En-3

2.4. Combinations

The number of indoor units that can be connected are as follows:

Model

Outdoor unit cooling 

capacity [kW]

Maximum connect-

able indoor units

Connectable total 

indoor unit capacity 

ratio [%]

AJ*072LELBH

22.4

20

50 to 150 (*1)

AJ*090LELBH

28.0

25

AJ*108LELBH

33.5

30

AJ*126LELBH

40.0

36

AJ*144LELBH

45.0

40

AJ*162LELBH

50.0

42

*1:  The conditions may differ depending on the connected indoor unit. For detailed infor-

mation, refer to the Design and Technical Manual.

2.5. Optional 

parts

 CAUTION

The following parts are optional parts specific to R410A refrigerant.
Do not use parts other than those listed below.

2.5.1  Separation tube kit and Header

Separation tube 
and header uses 
the following parts. 
A header is used 
for connecting the 
indoor units.

Total cooling ca-

pacity of indoor 

unit (kw)

Separation 

tube

Header

3-6 Branches

3-8 Branches

19.6 or less

UTP-AX054A

UTR-H0906L

UTR-H0908L

28.0 or less

UTP-AX090A

28.1 or more

UTP-AX180A UTR-H1806L

UTR-H1808L

2.5.2  External connect kit

Model

Usage

UTY-XWZXZ6

For External input (CN131, CN132, CN133, CN134)

For External output (Error status / CN136) (Operation status / CN137)

UTY-XWZXZF

For External input (CN135)

UTY-XWZXZ9

For External output (Base heater / CN115)

3. INSTALLATION 

WORK

Please obtain the approval of the customer when selecting the location of installation and 
installing the main unit.

3.1.  Selecting an installation location

 WARNING

Install the unit in a location that can withstand its weight, and where it will not topple or 
fall.

Calculate the proper refrigerant concentration if you will be installing it in an enclosed 
location.

Total amount of replenished refrigerant 
in refrigerant facility (kg)

Refrigerant concentration (kg/m³) 
(0.42 kg/m³)

Capacity of smallest room where unit 

is installed (m³)

If the results of the calculation exceed the concentration limit, increase the room surface 
area or install a ventilation duct.

 CAUTION

Do not tilt the outdoor unit more than 0.3 degrees. However, do not install the unit with it 
tilted towards the side containing the compressor.

Install this unit in a location with good ventilation.

If the unit must be installed in an area within easy reach of the general public, install as 
necessary a protective fence or the like to prevent their access.

Install the unit in an area that would not inconvenience your neighbors, as they could be 
affected by the airflow coming out from the outlet, noise, or vibration.
If it must be installed in proximity to your neighbors, be sure to obtain their approval.

If the unit is installed in a cold region that is affected by snow accumulation, snow fall, or 
freezing, take appropriate measures to protect it from those elements. 
To ensure a stable operation, install inlet and outlet ducts.

Install the unit in an area that would not cause problems even if the drain water is 
discharged from the unit. Otherwise, provide drainage that would not affect people or 
objects.

Install the unit in an area that has no heat sources, vapors, or the risk of the leakage of 
flammable gas in the vicinity.

Install the unit in an area that is away from the exhaust or vent ports that discharge 
vapor, soot, dust, or debris.

Install the indoor unit, outdoor unit, power supply cable, transmission cable and remote 
control cable at least 1 meter away from a television or radio. 
The purpose of this is to prevent TV reception interference or radio noise. (Even if they 
are installed more than 1 meter apart, you could still receive noise under some signal 
conditions.)

Keep the length of the piping of the indoor and outdoor units within the allowable range.

For maintenance purposes, do not bury the piping.

3.2. Drain 

processing

 CAUTION

Perform drain work in accordance with this Manual, and ensure that the drain water is 
properly drained. If the drain work is not carried out correctly, water may drip down from 
the unit, wetting the furniture.

When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe 
and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may 
freeze in extremely cold weather.

• If you are installing the drain pipe and drain caps, 

please provide a working space under the base of 
the outdoor unit.

• As the drain water flows out of the outdoor unit 

during heating operation, install the drain pipe and 
connect it to a commercial 16 mm hose.

• When installing the drain pipe, plug all the holes 

other than the drain pipe mounting hole in the 
bottom of the outdoor unit with putty so there is no 
water leakage.

Base of the outdoor unit

Drain pipe

Drain pipe mounting hole

600

446

Air

Unit: mm

Drain cap mounting 
hole × 9

Drain pipe 
mounting hole

3.3. Installation 

dimensions

 CAUTION

Provide sufficient installation space, such as transportation route, maintenance space, 
ventilation space, refrigerant piping space, and passageways.

Pay attention to the specifications of the installation space as shown in the figure. If 
the unit is not installed according to specifications, it may cause short circuit or poor 
performance. The unit may be prone to lapse into non-operation due to high pressure 
protection.

When there is a wall in front of the unit, provide a space of 500 mm or more as mainte-
nance space.
When there is a wall at the right side of the unit, provide a space of 100 mm or more.

An outdoor temperature of 35°C (DB) in air-conditioned operation is assumed for the 
installation space in this item. If the outdoor temperature exceeds 35°C (DB) and the 
outdoor unit is operating at a load exceeding its rated ability, provide a larger inlet 
space.

If you are installing more outdoor units than indicated here, please ensure sufficient 
space or consult your distributing agent as it may affect the performance due to short 
circuit and other problems.

Consider the transportation route, installation space, maintenance space, and access, 
and install the unit in a location with sufficient space for the refrigerant piping.

Keep the space shown in the installation examples.
If the installation is not performed accordingly, it 
could cause a short circuit and result in a lack of 
operating performance.

Air intake

Rear

Front

Do not obstruct the air intake of the outdoor unit with 
piping, wiring, stand, etc.

Refer to the Design and Technical Manual for installations not described in the following 
examples. 
Other installation is not recommended. Performance may drop significantly.

9380545347-01_IM.indb   3

9380545347-01_IM.indb   3

11/29/2019   8:49:51 AM

11/29/2019   8:49:51 AM

Summary of Contents for AIRSTAGE AJ 072LELBH Series

Page 1: ...or authorized service personnel only Nur für autorisiertes Fachpersonal Pour le personnel de service agrée uniquement Únicamente para personal de servicio autorizado A uso esclusivo del personale tecnico autorizzato Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό Somente para o pessoal do serviço técnico autorizado Только для авторизованного обслуживающего персонала Yalnızca yetkili servis personeli iç...

Page 2: ...all the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation make sure there is no refriger...

Page 3: ... start or stop the operation of air conditioning with power breaker Other wise it may cause malfunction or water leakage When setting it up near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the p...

Page 4: ...por soot dust or debris Install the indoor unit outdoor unit power supply cable transmission cable and remote control cable at least 1 meter away from a television or radio The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoo...

Page 5: ... unit WARNING Do not touch the fins Otherwise personal injury could result CAUTION When carrying the unit hold the handles on the right and left sides and be careful If the outdoor unit is carried from the bottom hands or fingers may be pinched Hoisting method When hoisting the outdoor unit hook the rope on the outside of the foot as shown in the figure Use sufficiently strong rope to bear the uni...

Page 6: ... local rules 1 Allowable tensile stress 33 N mm2 2 Allowable tensile stress 61 N mm2 3 Endurance pressure of the pipes 4 2MPa 3 5 Installing the unit Please install the outdoor unit without slant within 0 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concre...

Page 7: ...090 96 096 Capacity kW 1 1 2 2 2 8 3 6 4 5 5 6 7 1 9 0 10 0 11 2 12 5 14 0 18 0 22 4 25 0 28 0 In the case of ARXD007GLEH equivalent to model code of indoor unit Model code 007 Capacity 2 2kW 4 3 Protection of pipes Location Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of...

Page 8: ... valves Use a hexagon wrench Liquid valve size 4 mm Gas valve size 8 mm Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclock wise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening dire...

Page 9: ...he temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself When the electrical switchboard is ...

Page 10: ...door unit Signal amplifier System controller Touch panel controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 NOTES Do not use loop wiring This may lead to parts damage and erroneous operation 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enable automatic address setting for...

Page 11: ...l 126 144 162 model 162 model How to connect wiring to the terminal Caution when wiring cable 1 Use ring terminals with insulating sleeves as shown in the figure to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no stress ...

Page 12: ...tton setting NOTES 1 The external input priority mode must be set by pressing push button on PC board of outdoor unit Refer to 7 FIELD SETTING 2 Batch stop or Emergency stop pattern can be selected by outdoor unit PC board push button Refer to 7 FIELD SETTING 3 The emergency stop function mounted in this model does not guarantee the regula tions of each country For this reason sufficient checking ...

Page 13: ...ressure 1 equivalent to 072 090 model 30 Pa 108 model 40 Pa 126 144 162 model 60 Pa 0 1 25 Prohibited Factory default 2 5 0 0 26 Prohibited Factory default 2 6 0 0 27 Prohibited Factory default 2 7 0 0 28 Prohibited Factory default 2 8 0 0 29 Prohibited Factory default 2 9 0 0 7 FIELD SETTING CAUTION Discharge the static electricity from your body before setting up the DIP switches Never touch the...

Page 14: ...ectricity meter No is set to 000 and 201 to 299 the pulses input to CN135 become ineffective Available setting number is 001 to 200 3 When the electricity meter pulse setting is set to 0000 the pulses input to CN135 become ineffective Available setting number is 0001 to 9999 4 This item is not displayed for 072 090 and 108 models 1 Turn on the power of the outdoor unit and enter standby mode When ...

Page 15: ...cedures to check the addresses 7 6 2 Procedures to enable automatic address setting on indoor units Check that the rotary switch IU AD on the indoor unit PC board is set to 00 If it is not set to 00 it means the address of that device is not set Factory default is 00 Turn on the power of the indoor and outdoor units When the system is normal nothing will be displayed on the 7 segment display When ...

Page 16: ...ocedure 1 Remove the blank caps of the gas pipe and liquid pipe and check that the valves are closed 2 Remove the charging port cap 3 Connect a vacuum pump and a pressure gauge to a charging hose and connect it to the charging port 4 Activate the vacuum pump and vacuum the indoor unit and connection piping until the pressure gauge becomes 100 7 kPa 755mm Hg Evacuate from both the gas pipe and the ...

Page 17: ... caused near electrical components in the service panel If the outdoor unit is installed at a level that is higher than the indoor unit the water that has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water to the indoor units 9 TEST RUN 9 1 Indoor unit connection check N...

Page 18: ...rror codes can be confirmed by pressing the SELECT button Example When Indoor unit capacity error E221 and Indoor unit duplicate address error E261 occurred 1 When the address of the overlap indoor unit is displayed press and hold the ENTER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SELECT but ton to switch to the next error If error ...

Page 19: ...ssor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 Outdoor unit compressor motor loss of synchroniza tion E 9 7 1 Outdoor unit fan motor 1 lock error E 9 7 4 Outdoor unit fan motor 1 undervoltage error E 9 7 5 Outdoor unit fan motor 1 temperature error protective action E 9 7 9 Outdoor unit fan motor 1 driver error E 9 8 1 Outdoor unit fan motor 2 lock error E 9 8 5 Outdoor unit fan m...

Reviews: