background image

- (02 - 17) -

O

U

TD

O

O

R U

N

IT

AO

G

07-

14

LE

O

U

TD

O

O

R U

N

IT

AO

G

07-

14

LE

SAFETY DEVICES

10. 

Protection form

Model

AO

G07LE

AO

G09LE

AO

G12LE

AO

G14LE

Circuit protection

Current fuse
(MAIN PRINTED
CIRCUIT BOARD)

20A/250V

5A/250V

Fan motor protection

Thermal protection
program

OFF : 100

+10

-10

°C

ON : 95

+10

-10

°C

High Pressure Protection

Terminal protection program
COMPRESSOR TEMP.

OFF:110°C 

ON:After 7 minutes

Summary of Contents for AO*G07LEC

Page 1: ...AIR CONDITIONER Wall Mounted type INDOOR OUTDOOR AS G07LECA AS G09LECA AS G12LECA AS G14LECA AO G07LEC AO G09LEC AO G12LEC AO G14LEC DESIGN TECHNICAL MANUAL ...

Page 2: ...1 INDOOR UNIT WALL MOUNTED TYPE AS G07LECA AS G09LECA AS G12LECA AS G14LECA DTR_AS049E_03 2011 03 23 ...

Page 3: ...E 01 11 6 1 COOLING CAPACITY 01 11 6 2 HEATING CAPACITY 01 12 7 FAN PERFORMANCE 01 13 7 1 AIR VELOCITY DISTRIBUTION 01 13 7 2 AIR FLOW 01 15 8 OPERATION NOISE 01 17 8 1 NOISE LEVEL CURVE 01 17 8 2 SOUND LEVEL CHECK POINT 01 19 9 ELECTRIC CHARACTERISTICS 01 20 10 SAFETY DEVICES 01 21 11 EXTERNAL INPUT OUTPUT 01 22 11 1 EXTERNAL INPUT 01 22 11 2 EXTERNAL OUTPUT 01 24 12 FUNCTION SETTING 01 25 13 OPT...

Page 4: ... UNIT Air flow mode can be set in 4 steps and more detailed air flow setting is possible Fan speed Noise level Quiet 21dB A AS G07 09 12LE OUTDOOR UNIT Low noise mode Introduction of a low outdoor noise operation mode allow the outdoor unit to have quiet mode operation setting Performance may drop depending on the outside air temperature condition etc Rated noise value 3dB b a a a b DC compressor ...

Page 5: ...e temperature drops below 10 C Powerful operation z z 20 minutes continuous operation by maximum airflow and maximum compressor speed is possible Rapid cooling and heating makes the room comfortable quickly Powerful Setting temp Normal mode Time Temperature Low outdoor air temperature correspondence z z Corresponds to cooling operation at 10 C outdoor air temperature Corresponds to heating operati...

Page 6: ...ures z z Easy maintenance z z Easy maintenance and always clean Troublesome maintenance has been made easy Since the front panel is easy to remove maintenance is also easy Apple catechin Filter Long life Ion Deodorization Filter Ion Deodorization Filter Apple catechin Filter Dirty Air Clean Air ...

Page 7: ...ep timer function automatically corrects the temperature thermostat setting according to the timer setting to prevent excessive cooling and heating while sleeping 60min 1 C 2 C Timer setting 1 C 30min 60min 90min 2 C 3 C 4 C Timer setting Cooling operation dry operation When the sleep timer is set the set temperature automatically rises 1 C every hour The set temperature can rise up to a maximum o...

Page 8: ... x W x D mm 205 x 61 x 17 WEIGHT g 122 ACCESSORY Holder 1 Signal Transmitter 2 10 C HEAT button 3 MODE button 4 ECONOMY button 5 OUTDOOR UNIT LOW NOISE button 6 ON TIMER button 7 OFF TIMER button 8 CLOCK ADJUST button 9 POWERFUL button 10 SET TEMP button 11 START STOP button 12 FAN button 13 SWING button 14 SET button 15 SLEEP TIMER button 16 CANCEL button 17 RESET button 18 TIMER SET button 19 Re...

Page 9: ... 0 75 0 99 1 305 Min Max 0 25 1 60 0 25 1 60 0 25 1 99 0 25 2 40 Current Cooling Rated A 2 7 3 5 4 4 5 3 Max 6 0 6 0 6 5 9 0 Heating Rated 3 5 3 8 4 7 6 0 Max 7 5 7 5 9 0 10 5 EER Cooling kW kW 4 47 3 91 3 70 3 62 COP Heating 4 38 4 27 4 04 3 83 SENSIBLE CAPACITY Cooling kW 1 2 1 6 2 2 2 6 POWER FACTOR Cooling 76 80 91 91 Heating 85 86 92 94 Moisture removal l h pints h 1 3 2 3 1 3 2 3 1 8 3 2 2 1...

Page 10: ... 01 07 WALL MOUNTED TYPE AS G07 14LE WALL MOUNTED TYPE AS G07 14LE DIMENSIONS 444 MODEL AS G07LE AS G09LE AS G12LE Unit mm ...

Page 11: ...NTED TYPE AS G07 14LE WALL MOUNTED TYPE AS G07 14LE MODEL AS G14LE Unit mm 94 52 78 ø2 65 for pipe inlet ø2 65 for pipe inlet Outline of unit 323 353 Gas pipe 415 Liquid pipe 327 237 450 209 62 18 47 47 184 215 18 82 ...

Page 12: ... 01 09 WALL MOUNTED TYPE AS G07 14LE WALL MOUNTED TYPE AS G07 14LE INSTALLATION PLACE Unit mm 1500 or more 1800 or more 63 or more 45 or more 48 or more 52 or more Outline of unit 70 or more 100 or more ...

Page 13: ... 01 10 WALL MOUNTED TYPE AS G07 14LE WALL MOUNTED TYPE AS G07 14LE WIRING DIAGRAMS 555 MODEL AS G07LE AS G09LE AS G12LE AS G14LE ...

Page 14: ...5 2 80 1 72 0 65 40 1 76 1 22 0 62 1 96 1 23 0 63 2 03 1 33 0 63 2 16 1 34 0 64 2 23 1 44 0 64 2 36 1 44 0 65 2 50 1 53 0 65 43 1 63 1 13 0 62 1 82 1 14 0 62 1 88 1 24 0 63 2 00 1 24 0 63 2 07 1 34 0 64 2 19 1 33 0 64 2 31 1 42 0 65 AFR 11 5 Indoor temperature CDB 18 21 23 25 27 29 32 CWB 12 15 16 18 19 21 23 Outdoor temperature CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SH...

Page 15: ...15 3 96 1 17 3 86 1 19 3 76 1 22 3 67 1 24 7 6 4 41 1 17 4 31 1 20 4 20 1 22 4 10 1 25 3 99 1 27 10 8 4 64 1 19 4 53 1 21 4 42 1 24 4 31 1 26 4 20 1 29 15 10 4 81 1 18 4 69 1 20 4 58 1 23 4 46 1 25 4 35 1 27 AFR 11 8 Indoor temperature CDB 16 18 20 22 24 Outdoor temperature CDB CWB TC IP TC IP TC IP TC IP TC IP 15 16 3 40 1 72 3 32 1 76 3 24 1 80 3 16 1 83 3 07 1 87 10 11 3 76 1 72 3 67 1 76 3 58 ...

Page 16: ... 0 1 2 Unit m s m m TOP VIEW Vertical flap Up Horizontal flap Center 0 1 2 3 4 5 6 7 8 2 0 1 0 1 0 0 5 0 5 3 2 1 0 1 2 3 Unit m s m TOP VIEW Vertical flap Up Horizontal flap Right Left m 0 1 2 3 4 5 6 7 8 2 0 1 0 0 5 3 2 1 0 Unit m s m SIDE VIEW Vertical flap Up Horizontal flap Center m 0 1 2 3 4 5 6 7 8 2 0 1 0 0 5 3 2 1 0 Unit m s m SIDE VIEW Vertical flap Down Horizontal flap Center m 0 1 2 3 4...

