En-11

Wiring arrangement

In following figure, all the possible connectors are connected for description.
In actual installation, you cannot connect all the connectors at once.

Power supply cable

Clamps

Cable clamp

Cable tie (*1)

*1:  Cable ties for Drain pump unit are accessories of the Drain pump unit. 

Cable ties for other optional parts are locally purchased.

Cable tie 
(*1)

EMI core (accessory of 
the IR receiver unit)

6.6.  External input and external output (Optional parts)

(1) External input

•  Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit 

PCB CNA01 or CNA02.

•  “Operation/Stop” mode, “Emergency stop” mode or “Forced stop” mode can be selected 

with function setting of indoor unit.

•  Indoor unit can be Forced thermostat off  by using indoor unit PCB CNA03 or CNA04.
•  A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.
•  Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed.

•  The wire connection should be separate from the power cable line.

Input select

Use either one of these types of terminal according to the application. (Both types of 
terminals cannot be used simultaneously.)

● Apply voltage terminal ([CNA01], [CNA03])

When a power supply must be provided at the input device you want to connect, use the 
Apply voltage terminal ([CNA01], [CNA03]).

Input

d

ev

ic

e 1

Input

d

ev

ic

e 2

Input

d

ev

ic

e 3

Load 

resistance

Load 

resistance

Load 

resistance

*1

DC power supply
12 to 24V

connected unit

*a

*a

*a

P.C.B

CNA01

CNA03

*b

*1  Make the power supply DC12 to 24V. Select a power supply capacity with an ample 

surplus for the connected load.

Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a  The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
 

Provide a load resistance such that the current becomes DC10mA or less.

 

Select very low current use contacts (usable at DC12V, DC1mA or less).

*b   The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.

When connected to Apply voltage terminals of multiple indoor units with a connected unit, 
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below 
example.

DC power supply 
12 to 24V

connected unit

Load 

resistance

P.C.B

P.C.B

CNA01

P.C.B

Input

d

ev

ic

e 1

Input

d

ev

ic

e 2

In

d

o

o

r u

n

it

In

d

o

o

r u

n

it

In

d

o

o

r u

n

it

Load 

resistance

CNA01

CNA01

● Dry contact terminal ([CNA02], [CNA04])

When a power supply is unnecessary at the input device you want to connect, use the Dry 
contact terminal ([CNA02], [CNA04]).

P.C.B

GND

Ch 1

Ch 3

*c

*c

*c

*d

Ch 2

CNA02

CNA04

connected unit

*c  Select very low current use contacts (usable at DC12V, DC1mA or less).
*d  The wiring is diff erent from Apply voltage terminals. Be suffi  ciently careful when wiring.

When connected to Dry contact terminals of multiple indoor units with a connected unit, 
insulate each indoor unit with relay, etc. as shown on below example.

P

o

w

e

r s

u

p

p

ly f

o

r r

e

lay

In

d

o

o

r u

n

it

In

d

o

o

r u

n

it

In

d

o

o

r u

n

it

Input device 2

Input device 1

K1 to K6: Relay

(Device for DC Current)

P.C.B

K1

P.C.B

P.C.B

CNA02

K2

K3

K4

K5

K6

CNA02

CNA02

NOTE :

When connected to multiple indoor units directly, it will cause breakdown.

Operation behavior

● Input signal type

The input signal type can be selected.
It is switched by DIP switch on the indoor unit PCB. 

Pulse

The width of pulse 
must be longer than 
200msec.

Edge

DIP switch [Set 2 SW2]

Input signal type

OFF (Factory setting)

Edge

ON

Pulse

9373385257_IM.indb   11

9373385257_IM.indb   11

2/15/2019   8:46:35 AM

2/15/2019   8:46:35 AM

Summary of Contents for AirStage ARXA024GLEH

Page 1: ...icio autorizado MANUALE DI INSTALLAZIONE UNITÀ INTERNA tipo a condotto A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Τύπος αγωγού Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE INTERIOR Tipo de tubagem Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ ВНУТРЕННИЙ МОДУЛЬ Короб Только для авторизованного обслуживающего перс...

Page 2: ...ervice personnel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A refrigerant WARNING Do not introduce any substance other than the prescribed refrigerant into the refrigeration cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally ...

Page 3: ...2 I D 25 Hose band 1 For installing drain hose Drain hose insulation 2 Insulates the drain hose and drain cap 2 4 Optional parts When connecting the square duct and round duct use the optional square flange or round flange Square flange Model name UTD SF045T P N 9098180007 1 063 mm 40 mm 206 mm Round flange Model name UTD RF204 P N 9093160004 85 mm ø195 mm ø205 mm ø225 mm ø235 mm Long life filter Mode...

Page 4: ...Decide the mounting position with the customer as follows 1 Install the indoor unit on a place having a sufficient strength so that it withstands against the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space required to service the air conditioner 4 A place from where the air can be distributed evenly th...

Page 5: ...ssories Hanger Accessories Bolt Strength 9 81 to 14 71 N m WARNING Fasten the unit securely with special nuts A and B 3 3 2 Leveling Base vertical direction leveling on the unit right and left Right side Level Air Air Base horizontal direction leveling on top of the unit Drain hose 0 to 5 mm Give a slight tilt to the side to which the drain hose is connected The tilt should be in the range of 0 mm...

Page 6: ...ed seamless copper pipes It is desirable that the amount of residual oil is less than 40 mg 10 m Do not use copper pipes that have a collapsed deformed or discolored portion especially on the interior surface Otherwise the expansion valve or capillary tube may become blocked with contaminants Improper pipe selection will degrade performance As an air conditioner using R410A incurs pressure higher ...

Page 7: ...CAUTION Be sure to install the pipe against the port on the indoor unit correctly If the centering is improper the flare nut cannot tighten smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe Hold the torque wrench at its grip keeping at a the right angle with the pipe in...

Page 8: ... Check the drainage 4 Install the heat insulation 5 Use the attached heat insulation to insulate the drain port and band parts of the body Ensure there is no space Accessories Soft PVC side Accessories Drain hose Drain pan 10 to 15mm Hose band Applying area of adhesive Hard PVC side Drain pipe VP25 locally purchased Joint pipe locally purchased 4 mm or less Wrap the Drain hose insulation around th...

Page 9: ...ply cables to the transmission or remote controller terminals as this will damage the product Never bundle the power supply cable and transmission cable remote controller cable together Separate these cable by 50 mm or more Bundling these cables together will cause miss operation or breakdown When handling PCB static electricity charged in the body may cause malfunction of the PCB Follow the cauti...

Page 10: ...essure bonding may malfunction and cause the cables to abnormally heat up B For strand wiring 1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no str...

Page 11: ...rminal For external outnput CN8 For Remote sensor unit 1 CN48 For IR receiver unit 1 CN65 For one of the following MODBUS convertor 1 Wireless LAN adapter 1 CNA05 For Drain pump unit 1 CN106 CN820 For External power supply unit 1 1 For details refer to each installation manual 6 5 2 Power indicator lamp status Power indicator lamp Green Status contents Lit Lit when the power is turned on Fast flas...

Page 12: ... Do not impress a voltage exceeding 24V across pins 1 2 and 1 3 a The allowable current is DC 5mA to 10mA Recommended DC5mA Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage terminals of multiple indoor units with ...

Page 13: ...xternal input and output cable with appropriate external dimension depending on the number of cables to be installed Output voltage Hi DC12V 2V Lo 0V Permissible current 50mA Output select When indicator etc are connected directly Operation indicator Error indicator Indoor unit Fan status indicator connected unit P C B CNB 01 When connecting with unit equipped with a power supply CNB 01 P C B Conn...

Page 14: ...troller settings Refer to the wired or wireless remote controller manual for detailed setting information Set IU AD REF AD SW to 0 3 Automatic address settings Refer to the outdoor unit manual for detailed setting information Set IU AD REF AD SW to 0 CAUTION Be sure to turn OFF the power before performing the field setting 7 1 Setting the address Manual address setting method If the receiver unit i...

Page 15: ...set ting when cooling thermostat OFF 49 00 Follow the setting on the remote controller When set to 01 the fan stops when the thermostat is OFF in cooling operation Connection of the wired remote controller 2 wire type or 3 wire type and switching its therm istor are necessary 01 Stop Switching function for external inputs 60 00 Forced ther mostat off Setting is required when connecting a refrigera...

Page 16: ...it room temp therm istor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous error 10 8 Poor refrigerant circulation 13 1 RB unit error Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Wired remote controller display UTY RLR 2 wire type E...

Reviews: