background image

En-16

9. TEST 

RUN

9.1.  Indoor unit connection check

Normal operation will not be possible without performing the Indoor unit connection check.

9.1.1  Things to con

fi

 rm before starting the Indoor unit connection 

check

To ensure safety, check that the following work, inspections and operations have been 
completed.

Check Item

Check Column

1

Check that all work on the wiring connecting the outdoor 
unit and indoor units  has been completed.

2

Is a breaker installed at the power supply cable of out-
door unit and every indoor units?

3

Are the cables connected to the terminals without loose-
ness, and in accordance with the specifications?

4

Are all the indoor units stopped? Indoor unit connection 
check cannot be performed if any unit is operating.

5

Is the connection to Service tool (UTY-ASGX) and Web 
monitoring tool (UTY-AMGX) stopped?

9.1.2  Operating procedure for Indoor unit connection check

Please perform the indoor unit connection check according to following procedures.
The Indoor unit connection check can be completed within several minutes.

Set to Function mode [F3].

(When [F4] to [F9] are displayed, continue to press 
the “SELECT” button until [F3] is displayed.)

Press the “SELECT” button until “12” is displayed.

When indoor unit connection 
check cannot be performed

Turn on the power of indoor 
unit and outdoor unit.

Press the “ENTER” button for more than 3 seconds.

This will be displayed when the Indoor unit connection 
check starts.

: Press the “MODE/EXIT” button

: Press the “SELECT” button

: Press the “ENTER” button.
: Press the “ENTER” button for 

more than 3 seconds.

(*1) The number of connected indoor units

Ex.) When 8 units are connected

(*2) Volume ratio of the indoor units connection

Ex.) When the ratio is 120%

Please refer to the following “Error displays” 
for details.

When it finishes normally, nothing will be displayed on 
7 segment display. 

When error occurs

Confirm the number of connected indoor units and the 
volume ratio of the indoor units connection.

Exit indoor unit connection check mode.

9.1.3 Error displays

• When error occurs, “Err” and “Number of errors occurred” are alternately displayed on 

the 7 segment display every 1 second.

• For the content of error, please refer to the “10.2.Error codes”.
• When error codes are displayed, all the error codes can be confirmed by pressing the 

“SELECT” button.

Example:

When “Indoor unit capacity error [E221]” and “Indoor unit duplicate address error [E261]” 
occurred.

(*1)  When the address of the overlap indoor unit is 

displayed, press and hold the “ENTER” button 
for more than 3 seconds.

(*2)  When errors other than the address of the 

overlap indoor unit exist, press “SELECT” but-
ton to switch to the next error.

If error occurs, it will display “-”.

[Ad + address number]

9.2.  Pre-check for test run

Before the test operation, check the following items.
(1)  Is there a gas leakage? (At pipe connections {flange connections and brazed areas})
(2)  Is the system charged with the specified volume of refrigerant?
(3)  Is the refrigerant circuit address correct?
(4)  Is a breaker installed at the power supply cable of outdoor unit?
(5)  Are the cable connected to the terminals without looseness, and in accordance with 

the specifications?

(6)  Are the initial settings of the switches of the outdoor unit correctly configured?
(7)  Is the 3-way valve of the outdoor unit open? (Gas pipe and liquid pipe)
(8)  Is power supplied to the crank case heater for more than 12 hours? Electricity current 

in short period of time may result in compressor damage.

(9)  Are all the indoor units within the same coolant system connected to the power? Op-

erating indoor units which are not connected to the power may result in malfunctions.

(10)  Is Indoor unit connection check performed? Test run doesn't operate if Indoor unit 

connection check is not performed.

After checking that the above items are all in order, refer to 
“9.3.Test run method” to test operation the unit.
If there are problems, adjust immediately and recheck.

9.3.  

Test run method

Be sure to configure test run settings only when the outdoor unit has stopped operating.

• Depending on the communication status between the indoor and outdoor units, it may 

take several minutes for the system to start operating after settings for the test run are 
complete.

• After the test run settings are complete, the outdoor unit and the connected indoor 

units will start operating. Room temperature control will not activate during test opera-
tion (continuous operation).

• If a knocking sound can be heard in the liquid compression of the compressor, stop 

the unit immediately and then energize the crank case heater for a sufficient length of 
time before restarting the operation.

Perform test operation for each refrigerant system.
You can set “cooling test operation" or “heating test operation” with the push button on the 
outdoor unit PC board.

9380545248-02_IM.indb   16

9380545248-02_IM.indb   16

2018/1/24   9:36:33

2018/1/24   9:36:33

Summary of Contents for AIRSTAGE AJH126LELAH

Page 1: ...Й МОДУЛЬ For authorized service personnel only Только для авторизованного обслуживающего персонала PART No 9380545248 02 AJY126LELAH AJY144LELAH AJH126LELAH AJH144LELAH Original instructions 9380545248 02_IM indb i 9380545248 02_IM indb i 2018 1 24 9 36 29 2018 1 24 9 36 29 ...

Page 2: ...stall the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation make sure there is no refrig...

Page 3: ... near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the power 12 hours or earlier before operation begins When the energizing time is short it may cause failure Be sides please do not turn off pow...

Page 4: ... 1 meter away from a television or radio The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping 3 2 Drain processing CAUTION Perform ...

Page 5: ... more 500 or more 600 or more 1500 or more 3000 or more 3 4 Transporting the unit WARNING Do not touch the fins Otherwise personal injury could result CAUTION When carrying the unit hold the handles on the right and left sides and be careful If the outdoor unit is carried from the bottom hands or fingers may be pinched Hoisting method When hoisting the outdoor unit hook the rope on the outside of ...

Page 6: ...ordance with local rules 1 Allowable tensile stress 33 N mm2 2 Allowable tensile stress 61 N mm2 3 Endurance pressure of the pipes 4 2MPa 3 5 Installing the unit Please install the outdoor unit without slant within 0 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base su...

Page 7: ...n 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 5 PIPE INSTALLATION 5 1 Brazing CAUTION If air or another type of refrigerant enters the refrigera tion cycle the internal pressure in the refrigeration cycle will beco...

Page 8: ...Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclock wise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening direction Hexagon wrench Seal blank cap installation portion Liquid pipe Gas...

Page 9: ...ot exposed to high temperatures If the temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself...

Page 10: ...door unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 NOTES Do not use loop wiring This may lead to parts damage and erroneous operation 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enable automatic address...

Page 11: ...e shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent short circuit Use one side of the twisted pair cable Connect both ends of shielded wire to earth Ground 6 6 Externa...

Page 12: ...heater Output signal ON when the outdoor temperature goes down below 2 C and signal OFF at the outdoor temperature 4 C Voltage power supply input voltage cable 0 82 mm2 18AWG P C B Base heater 9 CN115 Black 8 8 Connect to pin 1 and pin 3 No connection pin 2 and pin 4 9 The allowable current is 1 A or less 7 FIELD SETTING CAUTION Discharge the static electricity from your body before setting up the...

Page 13: ... 9999 7 3 Rotary switch setting The rotary switch REF AD sets the refrigerant circuit address of the outdoor unit Config ure the settings only on the master unit of a refrigerant system If multiple refrigerant systems are connected set the rotary switch REF AD as shown in the table below Refrigerant circuit address Rotary Switch Setting Setting Setting range Type of switch REF AD 10 1 Refrigerant ...

Page 14: ...r unit on the network Refer to Fig Wiring example for automatic address setting 7 6 1 chapter for the wiring example For manual setting of address refer to the signal amplifier installation manual 7 5 2 Automatic address setting for signal amplifiers When setting the address of the signal amplifier please use the factory setting See the installation manual of the signal amplifier When the system i...

Page 15: ... to 101 kgf cm 18 0 to 22 0 N m 184 to 224 kgf cm 11 4 to 14 0 N m 116 to 143 kgf cm Gas valve 27 0 to 33 0 N m 275 to 337 kgf cm 22 5 to 27 5 N m 229 to 280 kgf cm 8 1 Sealing test CAUTION Use only nitrogen gas Never use refrigerant gas oxygen in flammable gas or poisonous gas to pressurize the system If oxygen is used there is the danger of an explosion Do not apply shock during sealing test It ...

Page 16: ... values specified in the Table A To open and close the valves use a specified hexagon wrench 8 3 2 Checking total amount of refrigerant and calculating the amount of refrigerant charge to be added The amount of refrigerant charge to be added is the total value of the basic refrigerant charge amount and the value calculated from the length of the liquid pipe Round up the value to 2 decimal places M...

Page 17: ...acity error E221 and Indoor unit duplicate address error E261 occurred 1 When the address of the overlap indoor unit is displayed press and hold the ENTER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SELECT but ton to switch to the next error If error occurs it will display Ad address number 9 2 Pre check for test run Before the test op...

Page 18: ... action E 9 8 9 Outdoor unit fan motor 2 driver error E 9 A 1 Outdoor unit coil 1 expansion valve 1 error E 9 A 2 Outdoor unit coil 2 expansion valve 2 error Refrigerant system error E A 1 1 Outdoor unit discharge temperature 1 error perma nent stop E A 3 1 Outdoor unit compressor 1 temperature error E A 4 1 Outdoor unit high pressure error E A 4 2 Outdoor unit high pressure protective action 1 E ...

Page 19: ...g condition refer to item 15 8 Max Current Maximum electric current Test condition IEC60335 2 40 9 Refrigerant Refrigerant type and initial charging amount 10 Max pressure HP LP Means pressure of High Pressure side Low Pres sure side 11 Protection Protection level against dust and water 12 Condition of cooling heating Dry bulb temperature and wet bulb temperature under standard cooling heating con...

Reviews: