En-13

(1)  Turn on the power of the outdoor unit and enter standby mode.
• When system is normal 

POWER/MODE lamp lights up. (ER-
ROR lamp is off.)

• When system is abnormal 

Check the settings as there is an error in the 
settings for outdoor unit address 
(DIP switch SET 3-1, 2) or number of con-
nected slave units (DIP switch SET 3-3, 4).

MODE
/NEXT

SELECT ENTER

POWER

MODE

ERROR

POWER/MODE 
lamp: ON

ERROR 
lamp: OFF

SELECT button

ENTER button

MODE/EXIT button

7 segment 
display: off

MODE
/NEXT

SELECT ENTER

POWER

MODE

ERROR

POWER/MODE 
lamp: ON

7 segment display: 
“-” display

ERROR lamp: 
Blinking

(2) Setting 

method

Use the “MODE/EXIT”, “SELECT”, 
and “ENTER” buttons to configure 
settings according to the proce-
dures below.
(If no setting is made, the factory 
default setting will be displayed.)

: Press the “MODE/EXIT” button

: Press the “SELECT” button

: Press the “ENTER” button.
: Press the “ENTER” button for 

more than 3 seconds.

1: Function setting

7 segment LED display (LED 105, LED 104)

(Flashing)

First 2 digits Last 2 digits

(When [F3] to [F9] are displayed, continue to press 
the “SELECT” button until [F2] is displayed.)

2:  Setting the first 

2 digits

3: Setting the last 2 digits

Continue to press the “SELECT” button until the 
desired number appears at the last 2 digits.

Every press of the 
“SELECT” button will 
change the setting 
number for the first 2 
digits.

(Continue to press the “SE-
LECT” button until the desired 
number appears at the last 2 
digits.)

Setting is complete when the lamp lights up

Press “ENTER” button to return to “2. Setting the 
first 2 digits” (If there is no operation for 5 seconds 
after the setting, the display will return to “2: Setting 
the first 2 digits”.)

Setting is complete when the lamp lights up

Press “ENTER” button to return to “2. Setting the 
first 2 digits” (If there is no operation for 5 seconds 
after the setting, the display will return to “2: Setting 
the first 2 digits”.)

EXIT: Press the “MODE/EXIT” button to cancel the setting mode.

7.5.  Address setting for signal ampli

fi

 ers

7.5.1  Address setting for signal ampli

fi

 ers

When using signal amplifiers, the address for signal amplifiers must be set.
The address for signal amplifiers can be set automatically from 1 outdoor unit (master 
unit) on the network.
Refer to “Fig. Wiring example for automatic address setting” (7.6.1 chapter) for the wiring 
example.
(For manual setting of address, refer to the signal amplifier installation manual.)

7.5.2  Automatic address setting for signal ampli

fi

 ers

When setting the address of the signal amplifier, please use the factory setting. (See the 
installation manual of the signal amplifier)
• When the system is normal, nothing will be displayed on the 7 segment display.
• When ERROR is displayed, inspect the units.
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit PC board to 
configure settings according to the procedures below.

1: Function setting

First 2 digits Last 2 digits

(the display when the main power is turned on)

Set to Function mode [F3].
(When [F4] to [F9] are displayed, continue to press 
the “SELECT” button until [F3] is displayed.)

Automatic address setting for 
signal amplifiers

Press the “SELECT” button until “10” is displayed.

Press the “ENTER” button for more than 3 seconds.

Setting is complete when the number of units is displayed

End

7.6.  Indoor unit address setting

7.6.1  Indoor unit address setting

Address must be set for the indoor unit.

Manual setting

• When setting with the switch inside the indoor unit, refer to 

the indoor unit operating manual.

• When setting with a remote control, refer to the remote 

control operating manual.

Automatic setting

• Check that the wiring is as shown in the figure below. 

Operate using the outdoor master unit of each refrigerant 
system.

Wiring example for automatic address setting

(1): Signal amplifier wiring example
(2)(3)(4): Indoor unit wiring example
(Connect the indoor and outdoor units of the same refrigerant system as shown below.)

Refrigerant system 1

Refrigerant system 2

Refrigerant system 3

Master unit

Master unit

Master unit

Signal amplifier

Signal amplifier

NOTES:

• The automatic address function can be used for a maximum of 9 indoor units installed to 

the same refrigerant system. When network is connected to other refrigerant systems, 
the automatic address function cannot be used.

• The addresses of indoor units that have been configured automatically cannot be as-

signed in the order when they are installed. (Refer to the indoor unit installation manual 
for the procedures to check the addresses.)

9380545248-02_IM.indb   13

9380545248-02_IM.indb   13

2018/1/24   9:36:33

2018/1/24   9:36:33

Summary of Contents for AIRSTAGE AJH126LELAH

Page 1: ...Й МОДУЛЬ For authorized service personnel only Только для авторизованного обслуживающего персонала PART No 9380545248 02 AJY126LELAH AJY144LELAH AJH126LELAH AJH144LELAH Original instructions 9380545248 02_IM indb i 9380545248 02_IM indb i 2018 1 24 9 36 29 2018 1 24 9 36 29 ...

Page 2: ...stall the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation make sure there is no refrig...

Page 3: ... near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the power 12 hours or earlier before operation begins When the energizing time is short it may cause failure Be sides please do not turn off pow...

Page 4: ... 1 meter away from a television or radio The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping 3 2 Drain processing CAUTION Perform ...

Page 5: ... more 500 or more 600 or more 1500 or more 3000 or more 3 4 Transporting the unit WARNING Do not touch the fins Otherwise personal injury could result CAUTION When carrying the unit hold the handles on the right and left sides and be careful If the outdoor unit is carried from the bottom hands or fingers may be pinched Hoisting method When hoisting the outdoor unit hook the rope on the outside of ...

Page 6: ...ordance with local rules 1 Allowable tensile stress 33 N mm2 2 Allowable tensile stress 61 N mm2 3 Endurance pressure of the pipes 4 2MPa 3 5 Installing the unit Please install the outdoor unit without slant within 0 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base su...

Page 7: ...n 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 5 PIPE INSTALLATION 5 1 Brazing CAUTION If air or another type of refrigerant enters the refrigera tion cycle the internal pressure in the refrigeration cycle will beco...

Page 8: ...Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclock wise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening direction Hexagon wrench Seal blank cap installation portion Liquid pipe Gas...

Page 9: ...ot exposed to high temperatures If the temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself...

Page 10: ...door unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 NOTES Do not use loop wiring This may lead to parts damage and erroneous operation 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enable automatic address...

Page 11: ...e shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent short circuit Use one side of the twisted pair cable Connect both ends of shielded wire to earth Ground 6 6 Externa...

Page 12: ...heater Output signal ON when the outdoor temperature goes down below 2 C and signal OFF at the outdoor temperature 4 C Voltage power supply input voltage cable 0 82 mm2 18AWG P C B Base heater 9 CN115 Black 8 8 Connect to pin 1 and pin 3 No connection pin 2 and pin 4 9 The allowable current is 1 A or less 7 FIELD SETTING CAUTION Discharge the static electricity from your body before setting up the...

Page 13: ... 9999 7 3 Rotary switch setting The rotary switch REF AD sets the refrigerant circuit address of the outdoor unit Config ure the settings only on the master unit of a refrigerant system If multiple refrigerant systems are connected set the rotary switch REF AD as shown in the table below Refrigerant circuit address Rotary Switch Setting Setting Setting range Type of switch REF AD 10 1 Refrigerant ...

Page 14: ...r unit on the network Refer to Fig Wiring example for automatic address setting 7 6 1 chapter for the wiring example For manual setting of address refer to the signal amplifier installation manual 7 5 2 Automatic address setting for signal amplifiers When setting the address of the signal amplifier please use the factory setting See the installation manual of the signal amplifier When the system i...

Page 15: ... to 101 kgf cm 18 0 to 22 0 N m 184 to 224 kgf cm 11 4 to 14 0 N m 116 to 143 kgf cm Gas valve 27 0 to 33 0 N m 275 to 337 kgf cm 22 5 to 27 5 N m 229 to 280 kgf cm 8 1 Sealing test CAUTION Use only nitrogen gas Never use refrigerant gas oxygen in flammable gas or poisonous gas to pressurize the system If oxygen is used there is the danger of an explosion Do not apply shock during sealing test It ...

Page 16: ... values specified in the Table A To open and close the valves use a specified hexagon wrench 8 3 2 Checking total amount of refrigerant and calculating the amount of refrigerant charge to be added The amount of refrigerant charge to be added is the total value of the basic refrigerant charge amount and the value calculated from the length of the liquid pipe Round up the value to 2 decimal places M...

Page 17: ...acity error E221 and Indoor unit duplicate address error E261 occurred 1 When the address of the overlap indoor unit is displayed press and hold the ENTER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SELECT but ton to switch to the next error If error occurs it will display Ad address number 9 2 Pre check for test run Before the test op...

Page 18: ... action E 9 8 9 Outdoor unit fan motor 2 driver error E 9 A 1 Outdoor unit coil 1 expansion valve 1 error E 9 A 2 Outdoor unit coil 2 expansion valve 2 error Refrigerant system error E A 1 1 Outdoor unit discharge temperature 1 error perma nent stop E A 3 1 Outdoor unit compressor 1 temperature error E A 4 1 Outdoor unit high pressure error E A 4 2 Outdoor unit high pressure protective action 1 E ...

Page 19: ...g condition refer to item 15 8 Max Current Maximum electric current Test condition IEC60335 2 40 9 Refrigerant Refrigerant type and initial charging amount 10 Max pressure HP LP Means pressure of High Pressure side Low Pres sure side 11 Protection Protection level against dust and water 12 Condition of cooling heating Dry bulb temperature and wet bulb temperature under standard cooling heating con...

Reviews: