background image

En-7

4.2. Pipe requirement

 

CAUTION

•  Refer to the Installation Manual of the outdoor unit for description of the length of 

connecting pipe or for difference of its elevation.

•  Use pipe with water-resistant heat insulation.

 

CAUTION

• 

Install  heat  insulation  around  both  the  gas  and  liquid  pipes.  Failure  to  do  so  may 

cause water leaks.

 

Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)

  In addition, if the humidity level at the installation location of the refrigerant piping is 

expected to exceed 70 %, install heat insulation around the refrigerant piping. If the 

expected humidity level is 70-80 %, use heat insulation that is 15 mm or thicker and 

if the expected humidity exceeds 80 %, use heat insulation that is 20 mm or thicker. 

If heat insulation is used that is not as thick as specified, condensation may form on 

the surface of the insulation. In addition, use heat insulation with heat conductivity of 

0.045 W/(m·K) or less (at 20 °C).

4.3. Flare connection (Pipe connection)

 

WARNING

•  Tighten  the  flare  nuts  with  a  torque  wrench  using  the  specified  tightening  method. 

Otherwise, the flare nuts could break after a prolonged period, causing refrigerant to 

leak and generate a hazardous gas if the refrigerant comes into contact with a flame.

4.3.1. Flaring

•  Use special pipe cutter and flare tool exclusive for R410A.

(1) 

Cut the connection pipe to the necessary length with a pipe cutter.

(2) 

Hold  the  pipe  downward  so  that  cuttings  will  not  enter  the  pipe  and  remove  any 

burrs.

(3) 

Insert the flare nut (always use the flare nut attached to the indoor and outdoor units 

respectively) onto the pipe and perform the flare processing with a flare tool. Use 

the special R410A flare tool, or the conventional flare tool. Leakage of refrigerant 

may result if other flare nuts are used.

(4) 

Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

/

Die

Pipe

A

B

Check if [L] is flared uniformly 

and is not cracked or scratched.

Pipe outside diameter 

[mm (in.)]

Dimension A [mm]

Dimension B

-

0

0.4 

[mm]

Flare tool for R410A,  

clutch type

6.35 (1/4)

0 to 0.5

9.1

9.52 (3/8)

13.2

12.70 (1/2)

16.6

15.88 (5/8)

19.7

19.05 (3/4)

24.0

When using conventional  flare tools to flare R410A pipes, the dimension A should  be 

approximately 0.5 mm more than indicated in the table (for flaring with R410A flare tools) 

to achieve the specified flaring. Use a thickness gauge to measure the dimension A.

Width across 

flats

Pipe outside 

diameter [mm (in.)]

Width across flats 

of Flare nut [mm]

6.35 (1/4)

17

9.52 (3/8)

22

12.70 (1/2)

26

15.88 (5/8)

29

19.05 (3/4)

36

4.3.2. Bending pipes

• 

If pipes are shaped by hand, be careful not to collapse them.

• 

Do not bend the pipes in an angle more than 90°.

• 

When pipes are repeatedly bend or stretched, the material will harden, making it 

difficult to bend or stretch them any more. 

• 

Do not bend or stretch the pipes more than 3 times.

 

CAUTION

• 

To prevent breaking of the pipe, avoid sharp bends. 

• 

If the pipe is bent repeatedly at the same place, it will break.

4.3.3. Pipe connection

 

CAUTION

• 

Be sure to install the pipe against the port on the indoor unit correctly. If the centering 

is improper, the flare nut cannot tighten smoothly. If the flare nut is forced to turn, the 

threads will be damaged.

•  Do  not  remove  the  flare  nut  from  the  indoor  unit  pipe  until  immediately  before 

connecting the connection pipe.

•  Hold the torque wrench at its grip, keeping it at a right angle with the pipe, in order to 

tighten the flare nut correctly.

•  Tighten the flare nuts with a torque wrench using the specified tightening method. 

Otherwise, the flare nuts could break after a prolonged period, causing refrigerant to 

leak and generate a hazardous gas if the refrigerant comes into contact with a flame.

