En-13
30
Energy saving
level setting (*1)
Level 1 (stop)
3
0
0
0
Level 2
(operated at 40% capacity)
0
1
Level 3
(operated at 60% capacity)
0
2
Level 4
(operated at 80% capacity)
0
3
Level 5
(operated at 100% capacity)
0
4
The capacity limit can be selected by the external input terminal (CN133) when
operating with the “Energy Saving Peak Cut function”.
The lower the level, the more the effect of energy saving, but the cooling/heating
performance will also drop.
31
Prohibited (Factory default)
3
1
0
0
40
Capacity priority
setting (in low
noise mode) (*1)
Off (quiet priority)
4
0
0
0
On (capacity priority)
0
1
If the cooling/heating performance becomes insufficient when the low noise mode
is set, it is possible to set “capacity priority” that automatically cancels the low
noise mode (once performance is restored, the mode will automatically return to
the low noise mode).
41
Low noise mode
setting (*1)
Off (Normal)
4
1
0
0
On (Low noise mode)
0
1
42
Low noise mode
level setting
Level 1
4
2
0
0
Level 2
0
1
Prohibited
0
2
52
Prohibited (Factory default) (*4)
5
2
0
0
53
Prohibited (Factory default)
5
3
0
0
60
Prohibited (Factory default)
6
0
0
0
70
Electricity meter
No. setting 1 (*2)
Setting number (x00)
7
0
0
0
Setting number (x01)
0
1
······
···
···
Setting number (x98)
9
8
Setting number (x99)
9
9
Set the ones digit and tens digit of the No. of the electricity meter connected to
CN135.
71
Electricity meter
No. setting 2 (*2)
Setting number (0xx)
7
1
0
0
Setting number (1xx)
0
1
Setting number (2xx)
0
2
Set the hundreds digit of the No. of the electricity meter connected to CN135.
72
Electricity meter
pulse setting
1 (*3)
Setting number (xx00)
7
2
0
0
Setting number (xx01)
0
1
······
···
···
Setting number (xx98)
9
8
Setting number (xx99)
9
9
Set the ones digit and tens digit of the No. of the electricity meter pulse setting
connected to CN135.
73
Electricity meter
pulse setting
2 (*3)
Setting number (00xx)
7
3
0
0
Setting number (01xx)
0
1
······
···
···
Setting number (98xx)
9
8
Setting number (99xx)
9
9
Set the hundreds digit and thousands digit of the electricity meter pulse setting
connected to CN135.
90
Prohibited (Factory default)
9
0
0
0
*1: Do not set this for outdoor units with Slave setting.
*2: When electricity meter No. is set to “000” and “201 to 299”, the pulses input to
CN135 become ineffective. Available setting number is "001" to "200"
*3: When the electricity meter pulse setting is set to “0000”, the pulses input to CN135
become ineffective. Available setting number is "0001" to "9999"
*4: This item is not displayed for 072, 090, and 108 models.
(1) Turn on the power of the outdoor unit and enter standby mode.
• When system is normal
POWER/MODE lamp lights up. (ER-
ROR lamp is off.)
• When system is abnormal
Check the settings as there is an error in the
settings for outdoor unit address
(DIP switch SET 3-1, 2) or number of con-
nected slave units (DIP switch SET 3-3, 4).
MODE
/NEXT
SELECT ENTER
POWER
MODE
ERROR
POWER/MODE
lamp: ON
ERROR
lamp: OFF
SELECT button
ENTER button
MODE/EXIT button
7-segment
display: off
MODE
/NEXT
SELECT ENTER
POWER
MODE
ERROR
POWER/MODE
lamp: ON
7-segment display:
“-” display
ERROR lamp:
Blinking
(2) Setting
method
Use the “MODE/EXIT”, “SELECT”,
and “ENTER” buttons to configure
settings according to the proce-
dures below.
(If no setting is made, the factory
default setting will be displayed.)
: Press the “MODE/EXIT” button
: Press the “SELECT” button
: Press the “ENTER” button.
: Press the “ENTER” button for
more than 3 seconds.
1: Function setting
7-segment LED display (LED 105, LED 104)
(Flashing)
First 2 digits Last 2 digits
(When [F3] to [F9] are displayed, continue to press
the “SELECT” button until [F2] is displayed.)
2: Setting the first
2 digits
3: Setting the last 2 digits
Continue to press the “SELECT” button until the
desired number appears at the last 2 digits.
Every press of the
“SELECT” button will
change the setting
number for the first 2
digits.
(Continue to press the “SE-
LECT” button until the desired
number appears at the last 2
digits.)
Setting is complete when the lamp lights up
Press “ENTER” button to return to “2: Setting the
first 2 digits” (If there is no operation for 5 seconds
after the setting, the display will return to “2: Setting
the first 2 digits”.)
Setting is complete when the lamp lights up
Press “ENTER” button to return to “2: Setting the
first 2 digits” (If there is no operation for 5 seconds
after the setting, the display will return to “2: Setting
the first 2 digits”.)
EXIT: Press the “MODE/EXIT” button to cancel the setting mode.