01-14
17. COMPRESSOR PREHEATING
18. 10°C
HEAT OPERATION
10°C HEAT operation performs as below when pressing 10°C HEAT button or Weekly timer setting on the remote
controller.
Mode Heating
Setting temperature 10°C
Fan mode Auto
LED display Economy
Defrost operation Operate as normal
( Table 18 : 10°C HEAT operation )
19.
ECONOMY OPERATION
20 .
HUMAN SENSOR CONTROL
The ECONOMY operation functions by pressing ECONOMY button on the remote controller.
At the maximum output, ECONOMY Operation is approximately 70% of normal air conditioner operation
for cooling and heating.
The ECONOMY operation is almost the same operation as below settings.
Mode Cooling/ Dry Heating
Target temperature Setting temp.+1°C Setting temp.-1°C
( Table 19 )
Mode Cooling/ Dry Heating
Target temperature Setting temp.+2°C Setting temp.-4°C
( Table 20 )
The HUMAN SENSOR functions by pressing SENSOR button on the remote controller.
When the sensor detects that there is no one in the room for 20 minutes or more,
it automatically changes the operation as below settings.
When someone comes back into the room, the human sensor will detect this, and
automatically revert to the original settings.
90°
6 m
6 m
50°
50°
Vertical angle 90°(Side view)
Horizontal angle 100°(Top view)
( Application range )
The sensor unit should detect when the human body (estimate: 100cmX30cm) or the object
which has more than 4 degreesC temp, difference from the background and are crossed with
1.0m/s speed in front of the sensor unit.
When the outdoor heat exchanger temperature is lower than 5°C and the all operation has
been stopped for 30 minutes, power is applied to the compressor and the compressor is heated.
(By heating the compressor, warm air is quickly discharged when operation is started.)
When operation was started, and when the outdoor heat exchanger temperature rises to 7°C or greater,
preheating is ended.
Summary of Contents for AO*G09LTCN
Page 4: ......
Page 5: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 26: ......
Page 27: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Page 64: ......
Page 65: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Page 71: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan September 2011 Printed in Japan ...