En-13
7.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
A B C D
A B C D
Indoor
unit
Remote
controller
Confusion
Code change
Custom code setting for indoor unit
Set the DIP switch SET 3 SW1, SW2 referring to the Table B.
IU AD
REF AD
RC AD
×10 ×1
×10 ×1
SET3
SET4
SW 4
SW 3
SW 2
SW 1
Dip switch “SET 3”
ON
OFF
Table B
Custom code
A (Factory setting)
B
C
D
DIP switch SET3 SW1
OFF
ON
OFF
ON
DIP switch SET3 SW2
OFF
OFF
ON
ON
7.3. Static pressure mode
CAUTION
If the applicable static pressure does not match the static pressure mode, the static
pressure mode may be changed to another mode manually.
It is necessary to set up a static pressure mode for each usage of static pressure.
Static pressure can be set at site.
Relation between set values and static pressure are as the following table.
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
Function
Number
Setting Number
Setting Static Pressure
AR024
AR030
AR036
AR045
26
00
SP mode 00
0 Pa
01
SP mode 01
10 Pa
02
SP mode 02
20 Pa
03
SP mode 03
30 Pa
04
SP mode 04
40 Pa
05
SP mode 05
50 Pa
06
SP mode 06
60 Pa
07
SP mode 07
70 Pa
08
SP mode 08
80 Pa
09
SP mode 09
90 Pa
10
SP mode 10
100 Pa
11
SP mode 11
110 Pa
12
SP mode 12
120 Pa
(110 Pa)
13
SP mode 13
130 Pa
(120 Pa)
14
SP mode 14
140 Pa
31
SP mode 31
(Factory setting)
40 Pa
50 Pa
60 Pa
* Please refer to FAN PERFORMANCE CURVE within Design & Technical Data for the
features of each setting.
7. FIELD SETTING
There are 3 methods for address setting by FIELD SETTING as follows.
Set by either of the methods.
Each setting method is described (1) to (3) below.
(1) IU AD, REF AD SW settings..... This section (7.1. Setting the address)
(2) Remote controller settings ....... Refer to the wired or wireless remote controller manual
for detailed setting information. (Set IU AD, REF AD
SW to 0)
(3) Automatic address settings ...... Refer to the outdoor unit manual for detailed setting
information. (Set IU AD, REF AD SW to 0)
CAUTION
• Be sure to turn OFF the power before performing the fi eld setting.
7.1. Setting the address
Manual address setting method
• If the receiver unit is attached, the indoor unit address and the refrigerant circuit
address can also be set up through the wireless remote controller.
CAUTION
Use an insulated screwdriver to set the DIP switches.
IU AD
REF AD
RC AD
×10 ×1
×10 ×1
SET3
SET4
For indoor
unit address
For refrigerant
circuit address
Setting
Setting
range
Type of switch
Indoor unit address
0 to 63
Setting
example
2
IU AD × 10
IU AD × 1
Refrigerant circuit
address
0 to 99
Setting
example
63
REF AD × 10
REF AD × 1
(1) Indoor unit address
Rotary switch (IU AD × 1)...Factory setting “0”
Rotary switch (IU AD × 10)...Factory setting “0”
When connecting multiple indoor units to 1 refrigerant system, set the address at IU
AD SW as shown in the Table A.
(2) Refrigerant circuit address
Rotary switch (REF AD × 1)...Factory setting “0”
Rotary switch (REF AD × 10)...Factory setting “0”
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A
for each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
• If working in an environ-
ment where the wireless
remote controller can be
used, the addresses can
also be set using the
remote controller.
• If setting the addresses
using the wireless
remote controller, set
the indoor unit address
and refrigerant circuit
address to “00”.
(For information on set-
ting using the wireless
remote controller.)
* Do not set the indoor
unit address (IU AD
SW) at 64 to 99.
It may result in failure.
Table A
Address
Rotary switch
setting
Address
Rotary switch
setting
Refrigerant
circuit
REF AD SW
Indoor unit
IU AD SW
× 10
× 1
× 10
× 1
0
0
0
0
0
0
1
0
1
1
0
1
2
0
2
2
0
2
3
0
3
3
0
3
4
0
4
4
0
4
5
0
5
5
0
5
⁞
⁞
⁞
⁞
⁞
⁞
10
1
0
10
1
0
11
1
1
11
1
1
⁞
⁞
⁞
⁞
⁞
⁞
99
9
9
63
6
3
9373385257_IM.indb 13
9373385257_IM.indb 13
2/15/2019 8:46:36 AM
2/15/2019 8:46:36 AM