- (02 - 09) -
O
U
TD
O
O
R U
N
IT
AO
G
07-
14
LE
O
U
TD
O
O
R U
N
IT
AO
G
07-
14
LE
MODEL
: AO
G14LE
Height difference H
1 Indoor unit is upper than outdoor unit.
2 Indoor unit is under than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
5
7.5
10
15
20
Height
difference H
(m)
Û
1
Indoor unit is
upper than
outdoor unit.
15
-
-
-
0.956
0.938
10
-
-
1.004
0.956
0.938
7.5
-
1.013
1.004
0.956
0.938
5
1.000
1.013
1.004
0.956
0.938
0
1.000
1.013
1.004
0.956
0.938
Û
2
Indoor unit is
under than
outdoor unit
-5
0.995
1.008
0.999
0.951
0.933
-7.5
-
1.005
0.997
0.948
0.931
-10
-
-
0.994
0.946
0.929
-15
-
-
-
0.937
0.919
COOLING
Pipe length (m)
5
7.5
10
15
20
Height
difference H
(m)
Û
1
Indoor unit is
upper than
outdoor unit.
15
-
-
-
0.893
0.909
10
-
-
0.955
0.908
0.924
7.5
-
0.975
0.959
0.912
0.928
5
0.992
0.979
0.963
0.916
0.931
0
1.000
0.987
0.970
0.923
0.939
Û
2
Indoor unit is
under than
outdoor unit
-5
1.000
0.987
0.970
0.923
0.939
-7.5
-
0.987
0.970
0.923
0.939
-10
-
-
0.970
0.923
0.939
-15
-
-
-
0.923
0.939
Summary of Contents for AO*G07LEC
Page 33: ...2 OUTDOOR UNIT SINGLE TYPE AO G07LEC AO G09LEC AO G12LEC AO G14LEC DTR_AO072E_02 2011 03 03 ...
Page 40: ... 02 06 OUTDOOR UNIT AO G07 14LE OUTDOOR UNIT AO G07 14LE MODEL AO G12LE AO G14LE ...
Page 49: ... 02 15 OUTDOOR UNIT AO G07 14LE OUTDOOR UNIT AO G07 14LE SOUND LEVEL CHECK POINT 88888 ...