En-14
7.4. Function setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to “7.1. Setting the address” for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Setting number
Default
Details
Filter indica-
tor interval
11
00 Standard
Adjust the filter cleaning interval noti-
fication. If the notification is too early,
change to setting 01. If the notifica-
tion is too late, change to setting 02.
01 Longer
02 Shorter
Filter indica-
tor action
13
00 Enable
Enable or disable the filter indicator.
Setting 02 is for use with a central
remote controller.
01 Disable
02
Display only on
central remote
controller
(Forbidden)
20
00
(Forbidden)
23
00
(Forbidden)
24
00
Static pres-
sure
26
Refer to “7.3. Static pressure mode”
(Forbidden)
27
Cool air
temperature
trigger
30
00 Standard
Adjust the cool air trigger tempera-
ture. To lower the trigger tem-
perature, use setting 01. To raise the
trigger temperature, use setting 02.
01 Adjust (1)
02 Adjust (2)
Heat air
temperature
trigger
31
00 Standard
Adjust the heat air trigger tempera-
ture. To lower the trigger temperature
by 6 degrees C, use setting 01. To
lower the trigger temperature by 4
degrees C, use setting 02. To raise
the trigger temperature, use setting
03.
01 Adjust (1)
02 Adjust (2)
03 Adjust (3)
Auto restart
40
00 Enable
Enable or disable automatic system
restart after a power outage.
01 Disable
Cool Air
Prevention
43
00 Super low
Restrain the cold airflow with making
the airflow lower when starting heat-
ing operation. To correspond to the
ventilation, set to 01.
01
Follow the
setting on
the remote
controller
External
control
46
00 Start/Stop
Allow an external controller to start
or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed
from an external controller, all re-
frigerant systems will be disabled.
* If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/Stop by a
remote controller is restricted.
01
Emergency
stop
02 Forced stop
Error report
target
47
00 All
Change the target for reporting
errors. Errors can either be reported
in all locations, or only on the central
remote controller.
01
Display only on
central remote
controller
Fan set-
ting when
cooling
thermostat
OFF
49
00
Follow the
setting on
the remote
controller
When set to 01, the fan stops when
the thermostat is OFF in cooling
operation. Connection of the wired
remote controller (2-wire type or
3-wire type) and switching its therm-
istor are necessary.
01 Stop
Switching
function for
external
inputs
60
00
Forced ther-
mostat off
Setting is required when connecting
a refrigerant-leak detecting device.
(only for J-IIIL series)
01
(Forbidden)
02
03
04
05
06
07
08
09
Refrigerant
leak detection
(Forbidden)
61
00
(Forbidden)
62
00
Auto mode
type
68
00
Single
setpoint auto
mode
(traditional)
Switch the setting method of
auto mode to single or dual
(cooling/heating).
For heat pump systems, it is
necessary to set the master indoor
unit (by wired remote controller).
01
Dual setpoint
auto mode
Function
Function
number
Setting number
Default
Details
Deadband
value
69
00 0°C
Choose the minimum temperature
between cooling and heating
settings (deadband) for Dual
setpoint auto mode (set in No. 68).
01 0.5°C
02 1.0°C
03 1.5°C
04 2.0°C
05 2.5°C
06 3.0°C
07 3.5°C
08 4.0°C
09 4.5°C
(Forbidden)
70
00
(Forbidden)
72
00
(Forbidden)
73
00
(Forbidden)
74
00
(Forbidden)
75
00
8. TEST RUN
8.1. Test run using Outdoor unit (PCB)
• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to
be used for the test run.
8.2. Test run using Remote Controller
• Refer to the Installation Manual for the remote controller to perform the test run using
the wireless remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER indicator lamps
fl ash slowly at the same time.
For details, please refer to the Manual of “IR Receiver Unit” or “Wired Remote Controller”.
9. CHECK LIST
Pay special attention to the check items below when installing the indoor unit(s). After
installation is complete, be sure to check the following check items again.
CHECK ITEMS
If not performed correctly
CHECK
BOX
Has the indoor unit been installed
correctly?
Vibration, noise,
indoor unit may drop
Has there been a check for gas leaks
(refrigerant pipes)?
No cooling, No heating
Has heat insulation work been
completed?
Water leakage
Does water drain easily from the indoor
units?
Water leakage
Is the voltage of the power source the
same as that indicated on the label on
the indoor unit?
No operation, heat or burn
damage
Are the wires and pipes all connected
completely?
No operation, heat or burn
damage
Is the indoor unit earthed (grounded)?
Short circuit
Is the connection cable the specified
thickness?
No operation, heat or burn
damage
Are the inlets and outlets free of any
obstacles?
No cooling, No heating
Does start and stop air conditioner
operation by remote controller or
external device?
No operation
After installation is completed, has the
proper operation and handling been
explained to the user?
9373385257_IM.indb 14
9373385257_IM.indb 14
2/15/2019 8:46:37 AM
2/15/2019 8:46:37 AM