3. Fan control
Tr: Room temperature
Ts: Setting temperature
3-1. Indoor fan control
¢
Fan speed
Indoor fan speed is defined as below.
Operation
mode
Fan mode
Speed (rpm)
18
22
24
30
36
45
Heating
HIGH
950
1,020
970
1,090
1,090
1,120
MED+
900
940
890
1,000
1,020
1,030
MED
880
880
810
900
920
940
LOW-
800
800
720
800
830
870
QUIET
750
750
620
680
700
740
Cool air
prevention
500
500
500
500
500
500
S-LOW
300
300
300
300
300
300
Cooling/Fan
HIGH
950
1,020
970
1,090
1,120
1,140
MED
880
880
810
900
920
940
LOW
800
800
720
800
830
870
QUIET
750
750
620
680
700
740
Soft quiet
500*
1
500*
1
500*
1
500*
1
500*
1
500*
1
S-LOW
300*
2
300*
2
300*
2
300*
2
300*
2
300*
2
Dry
X zone: 750
J zone: 750
X zone: 750
J zone: 750
X zone: 620
J zone: 620
X zone: 680
J zone: 680
X zone: 700
J zone: 700
X zone: 740
J zone: 740
*1: Fan mode only
*2: Cooling mode only
¢
Fan operation
Airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH while indoor unit fan
only runs.
When fan mode is set at AUTO, it operates on MED fan speed.
¢
Cooling operation
Switch the airflow AUTO, and indoor fan motor will run according to room temperature, as below.
On the other hand, if switched in HIGH—QUIET, indoor motor will run at a constant airflow of COOL
operation modes QUIET, LOW, MED, HIGH as shown in “Fan speed” above.
Airflow change over (Cooling: Auto)
When room
temperature rises
When room
temperature drops
Tr - Ts ≥ 2
°C
HIGH mode
MED mode
LOW mode
2
°C
> Tr - Ts ≥ 1
°C
1
°C > Tr - Ts
Tr - Ts ≥ 2.5
°C
2.5
°C
> Tr - Ts ≥ 1.5
°C
1.5
°C > Tr - Ts
3-1. Indoor fan control
- (04-15) -
3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for ABYG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Page 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Page 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Page 74: ......
Page 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Page 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Page 142: ......
Page 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...