Models: AOYG30KBTB and AOYG36KBTB
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
52°C ≤ Ta
8.0 A
7.5 A
50°C ≤ Ta < 52°C
12.0 A
11.5 A
42°C ≤ Ta < 50°C
14.0 A
13.5 A
2°C ≤ Ta < 42°C
18.0 A
17.5 A
Ta < 2°C
20.0 A
19.5 A
Heating
2°C ≤ Ta
18.0 A
17.5 A
Ta < 2°C
20.0 A
19.5 A
¢
Model: AOYG45KBTB
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
52°C ≤ Ta
10.0 A
9.5 A
50°C ≤ Ta < 52°C
13.0 A
12.5 A
46°C ≤ Ta < 50°C
15.0 A
14.5 A
42°C ≤ Ta < 46°C
18.0 A
17.5 A
2°C ≤ Ta < 42°C
20.0 A
19.5 A
Ta < 2°C
24.0 A
23.5 A
Heating
2°C ≤ Ta
20.0 A
19.5 A
Ta < 2°C
24.0 A
23.5 A
8-4. Indoor unit fan motor over temperature protection
When satisfy the following conditions, the protection works.
• After the 90 seconds from the fan operation, detect less than 300 rpm for 10 seconds.
• IPM trip protection works.
• Current overload protection works.
When detecting the above condtion, recheck the condition after 6 minutes. When count the twice,
the protection works.
•
Protection contents
Reduce the static pressure 20 Pa. When it does not dissolve even the minimum static pressure
condition, work the following operation.
– Fan motor error displayed when less than 300 rpm for 10 seconds is detected after the 90 sec-
onds from the fan operation.
– Fan stop 40 seconds when IPM trip protection works.
– Fan stop 50 seconds when corrent overload protection works.
8-3. Current release control
- (04-40) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for ABYG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Page 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Page 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Page 74: ......
Page 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Page 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Page 142: ......
Page 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...