7-10. Prevention to restart for 3 minutes (3 minutes st)
When the compressor fails to start for the number of times below, it does not enter operation status
for 3 minutes.
Retry number
18/22/24 model
50
30/36/45 model
30
Retry set number
3
When the compressor fails to start in the retry set number above, the compressor is stopped.
7-11. 4-way valve control
• If heating mode is selected at the compressor start, 4-way valve is energized for heating.
• When the air conditioner is switched between cooling and heating mode, compressor is stopped,
and the 4-way valve is switched when the 3 minutes passes and the compressor is started.
200
ms
1,500
ms
200
ms
2,000±100
ms
Compressor
4-way valve
power supply
4-way valve
polarity
4-way valve
switching
Heating mode
Cooling mode
7-12. Human sensor for energy saving
If no one enters the room for the set time, the set temperature is automatically controlled. (When
someone comes back into the room, the human sensor detect this, and automatically revert to the
original settings.)
Operation mode
Operation details
(If there is no one in the room for a while)
Cooling/Dry
The setting temperature is increased by maximum 2°C.
(Maximum setting temperature: 30°C)
Heating
The setting temperature is decreased by maximum 2°C.
(Minimum setting temperature: 16°C)
Auto
Energy saving function is performed automatically for the selected mode
(cooling/heating/dry).
Details about detection with the human sensor:
The human sensor detects whether there are people in the room by looking for movement by people
in the room.
7-10. Prevention to restart for 3 minutes (3 minutes st)
- (04-36) -
7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for ABYG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Page 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Page 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Page 74: ......
Page 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Page 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Page 142: ......
Page 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...