5. INDOOR FAN CONTROL
The airflow can be switched in 5 steps such as Auto, Quiet, Lo, Me, Hi, while the indoor fan only runs.
When fan mode is set at [Auto], it operates on [Me] fan Speed.
01-04
2. FAN OPERATION
3. COOLING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature,
as shown in Figure4.
On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow of [Cool]
operation modes Quiet, Lo, Me, Hi, as shown in Table 5.
( Fig.4 : Airflow change - over ( Cooling : Auto ) )
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
TR-Ts > 2°C
1°C > TR-Ts
2°C > TR-Ts > 1°C
=
TR-Ts > 2.5°C
=
1.5°C > TR-Ts
2.5°C > TR-Ts > 1.5°C
=
Hi mode
Me mode
Lo mode
1. Fan speed
( Table 5 : Indoor fan speed )
Operation mode
Air flow mode
Speed (rpm)
Cooling/ Fan
Heating
Dry
X zone: 650
J zone: 610
X zone: 650
J zone: 610
X zone: 740
J zone: 710
AS*G09LTCB
AS*G12LTCB
AS*G14LTCB
4. DRY OPERATION
Refer to the Table 5.
During the dry mode operation, the fan speed setting can not be changed.
Hi
Hi
Me+
Me
Me
Lo
Lo
Quiet
Quiet
S-Lo
Cool air prevention
Powerful
Powerful
1410
1300
1220
1120
960
650
610
570
1470
1370
1260
1180
960
650
610
570
1620
1510
1440
1220
1030
790
610
570
1410
1300
1080
960
650
1470
1370
1120
960
650
1550
1440
1220
980
740
Summary of Contents for AO*G09LTCN
Page 4: ......
Page 5: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 26: ......
Page 27: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Page 64: ......
Page 65: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Page 71: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2011 Printed in Japan ...