Fujitsu AIRSTAGE AJH126LELAH Installation Manual Download Page 11

En-10

6.5.2 Wiring procedure

• Remove the service panel. And connect the cable to the terminal in accordance with the 

terminal name plate.

• Use a ring terminal to connect the electric cables to the power supply terminal board.
• Keep the earth cable longer than the other cables.
• After connecting the electric cable, secure them with a cable clamp.
• Connect the cable without applying excessive tension.
• Use the specified cable type and connect the cable securely.

Secure with a cable 
clamp as shown in the 
figure below.

Tightening 

torque

M3 screw

0.5 to 0.6 N·m (5 to 6 kgf·cm)

M5 screw 

2.0 to 3.0 N·m (20 to 30 kgf·cm)

Power supply terminal

Ring terminal (M5)

Transmission terminal (M3)

Power supply cable

Power supply 
cable

Transmission cable

Transmission cable

Push mount 
cable tie 
(accessory)

Push mount 
cable tie 
(accessory)

Cable clamp

Cable tie

Earth (ground) 
cable

8 to 10 mm

55 to 60 mm

25 to 

40 mm

35 to 

40 mm

How to connect wiring to the terminal

Caution when wiring cable
(1)  Use ring terminals with insulating sleeves as shown in the figure to connect to the 

terminal block.

(2)  Securely clamp the ring terminals to the cables using an appropriate tool so that 

the cables do not come loose.

(3)  Use the specified cables, connect them securely, and fasten them so that there is 

no stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-

driver that is too small, otherwise, the screw heads may be damaged and prevent 
the screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(6)  See the table below for the terminal screw tightening torques.

Strip 3/8 in 

(10 mm)

Cable

Screw with 
special washer

Ring terminal

Terminal block

Ring terminal

Sleeve

Screw with 
special washer

Ring terminal

Cable

Shielding the transmission cable

Connect both ends of the shielded 
wire of the transmission cable to 
the earth (ground) terminal of the 
equipment or to the earth (ground) 
screw near the terminal.
Be sure to use one side of a 
twisted-pair cable when using 
transmission cable with 2 sets of 
twisted-pair cables.

Wind with insulation tape to prevent short circuit

Use one side 
of the twisted-
pair cable

Connect both ends of shielded 
wire to earth (Ground).

6.6.  External input and external output

6.6.1 Terminal position

CN136 BLK

EXT. OUT. 1

CN137  BLU

EXT. OUT. 2

CN131

YEL

CN132 GRN

CN134    RED

CN133 WHT

CN135

ORG

EXT.  IN. 1

PLUSE.  IN

EXT.  IN. 4

EXT.  IN. 2

EXT.  IN. 3

CN115    BLK

BASE HEATER

Base heater
(CN115: Black)

Outdoor unit PC board

Input 4
(CN134: Red)

Input 3
(CN133: White)

Input 2
(CN132: Green)

Input 1
(CN131: Yellow)

Input 5 (CN135: Orange)

Output 1 (CN136: Black)

Output 2
(CN137: Blue)

 CAUTION

Do not bundle the cable for base heater with other cables.

When connecting 
cable to Input 2

Cable (for external 
input and output)

Push mount cable tie (accessory)
(tightened with transmission cable)

Push mount cable tie 
(accessory) (tightened 
with transmission 
cable)

Cable (for external input and output)
*  If the outdoor unit is not installed in the wall, cover the exposed 

part of cable with a 1 mm thick or more insulation tubing.

6.6.2  External input terminal

Setting to low noise mode, cooling priority/heating priority selection, outdoor unit operation 
peak control setting, emergency/batch stop and electricity meter pulse are possible from 
the outside.

Wiring method and specifications

*  A twisted pair cable (22 AWG (0.33 mm²)) should be used. Maximum length of cable is 

150 m.

*  Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed

*  For each input, pin No. 1 is of positive polarity and pin No. 2 is of ground level.

Connected unit Connected unit Connected unit Connected unit Connected unit

Input 1
CN131 
(Yellow)

Input 2
CN132 
(Green)

Input 3
CN133 
(White)

Input 4
CN134 
(Red)

Input 5
CN135 
(Orange)

P.C.B

9380545248-02_IM.indb   10

9380545248-02_IM.indb   10

2018/1/24   9:36:32

2018/1/24   9:36:32

Summary of Contents for AIRSTAGE AJH126LELAH

Page 1: ...Й МОДУЛЬ For authorized service personnel only Только для авторизованного обслуживающего персонала PART No 9380545248 02 AJY126LELAH AJY144LELAH AJH126LELAH AJH144LELAH Original instructions 9380545248 02_IM indb i 9380545248 02_IM indb i 2018 1 24 9 36 29 2018 1 24 9 36 29 ...

Page 2: ...stall the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation make sure there is no refrig...

Page 3: ... near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the power 12 hours or earlier before operation begins When the energizing time is short it may cause failure Be sides please do not turn off pow...

