- (02 - 07) -
O
U
TD
O
O
R U
N
IT
AO
G
07-
14
LE
O
U
TD
O
O
R U
N
IT
AO
G
07-
14
LE
CAPACITY COMPENSATION RATE FOR PIPE LENGTH
5.
AND HEIGHT DIFFERENCE
MODEL
: AO
G07LE, AO
G09LE
Height difference H
1 Indoor unit is upper than outdoor unit.
2 Indoor unit is under than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
5
7.5
10
15
20
Height
difference H
(m)
Û
1
Indoor unit is
upper than
outdoor unit.
15
-
-
-
0.832
0.822
10
-
-
0.917
0.832
0.822
7.5
-
0.961
0.917
0.832
0.822
5
1.000
0.961
0.917
0.832
0.822
0
1.000
0.961
0.917
0.832
0.822
Û
2
Indoor unit is
under than
outdoor unit
-5
0.995
0.956
0.912
0.828
0.818
-7.5
-
0.954
0.910
0.826
0.816
-10
-
-
0.908
0.824
0.814
-15
-
-
-
0.815
0.805
COOLING
Pipe length (m)
5
7.5
10
15
20
Height
difference H
(m)
Û
1
Indoor unit is
upper than
outdoor unit.
15
-
-
-
0.872
0.910
10
-
-
0.961
0.886
0.925
7.5
-
0.979
0.965
0.890
0.929
5
0.992
0.983
0.969
0.893
0.933
0
1.000
0.991
0.976
0.901
0.940
Û
2
Indoor unit is
under than
outdoor unit
-5
1.000
0.991
0.976
0.901
0.940
-7.5
-
0.991
0.976
0.901
0.940
-10
-
-
0.976
0.901
0.940
-15
-
-
-
0.901
0.940