Trouble shooting 17
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 : Check connection of around the Compressor components
OK
OK
OK
OK
Check Point 3: Replace Main PCB
Outdoor unit Main PCB
Compressor
Compressor motor control error
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
If Check Point 1,2 do not improve the symptom, change Main PCB.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
(Refer to PARTS INFORMATION 2)
For Compressor Terminal, Main PCB
If the detected rotor location is out of phase with actual rotor location
more than 90°, the compressor stops.
After the compressor restarts, if the same operation is repeated
within 40sec, the compressor stops again.
If and repeats 5 times, the compressor stops permanently.
02-21
Check Point 1 : Check Noise from Compressor
Turn on Power and check operation noise.
If an abnormal noise show, replace Compressor.
OK
OK
Check Point 4: Replace Compressor
If Check Point 3 do not improve the symptom, change Compressor.
Indicate or Display:
Refer to error code table.
Summary of Contents for AO*G09LTCN
Page 4: ......
Page 5: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 26: ......
Page 27: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Page 64: ......
Page 65: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Page 71: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2011 Printed in Japan ...