•  Connect the piping so that the control box cover can easily be removed for servicing 

when necessary.

•  In order to prevent water from leaking into the control box, make sure that the piping 

is well insulated.

When the flare nut is tightened properly by your hand, hold the body side coupling with 

a separate spanner, then tighten with a torque wrench. (See the table below for the flare 

nut tightening torques.)

Tighten with 2 wrenches.

Holding wrench

Flare nut 

Connection pipe

Torque wrench

Indoor unit pipe  

(Body side)

Flare nut [mm (in.)]

Tightening torque [N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1,100)

4.4. Installing heat insulation

Install  the  heat  insulation  material  after  performing  a  refrigerant  leak  check  (see  the 

Installation Manual for the outdoor unit for details).

4.4.1. COUPLER HEAT INSULATION

•  Insulate with the coupler heat insulation (Accessories) around the gas pipe and liquid 

pipe at indoor unit.

•  After installing the coupler heat insulation, wrap both ends with vinyl tape so that 

there is no gap.

•  After affixing the coupler heat insulation, secure it with 2 binders (large), one on each 

end of the insulation.

•  Make sure that the binders overlap the heat insulation pipe.

Coupler heat

insulation 

(Accessories)

Cover this portion with 

heat insulation.

Binder (Large)

(Accessories)

Heat insulation

 

CAUTION

•  After  checking  for  gas  leaks  (refer  to  the  Installation  Manual  of  the  outdoor  unit), 

perform this section.

•  Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to 

do so may cause water leaks.

9374815173-04_IM.indb   7

9/21/2011   1:45:21 PM

Summary of Contents for AOHG12LALL

Page 1: ...zzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION MANUAL AIR CONDITIONER INDOOR UNIT Duct Type h c s t u e D s i a ç n a r F l o ñ a p s E o n a i l a t I ά k I v η λ λ E s ê u g u t r o P h s i l g n E e ç k r ...

Page 2: ...l and base size were changed Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Gas leakage detector Special gas leakage detector for HFC refrigerant R410A 1 SAFETY PRECAUTIONS Be sure to read this Manual thoroughly before installation The warnings and precautions indicated in this Manual contain important information pertaining to your safety Be sure to observe...

Page 3: ...ALLATION WORK 3 1 Selecting an installation location Especially the installation place is very important for the split type air conditioner because it is very difficult to move from place to place after the first installation WARNING Select installation locations that can properly support the weight of the indoor Install the units securely so that they do not topple or fall CAUTION Do not install ...

Page 4: ... mm or more Inlet air Inlet air Strong and durable floor Strong and durable floor 10 mm or less Right side PIPE side Right side PIPE side Grille Duct Grille Strong and durable floor 3 3A Installation the unit Ceiling concealed type WARNING Install the air conditioner in a location which can withstand a load do at least 5 times the weight of the main unit and which will not amplify sound or vibration ...

Page 5: ...utlet side Inlet side 7000 9000 12000 14000 BTU h 18000 BTU h A 650 mm 850 mm B P200 2 400 mm P200 3 600 mm CAUTION Be sure to install the air inlet grille and the air outlet grille for air circulation The correct temperature cannot be detected Grills must be fixed so that man cannot touch indoor unit fan and exchanger and cannot be removed by only hand operation without tool Be sure to install th...

Page 6: ...d the dew condensation Make sure to insulate between ducts and walls if metal ducts are used Please explain handling and washing methods of locally purchased materials to the customer To prevent people from touching the parts inside the unit be sure to install grilles on the inlet and outlet ports The grilles must be designed in such a way that cannot be removed without tools When connecting the d...

Page 7: ...electing the pipe material CAUTION Do not use existing pipes Use pipes that have clean external and internal sides without any contamination which may cause trouble during use such as sulfur oxide dust cutting waste oil or water It is necessary to use seamless copper pipes Material Phosphor deoxidized seamless copper pipes It is desirable that the amount of residual oil is less than 40 mg 10 m Do ...

Page 8: ...e careful not to collapse them Do not bend the pipes in an angle more than 90 When pipes are repeatedly bend or stretched the material will harden making it difficult to bend or stretch them any more Do not bend or stretch the pipes more than 3 times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break 4 3 3 Pipe connection CAUTIO...

Page 9: ... BAD Trap Observe the following procedures to construct centralized drain pipe fittings VP30 or more O D 38 mm or more Downward gradient 1 100 or more 700 mm or less WARNING Do not insert the drain piping into the sewer where sulfurous gas occurs Heat exchange erosion may occur Insulate the parts properly so that water will not drip from the connection parts Check for proper drainage after the con...

Page 10: ...o avoid space with Drain hose 1 and Hose band 2 press firmly the Drain hose insulation B 3 When drain pump is used Ceiling concealed type only 3 Drain hose insulation B Ensure there is no space When drain pump is not used Natural drainage 3 Drain hose insulation B Ensure there is no space STEP1 STEP3 Butt the insulation against the unit STEP 1 Unit Slit Press firmly Press firmly STEP 2 Slit Press fi...

Page 11: ...t the same time Otherwise electric shock or fire could result Always connect the earth cable Improper grounding work can cause electric shocks Install the remote controller cables so as not to be direct touched with your hand Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively Connect the connection cable firmly to the terminal board I...

Page 12: ...r branch box units by attaching a earth cable Unit shall be grounded in compliance with the applicable local and national cables CAUTION Be sure to refer to the above diagram for do correct field wiring Wrong wiring causes malfunction of the unit Check local electrical rules and also any specific wiring instructions or limitation 6 2 Connection cable preparation Keep the earth wire longer than the...

Page 13: ...ct the connector to the front case Screws SET BACK Front case back side Rear case Connector When remote controller cable is concealed 1 Conceal the remote controller cable 2 Pass the remote controller cable through the hole in the rear case and connect the remote controller cable to the remote controller terminal board specified in figure 3 Clamp the remote controller cable sheath with the binder ...

Page 14: ...er and turn it on again Function Details 1 Filter Sign The indoor unit has a sign to inform the user that it is time to clean the filter Select the time setting for the filter sign display interval in the table below according to the amount of dust or debris in the room If you do not wish the filter sign to be displayed select the setting value for No indication Factory setting Setting description...

Page 15: ...oom temperature can be selected from the following 2 examples Choose the detection location that is best for the installation location A Indoor unit setting factory setting The room temperature is detected by the indoor unit temperature sensor 1 When the THERMO SENSOR button is pressed the lock display flashes because the function is locked at the factory A Indoor unit B Indoor unit remote control...

Page 16: ...DIP SW 1 No 2 DIP SW 1 No 2 1 Normal OFF 2 Dual OFF ON 8 TEST RUN CAUTION Always turn on the power 12 hours prior to the start of the operation in order to ensure compressor protection CHECK ITEMS 1 Is operation of each button on the remote controller normal 2 Does each lamp light normally 3 Do not air flow direction louvers operate normally 4 Is the drain normal 5 Is there any abnormal noise and ...

Page 17: ...erminals Output terminal CN103 Input No Voltage terminal CN102 Wiring arrangement Binder Medium Accessories Bind with this cable 1 9 3 Remote sensor Optional parts Connection method Connection terminals Remote sensor terminal CN8 Wiring arrangement Binder Medium Accessories Bind with this cable Remove the existing connector and replace it with the remote sensor connector ensure that the correct co...

Page 18: ...t or optional parts for binder Use an accessory of optional parts for bushing Ceiling Avoid covering the air inlet with the wirings Binders Air inlet Binder Knockout hole Bushing Do not bind the power supply cable and other cables together CAUTION To protect the cable insulation after opening a knockout hole remove any burrs from the edge of the hole 10 CUSTOMER GUIDANCE Explain the following to t...

Page 19: ... Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way va...

Reviews: