En-2

 CAUTION

This mark indicates procedures which, if improperly per-
formed, might possibly result in personal harm to the user, or 
damage to property.

This unit must be installed by qualified personnel with a capacity certificate for handling 
refrigerant fluids. Refer to regulation and laws in use on installation place.

The installation must be carried out in compliance with regulations in force in the place 
of installation and the installation instructions of the manufacturer.

This unit is part of a set constituting an air conditioner. It must not be installed alone or 
with non-authorized by the manufacturer.

This unit contains no user-serviceable parts. Always consult authorized service person-
nel to repairs.

When moving, consult authorized service personnel for disconnection and installation 
of the unit.

Be sure to use a dedicated power circuit. 
Never use a power supply shared by another appliance.

072/090 model

• This product is conformed to IEC/EN61000-3-2.
• This product is designed for professional use.
• On the power supply connection, obtain the connection permission of the distribution 

network operator.

108/126/144/162 model

• This equipment complies with IEC 61000-3-12 provided that the short-circuit power 

Ssc is greater than or equal to following table at the interface point between the user's 
supply and the public system. It is the responsibility of the installer or user of the 
equipment to ensure, by consultation with the distribution network operator if neces-
sary, that the equipment is connected only to a supply with a short-circuit power Ssc 
than or equal to following table.

Model

Short-circuit power Ssc

AJ*108LELBH

5.456 MVA

AJ*126LELBH

2.832 MVA

AJ*144LELBH

2.832 MVA

AJ*162LELBH

3.417 MVA

162 model

• This unit must be connected to a power supply with impedance of 0.441 ohm and 

below. If the power supply does not satisfy this requirement, please consult the power 
supplier.

Do not install the unit in the following areas:
• For the installation conditions if installing in an area of high salt damage such as the 

coast, follow the Design & Technical Manual.

• Area filled with mineral oil or containing a large amount of splashed oil or steam, such 

as a kitchen. 
It will deteriorate plastic parts, causing the parts to fall or the unit to leak water. 

• Area that generates substances that adversely affect the equipment, such as sulfuric 

gas, chlorine gas, acid, or alkali. 
It will cause the copper pipes and brazed joints to corrode, which can cause refriger-
ant leakage.

• Area containing equipment that generates electromagnetic interference. 

It will cause the control system to malfunction, preventing the unit from operating 
normally.

• Area that can cause combustible gas to leak, contains suspended carbon fibers or 

flammable dust, or volatile flammables such as paint thinner or gasoline. 
If gas leaks and settles around the unit, it can cause a fire.

• Avoid installing the unit at places where it will come into contact with animals’ urine or 

ammonia.

The units are not explosion proof and therefore should not be installed in explosive 
atmosphere.

Do not use the unit for special purposes, such as storing food, raising animals, growing 
plants, or preserving precision devices or art objects. It can degrade the quality of the 
preserved or stored objects.

Ground the unit. Do not connect the ground cable to a gas pipe, water pipe, lightning 
rod, or a telephone ground cable. Improper grounding may cause electric shock.

Perform draining for the unit according to the Installation manual. Check that the water 
is properly drained.
If the drain processing is improperly installed, water may drip down from the unit, wet-
ting the furniture.

Do not touch the fins with bare hands.

Be sure not to start or stop the operation of air conditioning with power breaker. Other-
wise, it may cause malfunction or water leakage.

When setting it up near the equipment that generates electromagnetic waves and the 
equipment that generates the higher harmonics wave, be sure to take measures against 
noise. Otherwise, it may cause malfunction or failure.

When energizing to the crankcase heater, please turn on the power 12 hours or earlier 
before operation begins. When the energizing time is short, it may cause failure. Be-
sides, please do not turn off power during the busy season.

This appliance is not intended for use by persons (including children) with reduced 
physical, sensory or mental capabilities, or lack of experience and knowledge, unless 
they have been given supervision or instruction concerning use of the appliance by a 
person responsible for their safety. Children should be supervised to ensure that they 
do not play with the appliance.

2.  ABOUT THIS PRODUCT

2.1.  Precautions for using R410A refrigerant

Pay careful attention to the following points:

Since the working pressure is 1.6 times higher than that of R22 models, some of the 
piping and installation and service tools are special. (See the table in the SPECIAL 
TOOLS FOR R410A section.)
Especially, when replacing a conventional refrigerant (other than R410A) model with 
a new refrigerant R410A model, always replace the conventional piping and flare nuts 
with the R410A piping and flare nuts.

Models that use refrigerant R410A have a different charging port thread diameter to pre-
vent erroneous charging with R22, R407C and for safety. Therefore, check beforehand. 
[The charging port thread diameter for R410A is 1/2 UNF 20 threads per inch.]

Be more careful than the installation of the refrigerant (other than R410A) models, not 
to enter foreign matters (oil, water, etc.) and other refrigerant into the piping. Also, when 
storing the piping, securely seal the openings by pinching, taping, etc.

When charging the refrigerant, take into account the slight change in the composition 
of the gas and liquid phases, and always charge from the liquid phase side whose 
composition is stable.

2.2.  Special tools for R410A

Tool name

Contents of change for R22 tool

Gauge manifold

Pressure is huge and cannot be measured with a conven-
tional gauge. To prevent erroneous mixing of other refriger-
ants, the diameter of each port has been changed.
It is recommended to use a gauge manifold with a high 
pressure display range -0.1 to 5.3 MPa and a low pressure 
display range -0.1 to 3.8 MPa.

Charging hose

To increase pressure resistance, the hose material and base 
size were changed.

Vacuum pump

A conventional vacuum pump can be used by installing a 
vacuum pump adapter.
• A conventional vacuum pump can be used by installing a 

vacuum pump adapter. 

• Be sure that the pump oil does not back flow into the 

system. Use one capable for vacuum suction of -100.7kPa 
(5 Ton, -755mmHg).

Gas leakage detector

Special gas leakage detector for HFC refrigerant R410A.

2.3. Accessories

Use connecting parts as required.
Do not throw away the connecting parts until the installation has been complete.

Name and shape

Q’ty

Application

Specifications 
manual

1

Installation manual

1

(This manual)

Drain cap

9

For outdoor unit drain piping 
work

Drain pipe

1

For outdoor unit drain piping 
work

Joint pipe A

1

(090 model 

only)

For connecting gas pipe 
(L type)

Joint pipe B

1

(090 model 

only)

For connecting gas pipe 
(Straight type)

Joint pipe C

1

(090 model 

only)

For connecting liquid pipe 
(Straight type)

Joint pipe A-L

1

(108/126/

144/162 

model only)

For connecting gas pipe 
(L type)

Joint pipe B-L

1

(108/126/

144/162 

model only)

For connecting gas pipe 
(Straight type)

Push mount cable tie

2

For binding transmission cable

Grommet edging

2

For power supply cable and con-
nection cable installation.
Attach to the knockout hole.

9380545347-01_IM.indb   2

9380545347-01_IM.indb   2

11/29/2019   8:49:50 AM

11/29/2019   8:49:50 AM

Summary of Contents for AIRSTAGE AJ 072LELBH Series

Page 1: ...or authorized service personnel only Nur für autorisiertes Fachpersonal Pour le personnel de service agrée uniquement Únicamente para personal de servicio autorizado A uso esclusivo del personale tecnico autorizzato Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό Somente para o pessoal do serviço técnico autorizado Только для авторизованного обслуживающего персонала Yalnızca yetkili servis personeli iç...

Page 2: ...all the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation make sure there is no refriger...

Page 3: ... start or stop the operation of air conditioning with power breaker Other wise it may cause malfunction or water leakage When setting it up near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the p...

Page 4: ...por soot dust or debris Install the indoor unit outdoor unit power supply cable transmission cable and remote control cable at least 1 meter away from a television or radio The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoo...

Page 5: ... unit WARNING Do not touch the fins Otherwise personal injury could result CAUTION When carrying the unit hold the handles on the right and left sides and be careful If the outdoor unit is carried from the bottom hands or fingers may be pinched Hoisting method When hoisting the outdoor unit hook the rope on the outside of the foot as shown in the figure Use sufficiently strong rope to bear the uni...

Page 6: ... local rules 1 Allowable tensile stress 33 N mm2 2 Allowable tensile stress 61 N mm2 3 Endurance pressure of the pipes 4 2MPa 3 5 Installing the unit Please install the outdoor unit without slant within 0 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concre...

Page 7: ...090 96 096 Capacity kW 1 1 2 2 2 8 3 6 4 5 5 6 7 1 9 0 10 0 11 2 12 5 14 0 18 0 22 4 25 0 28 0 In the case of ARXD007GLEH equivalent to model code of indoor unit Model code 007 Capacity 2 2kW 4 3 Protection of pipes Location Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of...

Page 8: ... valves Use a hexagon wrench Liquid valve size 4 mm Gas valve size 8 mm Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclock wise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening dire...

Page 9: ...he temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself When the electrical switchboard is ...

Page 10: ...door unit Signal amplifier System controller Touch panel controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 NOTES Do not use loop wiring This may lead to parts damage and erroneous operation 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enable automatic address setting for...

Page 11: ...l 126 144 162 model 162 model How to connect wiring to the terminal Caution when wiring cable 1 Use ring terminals with insulating sleeves as shown in the figure to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no stress ...

Page 12: ...tton setting NOTES 1 The external input priority mode must be set by pressing push button on PC board of outdoor unit Refer to 7 FIELD SETTING 2 Batch stop or Emergency stop pattern can be selected by outdoor unit PC board push button Refer to 7 FIELD SETTING 3 The emergency stop function mounted in this model does not guarantee the regula tions of each country For this reason sufficient checking ...

Page 13: ...ressure 1 equivalent to 072 090 model 30 Pa 108 model 40 Pa 126 144 162 model 60 Pa 0 1 25 Prohibited Factory default 2 5 0 0 26 Prohibited Factory default 2 6 0 0 27 Prohibited Factory default 2 7 0 0 28 Prohibited Factory default 2 8 0 0 29 Prohibited Factory default 2 9 0 0 7 FIELD SETTING CAUTION Discharge the static electricity from your body before setting up the DIP switches Never touch the...

Page 14: ...ectricity meter No is set to 000 and 201 to 299 the pulses input to CN135 become ineffective Available setting number is 001 to 200 3 When the electricity meter pulse setting is set to 0000 the pulses input to CN135 become ineffective Available setting number is 0001 to 9999 4 This item is not displayed for 072 090 and 108 models 1 Turn on the power of the outdoor unit and enter standby mode When ...

Page 15: ...cedures to check the addresses 7 6 2 Procedures to enable automatic address setting on indoor units Check that the rotary switch IU AD on the indoor unit PC board is set to 00 If it is not set to 00 it means the address of that device is not set Factory default is 00 Turn on the power of the indoor and outdoor units When the system is normal nothing will be displayed on the 7 segment display When ...

Page 16: ...ocedure 1 Remove the blank caps of the gas pipe and liquid pipe and check that the valves are closed 2 Remove the charging port cap 3 Connect a vacuum pump and a pressure gauge to a charging hose and connect it to the charging port 4 Activate the vacuum pump and vacuum the indoor unit and connection piping until the pressure gauge becomes 100 7 kPa 755mm Hg Evacuate from both the gas pipe and the ...

Page 17: ... caused near electrical components in the service panel If the outdoor unit is installed at a level that is higher than the indoor unit the water that has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water to the indoor units 9 TEST RUN 9 1 Indoor unit connection check N...

Page 18: ...rror codes can be confirmed by pressing the SELECT button Example When Indoor unit capacity error E221 and Indoor unit duplicate address error E261 occurred 1 When the address of the overlap indoor unit is displayed press and hold the ENTER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SELECT but ton to switch to the next error If error ...

Page 19: ...ssor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 Outdoor unit compressor motor loss of synchroniza tion E 9 7 1 Outdoor unit fan motor 1 lock error E 9 7 4 Outdoor unit fan motor 1 undervoltage error E 9 7 5 Outdoor unit fan motor 1 temperature error protective action E 9 7 9 Outdoor unit fan motor 1 driver error E 9 8 1 Outdoor unit fan motor 2 lock error E 9 8 5 Outdoor unit fan m...