Models: AOYG30KBTB and AOYG36KBTB
Fan speed is defined by outdoor temperature and compressor frequency.
Unit: rpm
Fan step
Cooling or dry
Heating
13
830
—
12
830
—
11
740
—
10
700
830
9
650
740
8
570
690
7
570
620
6
570
590
5
570
480
4
540
410
3
480
340
2
400
270
1
270
200
S-HIGH
—
830
• When the compressor frequency increases, the outdoor fan speed also changes to the higher
speed.
• When the compressor frequency decreases, the outdoor fan speed also changes to the lower
speed.
NOTE:
After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 830 rpm
3-2. Outdoor fan control