Page 17: ...P Upward HORIZONTAL FLAP Center 0 1 2 3 4 5 6 7 8 2 0 1 0 0 5 3 2 1 0 Unit m s m SIDE VIEW VERTICAL FLAP Upward HORIZONTAL FLAP Center m 0 1 2 3 4 5 6 7 8 2 0 1 0 0 5 3 2 1 0 Unit m s m SIDE VIEW VERTICAL FLAP Downward HORIZONTAL FLAP Center m 0 1 2 3 4 5 6 7 8 2 0 1 0 1 0 0 5 0 5 2 1 0 1 2 Unit m s m m TOP VIEW VERTICAL FLAP Upward HORIZONTAL FLAP Right Left 0 1 2 3 4 5 6 7 8 ...

Page 18: ...Number of rotations r p m Air flow HIGH 1400 690 m3 h 191 l s 406 CFM MED 1200 610 m3 h 169 l s 359 CFM LOW 920 440 m3 h 122 l s 259 CFM QUIET 620 300 m3 h 83 l s 176 CFM Fan speed Number of rotations r p m Air flow HIGH 1440 710 m3 h 197 l s 417 CFM MED 1200 610 m3 h 169 l s 359 CFM LOW 980 480 m3 h 133 l s 282 CFM QUIET 670 310 m3 h 86 l s 182 CFM ...

Page 19: ... r p m Air flow HIGH 1400 770 m3 h 213 l s 453 CFM MED 1230 680 m3 h 188 l s 400 CFM LOW 1000 540 m3 h 150 l s 318 CFM QUIET 750 410 m3 h 114 l s 241 CFM Fan speed Number of rotations r p m Air flow HIGH 1400 770 m3 h 213 l s 453 CFM MED 1230 680 m3 h 188 l s 400 CFM LOW 1050 580 m3 h 161 l s 341 CFM QUIET 770 420 m3 h 116 l s 247 CFM ...

Page 20: ...Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 High Quiet Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 ...

Page 21: ...ound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 MODEL AS G14LE Cooling z z NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Heating z z Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 ...

Page 22: ... 01 19 WALL MOUNTED TYPE AS G07 14LE WALL MOUNTED TYPE AS G07 14LE SOUND LEVEL CHECK POINT 88888 ...

Page 23: ...Model name AS G07LE AS G09LE AS G12LE AS G14LE Power supply Voltage V 230 Frequency Hz 50 Max operating current A 0 4 1 Wiring Spec Connection cable mm2 1 0 1 5 1 5 Limited wiring length m 21 1 Wiring Spec Selected Sample Selected based on Japan Electrotechnical Standard and Codes Committee E0005 ...

Page 24: ... G07 14LE SAFETY DEVICES 1111 Protection form Model AS G07LE AS G09LE AS G12LE AS G14LE Circuit protection Current fuse PCB 3 15A 250V Terminal protection Current thermal fuse 3A 250V Fan motor protection Thermal protector program 100 15 10 C OFF 95 5 10 C ON ...

Page 25: ... ON Initial starting after power turned on Starting other than at the left Operation mode Auto changeover Mode at previous operation Set temperature 24 C Temperature at previous operation Air flow mode AUTO Mode at previous operation Up down air direction swing Standard air direction swing OFF Air direction at previous operation Left right air direction swing Standard air direction swing OFF Air d...

Page 26: ...ation Stop Command Forced stop Normal Remote control operation invalidity Parts Optional z z Parts name Model name External connect kit UTY XWZX Communication box kit UTY XCBXE for AS G07 09 12LE UTY XCBXZ1 for AS G14LE For operating the EXTERNAL function the Compact wall mounted type requires the communication kit in addition to the wire UTY XWZX Wire External input UTY XWZX ...

Page 27: ...mA Field supply Optional parts Ex Display Indoor control PC board Communication kit Connected unit Ex Relay unit 1 2 Signal Relay power supply V Connector 10 m 24V DC ON OFF Operation Stop Indoor unit Output signal Parts Optional z z Parts name Model name External connect kit UTY XWZX Communication box kit UTY XCBXE for AS G07 09 12LE UTY XCBXZ1 for AS G14LE For operating the EXTERNAL function the...

Page 28: ...the SET TEMP 111 button to change the signal code between Match the code on the display to the air conditioner signal code initially set to If the signal code does not need to be selected press the 10 C Heat button and proceed to STEP 2 Press the MODE button and check that the indoor unit can receive signals at the 222 displayed signal code Press the 10 C Heat button to accept the signal code and ...

Page 29: ... Standard 11 00 Long interval 01 Short interval 02 No indication 03 The filter sign interval time is different according to Indoor unit type as follows Setting description Compact Wall Mounted Standard 400 hours Long interval 1000 hours Short interval 200 hours 2 Cooler room temperature correction Depending on the installed environment the room temperature sensor may require a correction The setti...

Page 30: ...the control by Wired remote controller temperature sensor Factory setting Setting description Function number Setting value No 42 00 Yes 01 If setting value is 00 Room temperature is controlled by the indoor unit temperature sensor If setting value is 01 Room temperature is controlled by either indoor unit temperature sensor or remote controller unit sensor 6 Remote controller signal code Change t...

Page 31: ... code on the display to the air conditioner signal code Press the MODE button again to return to the clock display The signal code will 444 be changed If no buttons are pressed within 30 seconds after the signal code is displayed the system returns to the original clock display In this case start again from step 1 The air conditioner signal code is set to A prior to shipment Contact your retailer ...

Page 32: ...oner PC board for AS G07 09 12LE Communication kit UTY XCBXZ1 Use to connect with optional devices and air conditioner PC board for AS G14LE External connect kit UTY XWZX Required when external device is connected Optional communication kit is necessary for the installation Apple catechin filter UTR FA16 Fine dust invisible mold spores and harmful microorganisms are absorbed onto the fi lter by st...

Page 33: ...2 OUTDOOR UNIT SINGLE TYPE AO G07LEC AO G09LEC AO G12LEC AO G14LEC DTR_AO072E_02 2011 03 03 ...

Page 34: ...REFRIGERANT CIRCUIT 02 04 4 WIRING DIAGRAMS 02 05 5 CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE 02 07 6 ADDITIONAL CHARGE CALCULATION 02 10 7 AIR FLOW 02 11 8 OPERATION NOISE 02 13 8 1 NOISE LEVEL CURVE 02 13 8 2 SOUND LEVEL CHECK POINT 02 15 9 ELECTRIC CHARACTERISTICS 02 16 10 SAFETY DEVICES 02 17 ...

Page 35: ...Charge g 650 800 1050 Refrigerant oil Type POE VG74 Enclosure Material Steel Colour Beige Approximate colour of MUNSELL 10YR7 5 1 0 Dimensions H W D Net mm 540 660 290 540 790 290 Gross mm 611 797 401 648 938 400 Weight Net kg lbs 23 51 29 64 34 75 Gross 26 57 32 71 38 84 Connenction pipe Size Liquid mm Ø6 35 Ø1 4 in Gas Ø9 52 Ø3 8in Ø12 7 Ø1 2in Method Flare Pre charge length m 15 Max length 20 M...

Page 36: ...0 mm or more 100 mm or more 600 mm or more 300 mm or more 100 mm or more 300 mm or more Service space 300 mm or more 300 mm or more 300 mm or more When there are obstacles at the back or front sides When there are obstacles at the back side s and top When there are obstacles at the back side with the installation of more than one unit ...

Page 37: ...mm or more 600 mm or more 300 mm or more 100 mm or more 250 mm or more Service space 250 mm or more 250 mm or more 300 mm or more When there are obstacles at the back or front sides When there are obstacles at the back side s and top When there are obstacles at the back side with the installation of more than one unit ...

Page 38: ... MODEL AO G07LE AO G09LE AO G12LE AO G14LE 2 Way valve Strainer Strainer 3 Way valve Muffler 4 Way valve Expansion valve Heat exchanger INDOOR Heat exchanger OUTDOOR Compressor Cooling Heating Refrigerant pipe diameter Liquid 1 4 6 35 mm Gas 3 8 9 52 mm 07 09 12LE 1 2 12 7 mm 14LE ...

Page 39: ... 02 05 OUTDOOR UNIT AO G07 14LE OUTDOOR UNIT AO G07 14LE WIRING DIAGRAMS 444 MODEL AO G07LE AO G09LE ...

Page 40: ... 02 06 OUTDOOR UNIT AO G07 14LE OUTDOOR UNIT AO G07 14LE MODEL AO G12LE AO G14LE ...

Page 41: ...t 15 0 832 0 822 10 0 917 0 832 0 822 7 5 0 961 0 917 0 832 0 822 5 1 000 0 961 0 917 0 832 0 822 0 1 000 0 961 0 917 0 832 0 822 Û2 Indoor unit is under than outdoor unit 5 0 995 0 956 0 912 0 828 0 818 7 5 0 954 0 910 0 826 0 816 10 0 908 0 824 0 814 15 0 815 0 805 COOLING Pipe length m 5 7 5 10 15 20 Height difference H m Û1 Indoor unit is upper than outdoor unit 15 0 872 0 910 10 0 961 0 886 0...

Page 42: ... 5 0 994 0 968 0 896 0 879 5 1 000 0 994 0 968 0 896 0 879 0 1 000 0 994 0 968 0 896 0 879 Û2 Indoor unit is under than outdoor unit 5 0 995 0 989 0 963 0 891 0 875 7 5 0 987 0 961 0 889 0 873 10 0 959 0 887 0 871 15 0 878 0 862 COOLING Pipe length m 5 7 5 10 15 20 Height difference H m Û1 Indoor unit is upper than outdoor unit 15 0 858 0 868 10 0 929 0 872 0 882 7 5 0 960 0 933 0 876 0 885 5 0 99...

Page 43: ... 5 1 013 1 004 0 956 0 938 5 1 000 1 013 1 004 0 956 0 938 0 1 000 1 013 1 004 0 956 0 938 Û2 Indoor unit is under than outdoor unit 5 0 995 1 008 0 999 0 951 0 933 7 5 1 005 0 997 0 948 0 931 10 0 994 0 946 0 929 15 0 937 0 919 COOLING Pipe length m 5 7 5 10 15 20 Height difference H m Û1 Indoor unit is upper than outdoor unit 15 0 893 0 909 10 0 955 0 908 0 924 7 5 0 975 0 959 0 912 0 928 5 0 99...

Page 44: ...O G14LE Refrigerant charge z z Refrigerant type R410A Refrigerant amount g 650 Total pipe length m 15 or less 20 MAX 20g m Additional charge g 0 100 Refrigerant type R410A Refrigerant amount g 800 Total pipe length m 15 or less 20 MAX 20g m Additional charge g 0 100 Refrigerant type R410A Refrigerant amount g 1050 Total pipe length m 15 or less 20 MAX 20g m Additional charge g 0 100 ...

Page 45: ...ating z z MODEL AO G12LE Cooling z z Heating z z Number of rotations r p m Air flow 730 1720 m3 h 476 l s 1011 CFM Number of rotations r p m Air flow 650 1510 m3 h 418 l s 888 CFM Number of rotations r p m Air flow 860 1830 m3 h 507 l s 1076 CFM Number of rotations r p m Air flow 760 1600 m3 h 443 l s 941 CFM ...

Page 46: ...OR UNIT AO G07 14LE OUTDOOR UNIT AO G07 14LE MODEL AO G14LE Cooling z z Heating z z Number of rotations r p m Air flow 800 1800 m3 h 499 l s 1058 CFM Number of rotations r p m Air flow 750 1660 m3 h 460 l s 976 CFM ...

Page 47: ... center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Heating z z Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pres...

Page 48: ...0 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Heating z z Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0dB 0 00...

Page 49: ... 02 15 OUTDOOR UNIT AO G07 14LE OUTDOOR UNIT AO G07 14LE SOUND LEVEL CHECK POINT 88888 ...

Page 50: ... Wiring Spec Main Fuse Circuit breaker Current A 20 Power Cable mm2 1 5 3 Limited wiring length m 21 1 The maximum current is the total current of indoor unit and outdoor unit 2 Wiring Spec Selected Sample Selected based on Japan Electrotechnical Standard and Codes Committee E0005 3 Limited wiring length This is the wiring length in case voltage descent is less than 2 When the wiring length become...

Page 51: ... Model AO G07LE AO G09LE AO G12LE AO G14LE Circuit protection Current fuse MAIN PRINTED CIRCUIT BOARD 20A 250V 5A 250V Fan motor protection Thermal protection program OFF 100 10 10 C ON 95 10 10 C High Pressure Protection Terminal protection program COMPRESSOR TEMP OFF 110 C ON After 7 minutes ...

Reviews: