background image

En-7

5.4.2  Removing the pinch pipe

 WARNING

Remove the pinch pipe only when the internal gas is completely drained as shown on 
the below instructions.
If gas still remains inside, the piping may crack if you melt the brazing filler metal of the 
junction area with a burner.

Before connecting the piping, remove the pinch pipe in accordance with the following 
instructions:

1)  Verify that the liquid 

side and gas side 3-way 
valves are closed.

2)  Cut the end of the liquid 

side and gas side pinch 
pipe and vent the gas 
inside the pinch pipe.

3)  After all the gas is vented, 

melt the brazing filler 
metal on connecting part 
using a torch and remove 
the pinch pipe.

3-way valves

Pinch pipes

End of pinch pipes

5.4.3 Pipe connection

 CAUTION

Seal the pipe route hole with putty (locally purchased) such that there are no gaps. 
Small insects or animals that are trapped in the outdoor unit may cause a short circuit in 
the electrical component box.

To prevent pipe damage; do not make sharp bends.
Bend the pipe at a radius of 70 mm or greater.

Do not bent pipe many times at same part to prevent break.

After completing all the pipe connection by brazing, perform the indoor unit pipe connec-
tion with a flare joint.

When removing the pinch pipe or brazing the joint pipe, carry out the work while cooling 
down the 3-way valve sufficiently.

• Braze the joint pipe onto the 3-way valves at the liquid and gas side. Install the joint pipe 

appropriately so that it can be connected easily with the main pipe.

• Braze the joint pipe at the liquid and gas side with the main pipe.
*  Be sure to supply nitrogen when brazing.

Connection example

Front connection

Bottom connection

Liquid pipe
(locally 
purchased)

Gas pipe
(locally 
purchased)

Joint pipe A-L 
(accessory)

Liquid pipe
(locally purchased)

Gas pipe
(locally 
purchased)

Joint pipe B-L 
(accessory)

5.4.4  Handling precautions for the valves

• Mounted part of Blank cap is sealed for protection.
• Fasten blank cap tightly after opening valves.

Operating the valves

• Use a hexagon wrench. 

Liquid valve: size 4 mm, Gas valve: size 8 mm.

Opening:

(1)  Insert the hexagon wrench into the 

valve shaft, and turn it counterclock-
wise.

(2)  Stop turning when the valve shaft can 

no longer be turned. (Open position)

Closing:

(1)  Insert the hexagon wrench into the 

valve shaft, and turn it clockwise.

(2)  Stop turning when the valve shaft can 

no longer be turned. (Closed position)

Opening 
direction

Hexagon wrench

Seal
 (blank 

cap 

installation 
portion)

Liquid 
pipe

Gas pipe

Opening 
direction

5.3.  Opening the knockout hole

 CAUTION

Be careful not to deform or scratch the panel while opening the knockout holes.

To protect the piping insulation after opening a knockout hole, remove any burrs from 
the edge of the hole. It is recommended to apply rust prevention paint to the edge of the 
hole.

• Pipes can be connected from 3 directions, front, lateral side and bottom. (Fig. A)
• When connecting at the bottom, remove the service panel and piping cover on the front 

of the outdoor unit, and open the knockout hole provided at the bottom corner of the 
piping outlet.

92

21

61

100

94

21

61

94

60 12

14

90

Unit: mm

Fig. A

Service panel

Top view of 
the base

Front connection

Lateral connection

Bottom connection

• It can be installed as shown on “Fig. B” cutting out the 2 slits as indicated on “Fig. C”. 

(When cutting slits, use a steel saw.)

Slit

Slit

Fig. B

Bottom 
connection

Fig. C

5.4. Pipe 

connection

 CAUTION

Do not use mineral oil on a flared part. Prevent mineral oil from getting into the system 
as this would reduce the lifetime of the units.

While brazing the pipes, be sure to blow dry nitrogen gas through them.

The maximum lengths of this product are shown in the table. If the units are further 
apart than this, correct operation cannot be guaranteed.

5.4.1 Bending pipes

 CAUTION

To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of 
curvature of 4 in (100 mm) or more.

If the pipe is bent repeatedly at the same place, it will break.

• If pipes are shaped by hand, be careful not to collapse them.
• Do not bend the pipes at an angle of more than 90°.
• When pipes are repeatedly bent or stretched, the material will harden, making it difficult 

to bend or stretch them anymore.

• Do not bend or stretch the pipes more than 3 times.

9380545248-02_IM.indb   7

9380545248-02_IM.indb   7

2018/1/24   9:36:31

2018/1/24   9:36:31

Summary of Contents for AIRSTAGE AJH126LELAH

Page 1: ...Й МОДУЛЬ For authorized service personnel only Только для авторизованного обслуживающего персонала PART No 9380545248 02 AJY126LELAH AJY144LELAH AJH126LELAH AJH144LELAH Original instructions 9380545248 02_IM indb i 9380545248 02_IM indb i 2018 1 24 9 36 29 2018 1 24 9 36 29 ...

Page 2: ...stall the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation make sure there is no refrig...

Page 3: ... near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the power 12 hours or earlier before operation begins When the energizing time is short it may cause failure Be sides please do not turn off pow...

Page 4: ... 1 meter away from a television or radio The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping 3 2 Drain processing CAUTION Perform ...

Page 5: ... more 500 or more 600 or more 1500 or more 3000 or more 3 4 Transporting the unit WARNING Do not touch the fins Otherwise personal injury could result CAUTION When carrying the unit hold the handles on the right and left sides and be careful If the outdoor unit is carried from the bottom hands or fingers may be pinched Hoisting method When hoisting the outdoor unit hook the rope on the outside of ...

Page 6: ...ordance with local rules 1 Allowable tensile stress 33 N mm2 2 Allowable tensile stress 61 N mm2 3 Endurance pressure of the pipes 4 2MPa 3 5 Installing the unit Please install the outdoor unit without slant within 0 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base su...

Page 7: ...n 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 5 PIPE INSTALLATION 5 1 Brazing CAUTION If air or another type of refrigerant enters the refrigera tion cycle the internal pressure in the refrigeration cycle will beco...

Page 8: ...Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclock wise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening direction Hexagon wrench Seal blank cap installation portion Liquid pipe Gas...

Page 9: ...ot exposed to high temperatures If the temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself...

Page 10: ...door unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 NOTES Do not use loop wiring This may lead to parts damage and erroneous operation 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enable automatic address...

Page 11: ...e shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent short circuit Use one side of the twisted pair cable Connect both ends of shielded wire to earth Ground 6 6 Externa...

Page 12: ...heater Output signal ON when the outdoor temperature goes down below 2 C and signal OFF at the outdoor temperature 4 C Voltage power supply input voltage cable 0 82 mm2 18AWG P C B Base heater 9 CN115 Black 8 8 Connect to pin 1 and pin 3 No connection pin 2 and pin 4 9 The allowable current is 1 A or less 7 FIELD SETTING CAUTION Discharge the static electricity from your body before setting up the...

Page 13: ... 9999 7 3 Rotary switch setting The rotary switch REF AD sets the refrigerant circuit address of the outdoor unit Config ure the settings only on the master unit of a refrigerant system If multiple refrigerant systems are connected set the rotary switch REF AD as shown in the table below Refrigerant circuit address Rotary Switch Setting Setting Setting range Type of switch REF AD 10 1 Refrigerant ...

Page 14: ...r unit on the network Refer to Fig Wiring example for automatic address setting 7 6 1 chapter for the wiring example For manual setting of address refer to the signal amplifier installation manual 7 5 2 Automatic address setting for signal amplifiers When setting the address of the signal amplifier please use the factory setting See the installation manual of the signal amplifier When the system i...

Page 15: ... to 101 kgf cm 18 0 to 22 0 N m 184 to 224 kgf cm 11 4 to 14 0 N m 116 to 143 kgf cm Gas valve 27 0 to 33 0 N m 275 to 337 kgf cm 22 5 to 27 5 N m 229 to 280 kgf cm 8 1 Sealing test CAUTION Use only nitrogen gas Never use refrigerant gas oxygen in flammable gas or poisonous gas to pressurize the system If oxygen is used there is the danger of an explosion Do not apply shock during sealing test It ...

Page 16: ... values specified in the Table A To open and close the valves use a specified hexagon wrench 8 3 2 Checking total amount of refrigerant and calculating the amount of refrigerant charge to be added The amount of refrigerant charge to be added is the total value of the basic refrigerant charge amount and the value calculated from the length of the liquid pipe Round up the value to 2 decimal places M...

Page 17: ...acity error E221 and Indoor unit duplicate address error E261 occurred 1 When the address of the overlap indoor unit is displayed press and hold the ENTER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SELECT but ton to switch to the next error If error occurs it will display Ad address number 9 2 Pre check for test run Before the test op...

Page 18: ... action E 9 8 9 Outdoor unit fan motor 2 driver error E 9 A 1 Outdoor unit coil 1 expansion valve 1 error E 9 A 2 Outdoor unit coil 2 expansion valve 2 error Refrigerant system error E A 1 1 Outdoor unit discharge temperature 1 error perma nent stop E A 3 1 Outdoor unit compressor 1 temperature error E A 4 1 Outdoor unit high pressure error E A 4 2 Outdoor unit high pressure protective action 1 E ...

Page 19: ...g condition refer to item 15 8 Max Current Maximum electric current Test condition IEC60335 2 40 9 Refrigerant Refrigerant type and initial charging amount 10 Max pressure HP LP Means pressure of High Pressure side Low Pres sure side 11 Protection Protection level against dust and water 12 Condition of cooling heating Dry bulb temperature and wet bulb temperature under standard cooling heating con...

Reviews: