Heating mode
F zone
7°C
E zone
2°C
D zone
-7°C
C zone
B zone
A zone
-10°C
-15°C
G zone
12°C
H zone
16°C
I zone
20°C
Model name
Outdoor temperature zone
Limitation of compressor
frequency
AOYG30KBTB
AOYG36KBTB
A zone
58 rps
B zone
52 rps
C zone
43 rps
D zone
38 rps
E zone
28 rps
F zone
23 rps
G zone
20 rps
H zone
17 rps
I zone
17 rps
AOYG45KBTB
A zone
46 rps
B zone
42 rps
C zone
35 rps
D zone
32 rps
E zone
23 rps
F zone
20 rps
G zone
17 rps
H zone
13 rps
I zone
16 rps
1-5. Compressor frequency limitation by outdoor temperature