Page 4: ... 1 meter away from a television or radio The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping 3 2 Drain processing CAUTION Perform ...

Page 5: ... more 500 or more 600 or more 1500 or more 3000 or more 3 4 Transporting the unit WARNING Do not touch the fins Otherwise personal injury could result CAUTION When carrying the unit hold the handles on the right and left sides and be careful If the outdoor unit is carried from the bottom hands or fingers may be pinched Hoisting method When hoisting the outdoor unit hook the rope on the outside of ...

Page 6: ...ordance with local rules 1 Allowable tensile stress 33 N mm2 2 Allowable tensile stress 61 N mm2 3 Endurance pressure of the pipes 4 2MPa 3 5 Installing the unit Please install the outdoor unit without slant within 0 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base su...

Page 7: ...n 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of moisture and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit 5 PIPE INSTALLATION 5 1 Brazing CAUTION If air or another type of refrigerant enters the refrigera tion cycle the internal pressure in the refrigeration cycle will beco...

Page 8: ...Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclock wise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening direction Hexagon wrench Seal blank cap installation portion Liquid pipe Gas...

Page 9: ...ot exposed to high temperatures If the temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself...

Page 10: ...door unit Indoor unit Signal Amplifier System Controller Touch Panel Controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 NOTES Do not use loop wiring This may lead to parts damage and erroneous operation 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enable automatic address...

Page 11: ...e shielded wire of the transmission cable to the earth ground terminal of the equipment or to the earth ground screw near the terminal Be sure to use one side of a twisted pair cable when using transmission cable with 2 sets of twisted pair cables Wind with insulation tape to prevent short circuit Use one side of the twisted pair cable Connect both ends of shielded wire to earth Ground 6 6 Externa...

Page 12: ...heater Output signal ON when the outdoor temperature goes down below 2 C and signal OFF at the outdoor temperature 4 C Voltage power supply input voltage cable 0 82 mm2 18AWG P C B Base heater 9 CN115 Black 8 8 Connect to pin 1 and pin 3 No connection pin 2 and pin 4 9 The allowable current is 1 A or less 7 FIELD SETTING CAUTION Discharge the static electricity from your body before setting up the...

Page 13: ... 9999 7 3 Rotary switch setting The rotary switch REF AD sets the refrigerant circuit address of the outdoor unit Config ure the settings only on the master unit of a refrigerant system If multiple refrigerant systems are connected set the rotary switch REF AD as shown in the table below Refrigerant circuit address Rotary Switch Setting Setting Setting range Type of switch REF AD 10 1 Refrigerant ...

Page 14: ...r unit on the network Refer to Fig Wiring example for automatic address setting 7 6 1 chapter for the wiring example For manual setting of address refer to the signal amplifier installation manual 7 5 2 Automatic address setting for signal amplifiers When setting the address of the signal amplifier please use the factory setting See the installation manual of the signal amplifier When the system i...

Page 15: ... to 101 kgf cm 18 0 to 22 0 N m 184 to 224 kgf cm 11 4 to 14 0 N m 116 to 143 kgf cm Gas valve 27 0 to 33 0 N m 275 to 337 kgf cm 22 5 to 27 5 N m 229 to 280 kgf cm 8 1 Sealing test CAUTION Use only nitrogen gas Never use refrigerant gas oxygen in flammable gas or poisonous gas to pressurize the system If oxygen is used there is the danger of an explosion Do not apply shock during sealing test It ...

Page 16: ... values specified in the Table A To open and close the valves use a specified hexagon wrench 8 3 2 Checking total amount of refrigerant and calculating the amount of refrigerant charge to be added The amount of refrigerant charge to be added is the total value of the basic refrigerant charge amount and the value calculated from the length of the liquid pipe Round up the value to 2 decimal places M...

Page 17: ...acity error E221 and Indoor unit duplicate address error E261 occurred 1 When the address of the overlap indoor unit is displayed press and hold the ENTER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SELECT but ton to switch to the next error If error occurs it will display Ad address number 9 2 Pre check for test run Before the test op...

Page 18: ... action E 9 8 9 Outdoor unit fan motor 2 driver error E 9 A 1 Outdoor unit coil 1 expansion valve 1 error E 9 A 2 Outdoor unit coil 2 expansion valve 2 error Refrigerant system error E A 1 1 Outdoor unit discharge temperature 1 error perma nent stop E A 3 1 Outdoor unit compressor 1 temperature error E A 4 1 Outdoor unit high pressure error E A 4 2 Outdoor unit high pressure protective action 1 E ...

Page 19: ...g condition refer to item 15 8 Max Current Maximum electric current Test condition IEC60335 2 40 9 Refrigerant Refrigerant type and initial charging amount 10 Max pressure HP LP Means pressure of High Pressure side Low Pres sure side 11 Protection Protection level against dust and water 12 Condition of cooling heating Dry bulb temperature and wet bulb temperature under standard cooling heating con...

Reviews: