrangement Binder Medium Accessories Bind with this cable 1 9 3 Remote sensor Optional parts Connection method Connection terminals Remote sensor terminal CN8 Wiring arrangement Binder Medium Accessories Bind with this cable Remove the existing connector and replace it with the remote sensor connector ensure that the correct co...

Page 18: ...t or optional parts for binder Use an accessory of optional parts for bushing Ceiling Avoid covering the air inlet with the wirings Binders Air inlet Binder Knockout hole Bushing Do not bind the power supply cable and other cables together CAUTION To protect the cable insulation after opening a knockout hole remove any burrs from the edge of the hole 10 CUSTOMER GUIDANCE Explain the following to t...

Page 19: ... Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way va...

Reviews: